Инструкция на Кондиционеры серии LV
Кондиционеры серии LV-B1860RL, LV-B2460RL (применительно к новым хладагентом R-410A). Инструкция по монтажу и эксплуатации.
Смотрите также: Инструкция по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
Room Air Conditioner
-
Functions
Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature •Room temperature sensor. (Thermistor) Room temperature control •Maintains the room temperature in accordance with the Setting Temp. Starting Current Control •Indoor fan is delayed for 5 seconds at the starting. Time…
-
Remote Controller
Operation ON/OFF Operation Mode Selection (Cooling (Heating model only) model only) Cooling Operation Mode.( ) Auto Operation Mode.( Soft Dry Operation Mode.( ) Heating Operation Mode.( Fan Speed Selection (Low) (Med) (High) (CHAOS) Room Temperature Display : High:39°C ↔ LOW:11°C Temperature Setting…
-
Product Specifications (Cooling & Heating)
Model Name Item LV-B1860RL LV-B2460RL Unit Cooling Capacity Btu/h(kcal/h) 20,000(5,040) 24,000(6,048) Heating Capacity Btu/h(kcal/h) 20,000(5,040) 24,000(6,048) Moisture Removal ℓ/h 2.5 3.5 Power Source Air Circulation ø, V, Hz Indoor 1ø, 220-240V~, 50Hz m3/min Outdoor Input Cooling W Heating…
-
Dimensions
-
(2) Outdoor Unit
-
Refrigeration Cycle Diagram
• LV-B1860RL • LV-B2460RL INDOOR UNIT OUTDOOR UNIT LIQUID SIDE CAPILLARY TUBE CHECK VALVE CAPILLARY TUBE HEAT EXCHANGER HEAT EXCHANGER GAS SIDE REVERSING VALVE COOLING HEATING COMPRESSOR Pipe size(Diameter: ) Piping length(m) Elevation(m) MODEL Gas Liquid Rated Max Rated Max LV-B1860RL 1/2" 1/4"…
-
Wiring Diagram
-
Operation Details
(1) The function of main control 1. Time Delay Safety Control • 3min… The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle. (Protection of compressor) … • 5sec Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.…
-
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following Intake Air temp. COMP. ON (SET TEMP.+0.5°C) COMP. OFF (SET TEMP. -0.5°C) More than More than 3 minutes 3 minutes INDOOR FAN Selecting fan…
-
5. Auto Operation
• The operation procedure is as following. (Cooling & Heating Model) Press Start/Stop Button Select Auto Operation Mode Check the Room temperature Operation mode Indoor fan speed Setting temperature are automatically decided by Fuzzy rule. Intake-air temperature below 21°C Operation Mode Heating…
-
• Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature. - Compressor ON temperature; Setting temperature +1°C - Compressor OFF temperature; Setting temperature -0.5°C • Auto Operation for Heating. Intake Air temp. below 20°C over 20℃~below 21°C Setting temp. 20°C Intake…
-
6. Natural wind by CHAOS logic
For more fresh feeling than other fan speed mode, press the indoor fan Speed Selector and set to CHAOS mode. In this mode, the wind blows like natural breeze by automatically changing fan speed according to the CHAOS logic. Intake Air temp. Setting CHAOS Natural wind Cooling on temp. (Setting…
-
7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. • For Heating Model Indoor piping temp. 28°C 26°C Intake Air temp. Setting temp. +3.0˚C (Compressor OFF) Setting temp. (Compressor ON) minimum 30sec. minimum 3min. minimum 1min.…
-
9. Deice Control
• Deicing operation is controlled by timer and sensing the outdoor piping temperature. • The first deicing starts only when the outdoor pipe temperature falls below -6°C after 30 minutes passed from starting of heating operation. • Deicing ends after 5 minutes passed from starting of deice operation…
-
11. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch. • The standard conditions are as following. Heat pump Model Room Temp≥ 24°C 21°C Room Temp≤24°C Room Temp 21°C Operation Mode Cooling Soft Dry Heating FAN Speed High Soft Dry Rule High Setting Temp. 22°C…
-
Display Function
1. Heating Model Operation Indicator • Coolling, Soft Dry, Fan, Heating Timer Indicator • Timer Mode Sleep Timer Indicator • Sleep Mode Deice Indicator • Hot-start, Deice Note) For normal operation after checking by test mode, you should press SW1 nine times for resetting or reconnect the power…
-
Installation
1. Installation of Indoor, Outdoor Unit 1. Selection of the best location More than 20cm 1) Indoor unit More than 20cm • There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be…
-
2. Indoor unit installation
■ Before Installing, prepare Installation Plates • 'Installation Plates' are attached at the bottom of indoor unit. Detach them by removing each 3 screws at both sides. • Detach 'Side Plate (R,L)' by removing each 2 screws on both sides. • Pull the upper right and left side of 'Inlet Grille' to the…
