Инструкция на Подпотолочные сплит-cистемы серии MCM D/DR
Подпотолочные сплит-cистемы модели MCM020D/DR, MCM025D/DR, MCM030D/DR, MCM040D/DR, MCM050D/DR Полный сервис-мануал.
Загружаем документ…
Текст инструкции
-
Catalog 2110B
-
Special features
Ultra Slim New Stylish Design Profile This unit is contemporary in design and match even the most up to date interior decor. The slim, round profile and compact design of this unit adds a touch of elegance to every decor. No indoor connection pipe and hanger bracket are visible. Ceiling And Floor…
-
Specifications
Cooling only MODEL INDOOR UNIT OUTDOOR UNIT COIL FIN INDOOR UNIT COMP. MCM050D MMC050B MLC050C 12,600 12,600 14,654 14,654 50,000 50,000 1,120 / 31.8 4 POLES X 145W 240 1.04 S.B.C 740 / 21.0 4 POLES X 95W 132 0.58 S.I.G.C 1,120 / 31.8 4 POLES X 145W 240 1.04 S.I.G.C 9.52 / 3/8 0.35 / 0.014 ALUMINIUM…
-
Heat Pump
MODEL INDOOR UNIT OUTDOOR UNIT COIL TUBE COIL FIN PIPE OUTDOOR UNIT FAN COMP INDOOR UNIT FIN TUBE FAN NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY POWER SOURCE REFRIGERANT / CONTROL AIR FLOW FAN MOTOR RATED INPUT POWER RATED RUNNING CURRENT MATERIAL DIAMETER THICKNESS MATERIAL THICKNESS ROW FIN…
-
Outlines and dimensions
-
Outdoor unit
-
Model : MLC 040/050C, MLC 030/040/050CR
Caution Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places. 7
-
Wiring diagrams
Model : MCM 020/025D - MLC 020/025B 8
-
Model: MCM 020DR - MLC 020BR
-
Model: MCM 030DR - MLC 030CR
-
Model: MCM 040DR - MLC 040CR
-
Installation
Caution Sharp edges and coil surface are potential injury hazard. Avoid from contact with them. (1) INSTALLATION OF INDOOR UNIT Preliminary Site Survey • Electrical supply and installation shall conform to the local authority (eg. National Electrical Board). • Voltage supply fluctuation must not…
-
Please ensure that the following steps are taken
• Cheek the gradient for drainage flow as recommended in Figure B. • Provide clearance for easy servicing and optimal air flow as shown in Figure B. • The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air. • Do not install the indoor…
-
Installation - Ceiling Exposed Type
STEP 1 Remove air intake grille, side panel, side close-up and hanger bracket from the unit; see Fig E. Figure E STEP 2 Position the hanger rods as per Fig B and install the hanger bracket; see Fig F. Figure F STEP 3 Hanger up the unit and tighten the bolt, after completed the piping and drain pipe…
-
Installation - Floor Standing Type
STEP 1 Remove air intake grille, side panel, side close-up and side panel from the unit; see Fig E. STEP 2 Position the floor support and wall mounting bracket as per Fig B. install the unit; see Fig 1. * Wall mounting bracket will be supplied upon request. Fig I STEP 3 Two type of piping and drain…
-
(2) Installation Of Outdoor Unit
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfil the following requirements:- • • • • • • Install the condensing (outdoor) unit in away such that hot air…
-
MMC SERIES
ALL MODELS Minimum Distance A 300mm B 1000mm C 300mm (3) Refrigerant Piping Maximum Pipe Length And Maximum Number Of Bends • When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant flow increases…
-
(4) Wiring
Electrical Connections • Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES for field wiring rules. Be sure that installation comply with such rules and regulations. General Precautions • Ensure that the rated voltage of the unit…
-
(6) Additional Charge
• The refrigerant gas has already charged into the outdoor unit. For the piping length of 5m. Additional refrigerant charge after vacuuming is not necessary. • When the piping length is more than 5m, please use the table below (unit in gram). MODEL 7m 10m 15m (7) Overall Checking • Ensure the…
-
(8) Standard Operating Condition
Cooling Only Unit Temperature minimum indoor temperature maximum indoor temperature minimum outdoor temperature maximum- outdoor temperature Ts °C 19.4 26.7 19.4 46.0 Th °C 13.9 19.4 13.9 24.0 Heat Pump Unit Temperature minimum indoor temperature maximum indoor temperature minimum outdoor…
-
Servicing and maintenance
Warning Disconnect from Main Supply before Servicing the air conditioner The unit is designed to give a long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Components Air Filters Maintenance Procedure…
-
The design of the MLC outdoor series allows servicing to be carried out readily and easily. The removal of the top side, front and back panel make almost every part accessible. Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface once…
-
Troubleshooting
When any air-conditioner malfunction is noted, immediately switch off the power supply to the unit, and contact the local dealer, if necessary. Some simple troubleshooting tips are given below : FAULT 1. Fan does not work 3 minutes after starting CAUSE • Protection against the frequent starting.…
-
Diagnosis By Flow Chart (Cooling Only)
The following chart are efficient checking procedures for troubleshooting when these fan-coil units, are coupled with the condensing units using standard wiring. For dual circuited models, perform the procedures for each circuit. No Cooling : Check : Faulty : Cause Remedy No Cooling ( Compresor Does…
-
Insufficient Cooling
Insufficient Cooling Compressor Cycling Cycling On Dual Pressure Switch Tripping High Discharge Pressure or Low Suction Pressure See "High Discharge Pressure" or "Low Suction Pressure" Clogged Capillary or Pressure Switch Repair Clogging and Replace The Switch If Required Switch Faulty Running…
-
High Suction Pressure
High Suction Pressure Low Evaporator Air Inlet Temperature Excessive Fresh Air Intake Reduce The Fresh Air Intake Insufficient Duct Insulation Reinforce The Duct Insulation Defective Compressor Valve Overcharged Refrigerant Change Or Repair The Compressor Purge The Refrigerant Low Suction Pressure…
-
For Heat Pump Models
By means of pressure readings : = = High Side Low Side High Side Low Side High Side Low Side Too High PROBABLE CAUSE A Little High Normal Circuit Too Low Data A Little Low PRESSURE 1. Overcharged with refrigerant. 2. Non-condensable gases in refrigerant circuit (e.g. oil). 3. Obstructed…
-
The most common causes of air conditioner failure to “start" are
a) Voltage not within ±10% of rated voltage. b) Power supply interrupted. c) Control settings improper. d) Air conditioner is disconnected from main power source. e) Fuse blown or circuit breaker off. ii) Diagnosis Of Refrigerant Circuit / Application There might be some cases where the unit starts…
-
DOP : 0299
Americas - 13600 Industrial Park Boulevard, P.O. Box 1551, Minneapolis, MINI 55440 USA (612) 553-5330 Asia - Jalan Pengapit 15/19, P.O. Box 7072, 40702 Shah Alam, Selangor Darul Eshan, Malaysia - Tel: 6-03-5594922 - Fax: 6-03-5506980 - Telex: MA 38521 Europe - 42 Cours Jean Jaurès - 17800 Pons…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.