-
• Insert the nuts and washer onto the suspension bolts
for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the anchor-nuts firmly. • Secure the Installation plates onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers. Anchor nut 1) Ceiling Nut Washer Suspension bolts Suspension bolts…
-
CAUTION
1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 7mm. 3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be…
-
• Secure the unit to the Installation Plates with four M8
bolts and washers. R • Before working, refer to "Connecting pipe and cable to Indoor Unit" on page 32. • Hook up the Inlet Grille Hook to the cabinet. • Hang the Inlet Hanger to the screw. Inlet hanger R Hook Cabinet Bottom • Fit the projection hooks of the side plates to the 'Side Panel' and the…
-
2) Installation on the Wall
• Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor nut on the wall. 1076 mor e th 260 an 265 • Drill the piping hole on the wall…
-
Install the Indoor unit onto Installation Plate
• Insert 2 hooks on the both left and right side of the unit to the inner slot (wall side) of the Installation Plate. Inner slot • Secure the unit to the Installation Plate with four M8 bolts and washers. R • Before working, refer to "Connecting pipe and cable to Indoor Unit" on page 32. • Hook up…
-
3) Installation on the floor
From the left wall more than 760mm Installation of Mount Bracket. • Select and mark the position for Mount Brackets and the piping hole. • Drill the hole for the anchor nut on the wall. • Drill the piping hole using a ø70 hole-core drill. • Secure the Mount Brackets on the wall with four M4 screws.…
-
2. Piping and Drainage of Indoor Unit
2-1. Preparation of Piping Pipe cutter 1. Cut the pipes and the cable. • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than measured distance. • Cut the cable 1.5m longer than the length of…
-
2-2. Installation on the ceiling
1) Connecting the pipes to the indoor unit R The pipe can be connected to right side, bottom or back of the unit. 2 1. For the Right Side Piping • After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers. • Finally, tighten the…
-
2-3. Installation on the wall or floor
1) Connecting the pipes to the indoor unit 1. For the Right Rear Piping • Remove the knock-out at the back side of the cabinet. • After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers. • Finally, tighten the flare nut with…
-
3. Connecting Pipes to the Outdoor Unit
1) Connecting the pipes to the Outdoor unit 1. Align the center of the pipings and sufficiently tighten the flare nut with fingers. 2. Finally, tighten the flare nut with torque wrench until the wrench clicks. • When tightening the flare nut with torque wrench, ensure the direction for tightening…
-
5. Connecting Cables between Indoor Unit and Outdoor Unit
R 1) Connecting cables to the Indoor Unit 1) Remove the Air guide - L by loosening 2 screws after removing the Inlet grille from the Indoor unit. 2) Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of…
-
3) Connecting the cable to Outdoor Unit
Outdoor unit 1. Remove the Cover control from the unit by loosening a screw. Connect the wires to the terminals on the control board individually as following. Terminal block Over 5mm Holder for power supply cord 2. Secure the cable onto the control board with the holder (clamper). 3. Refix the…
-
4) Form the pipings
Seal a small opening around the pipings with gum type sealer. 1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings) • If you want to connect an additional drain hose, the end of the drain-outlet should keep distance…
-
6. Air Purging of the Piping and Indoor Unit
1) Air purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5.…
-
3. Evacuation
• Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The…
-
7. Test running
1) Connection of power supply 1. Connect the power supply cord to the independent power supply. • Circuit breaker is required. 2. Prepare the remote control. • Insert two batteries provided. Remove the battery cover from the remote controller. • Slide the cover according to the arrow direction.…
-
Operation
(1) Name and Function-Remote controller 1) Cooling Model Remote Controller 1 OPERATION DISPLAY Displays the operation conditions. Signal transmitter. 2 START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. Transmits the signals to the room air…
-
2) Heat Pump Model
Remote Controller 1 OPERATION DISPLAY Displays the operation conditions. 2 START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. Signal transmitter. Transmits the signals to the room air conditioner. MODE SELECTION BUTTON 3 OPERATION Used to…
-
Disassembly of the parts (Indoor unit)
Warning : Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”. 1. Remove the air filter. • Pull the inlet grille slightly toward you. • Pull out the air filter. (2 pieces) R Inlet Grille 2. Remove the girlle from chassis • Remove the screws…
-
4. Remove air guide upper, crossflow fan and
motor. • Remove the screws of both sides and center securing the upper air-guide. • Remove 2 screws fastening the bracket of door switch. Door Switch R • Remove a bearing assembly by removing a screw and the bearing cover. • Remove 4 screws securing the motor cover. • Loosen the screw securing the…
-
6. Remove the front panel
• Remove the screws of both sides fixing the front panel. • Push the upper side of front panel strongly to pull out the front panel from the inner hook of diffuser frame. • Pull down the front panel carefully not so as to harm the display PCB wires and thermistor wires. Diffuser frame Diffuser frame…
-
9. Remove the vane-upper, vane-lower and step
motor. • Remove 2 screws securing the step motor assembly and pull it out from the vanes carefully. • Unhook the vanes from the vane supporter and remove the upper vane and lower vane by pulling the center of vanes with care. Step Motor Vane Supporter Lower Vane Upper Vane 10. Remove the drain pan…
-
2-way, 3-way Valve
2-way Valve (Liguid Side) Hexagonal wrench (4mm) Flare nut 3-way Valve (Gas Side or Liquid Side) Valve cap Open position Flare nut Closed position Open position Closed position To piping connection To piping connection To outdoor unit 1. Pin Service Service port cap port To outdoor unit Works Shaft…
-
1. Pumping down
Liquid side Indoor unit 2-Way valve Open Outdoor unit Gas side Closed 3-Way valve Lo CLOSE CLOSE Purge the air • Procedure (6) Immediately set the 3-way valve to the closed position when the gauge indicates 1Kg/cm2G and stop operation. (1) Confirm that both liquid side and gas side valves are set to…
-
2. Evacuation
Liquid side Indoor unit Outdoor unit 2-Way valve Open 3-Way valve Open Gas side Vacuum pump Lo OPEN CLOSE • Procedure (1) Connect the vacuum pump to the charge set’s center hose CAUTION Use vacuum pump equipped with check value applied to be prevented from flowing backward. (2) Evacuation for…
-
3. Gas Charging
(After Evacuation) Liquid side Indoor unit 2-Way valve Open Outdoor unit Gas side Open 3-Way valve Check valve Charging cylinder R-410A Lo OPEN CLOSE • Procedure \ (1) Connect the charge hose to the charging cylinder. – Connect the charge hose which you disconnected from the vacuum pump to the valve…
-
4. Additional gas charging
(Gas leakage) • When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suction pressure. • Use the graph or the equation below to get operating suction pressure according to indoor and outdoor temperature. Suction pressure was measured at 3-way…
-
Cycle Troubleshooting Guide
Trouble analysis 1. Check temperature difference between intake and discharge air and operating current. Temp. Difference Operating Current Temp. difference Current : approx. 0°C : less than 80% of rated current All amount of refrigerant leaked out Check refrigeration cycle Temp. difference Current…
-
Electronic Parts Troubleshooting Guide
-
Possible Trouble 2
Is it DRY mode? : The indoor fan does not operate. YES Does the temperature set all right? NO Is it the HOT mode? Adjust set temperature YES YES Does the temperature set all right? NO Adjust set temperature YES NO Is IC02M operated normally? NO NO Exchange IC02M YES Is the each S.S.R any problem?…
-
Possible Trouble 3
Is IC01M operated normally? : Up/Down Air direction louver does not operate. NO Exchange IC01M YES Is the PIN 1 of CN-UP/DOWN DC12V? NO Check the main P.C.B DC12V pattern YES Check the step motor and connector (CN-UP/DOWN 1,2) Possible Trouble 4 Is the battery consumed much? : Remote controller does…
-
Possible Trouble 5
Is 4way-valve operated? : Ineffective Heating NO Check RY-4WAY YES Is IC02M operated normally? NO Exchange IC02M YES Check the RY-4WAY and 4way-valve Possible Trouble 6 Is the F/OP key any problem? : The unit does not operate by forced operation switch. YES Exchange F/OP key NO Check P.C.B pattern…
-
Electronic control device
-
Schematic Diagram
-
1. Indoor Unit Exploded View and Replacement Parts List
-
Parts List (Heat Pump Models)
-
No
-
Parts List
-
May, 2000 Printed in Korea