Инструкция на Кондиционеры серии LK-HC
Кондиционеры серии LK-0580HC, LK-0580CC, LK-0880HH, LK-0880CH, LK-1080HH, LK-1080CH, LK-1580HH, LK-1580CH, LK-2080CH. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
Single Packaged
-
General Data
Table-1 Nominal ton Models Electrical Data Performance Features Compressor Outdoor Coil ARI Net Cooling Capacity Voltage M.C.A(with standard motor) Cooling Power Input Cooling Air Circulation Nominal CFM EER Cooling Sound Rating Cooling Wired Remote Controller Time Delay Safety Function Cooling…
-
Table-2
Nominal ton Models Electrical Data Performance Features Compressor Outdoor Coil ARI Net Cooling Capacity Voltage M.C.A(with standard motor) Cooling Power Input Cooling Air Circulation Nominal CFM EER Cooling Sound Rating Cooling Wired Remote Controller Time Delay Safety Function Cooling Operation…
-
Table-3
Nominal ton Models Capacity HEAT-PUMP (Ton) ARI Net Cooling Capacity Heating Capacity Electrical Data Voltage M.C.A(with standard motor) Power Input Performance Features Compressor Outdoor Coil Air Circulation EER Sound Rating Wired Remote Controller Time Delay Safety Function Cooling Operation Mode…
-
Performance data
Supply Fan Performance LK-0580HC/0580CC(SI) Table-1 High Speed L/s 1038 1085 1133 Mid Speed Low Speed ESP BkW ESP BkW ESP BkW 22.27 19.68 17.09 14.49 11.90 9.30 6.71 4.12 0.38 0.41 0.45 0.48 0.52 0.56 0.59 0.63 21.19 17.25 13.32 9.39 5.46 1.53 - 0.33 0.37 0.40 0.43 0.47 0.50 - 7.52 0.75 - 0.38 0.42…
-
Table-3 L/s External Static Pressure(inches of water) 2.5 5.1 7.6 10.2 12.7 15.2 17.8 20.3 22.9 25.4 31.8 38.1 RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW 982 645 0.19 668 0.24 691 0.28 714 0.33 738 0.38 761 0.42 784 0.47 807 0.51 830 0.56 854 0.6…
-
Table-6
CFM Supply Fan Performance LK-1080HH/1080CH (English) External Static Pressure(inches of water) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3Hp STANDARD MOTOR & DRIVE 2720 609 0.53 615 0.53 623 0.62 632…
-
Table-7
L/s Evaporator Fan Performance LK-1080HH/1080CH (SI) External Static Pressure(mm aq.) 2.5 5.1 7.6 10.2 12.7 15.2 17.8 20.3 22.9 25.4 27.9 30.5 RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW 3Hp STANDARD MOTOR & DRIVE 1284 609 0.40 615 0.43 623 0.47…
-
Table-9
CFM Evaporator Fan Performance LK-1580CH/1580HH (English) External Static Pressure(inches of water) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 4Hp STANDARD MOTOR & DRIVE - 624 1.21 641 1.28 658 1.36…
-
Table-10
L/s Evaporator Fan Performance LK-1580HH/1580CH (SI) External Static Pressure(mm aq.) 2.5 5.1 7.6 10.2 12.7 15.2 17.8 20.3 22.9 25.4 27.9 30.5 RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW - 624 0.90 641 0.96 658 1.01 674 1.07 691 1.12 708 1.18 725…
-
Evaporator Fan Performance LK-2080CH (English)
Table-12 CFM External Static Pressure(inches of water) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 5Hp STANDARD MOTOR & DRIVE - 477 1.18 502 1.34 526 1.51 549 1.68 573 1.87 598 2.08 620 2.30 644 2.50…
-
Table-13 L/s External Static Pressure(mm aq.) 2.5 5.1 7.6 10.2 12.7 15.2 17.8 20.3 22.9 25.4 27.9 30.5 RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW - 477 0.88 502 1.00 526 1.13 549 1.25 573 1.39 598 1.55 620 1.72 644 1.86 3020 - - - - - - - 3398…
-
Table-15
-
Table-17
-
Electrical Requirements
-
Table-20
-
Dimensions
-
LK-0880CH/0880HH
-
LK-1080CH/1080HH
-
LK-1580CH/1580HH
-
LK-2080CH
-
7.5~10 Ton Accessories
-
LK-0580HC
-
LK-0580CC
-
LK-0880HH
-
LK-0880CH
-
LK-1080HH
-
LK-1080CH
-
LK-1580HH
-
LK-1580CH
-
LK-2080CH
-
Troubleshooting Guide
PACKAGE AIR CONDITIONER VOLTAGE LIMITS NAME PLATE RATING MINIMUM MAXIMUM 380 - 415V 342V 456V 1. No cooling and heating operation performed 1) Both the blower and the compressor do not work WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts except the unit • Electric supply interrupted •…
-
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Motor • Over-heated • Wire short Check how it is insulated. Repair or replace it. Electric Wiring Cut off of wiring Check it with a tester. Rewiring or repair. Check it with tester. Replace it. Short circuited on operation Capacitor Defected 4) Only…
-
2. The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Outdoor coil Coil is dirty *1 Checking Wash it by means of something like chemical washing. In-condensable gas blended. Air intruded into the refrigerant pipe line *1 In the event that difference between the saturating temperature corresponding to high…
-
3. The unit is working, but not cooling and heating sufficiently
(Both blower and compressor are working) WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Load Much Cooling or Heating load Heat load increased. Window or door has many cracks or gaps. Do necessary disposal respectively. Air flow Obstacle disturbs Intake of uniform airflow. Checking Correct it. Short…
-
Electronic parts Troubleshooting Guide
Possible trouble 1 Is the input voltage of transformer AC220V? : The unit does not operate. NO 1. Check the Fuse. 2. Check the wiring of AC220V. NO 1. Exchange the transformer. 2. Check the connector of transformer. YES Is the output voltage of transformer AC24V & AC13V? YES Is the output voltage of…
-
Possible trouble 3
: Key input of remote-controller does not respond. Is the connection between MAIN PCB and remote-controller correct? NO 1. Check or repair Connector wiring. 2. Exchange the Connector. YES 1. Replace the pressed key. 2. Exchange the Knob or Key. YES Is any key on the remote-controller keeping…
-
Possible trouble 5
Is the unit operating? : No cooling operation performed. NO 1. Press power ON/OFF button. YES Is the cooling mode? NO 1. Press cooling operation key. 2. After reenergizing power supply, press power "ON/OFF" button. NO 1. Set following. 'Set Temp. < Room Temp.' YES Set Temp. < Room Temp.? YES Is the…
-
Possible trouble 6
Is the heater operation? : No heater operation performed. NO 1. Select heater operation mode. YES Is the heater LCD "ON"? NO 1. Reconnecting power supply. Press Heater Key. NO 1. Set following. 'Set temp. > Room temp.' YES Set temp. > Room temp.? YES Is the output voltage of IC02D on the MAIN PCB…
-
Possible trouble 7
Is the indoor fan operation? : No humidifier operation performed. 1. Press cooling or fan operation or heater operation key. NO YES Is the HUMID LCD "ON"? NO 1. Press humidifier Key. YES Is the output voltage of IC02D on the MAIN PCB DC5V? NO 1. Check or exchange IC01D. IC02D on the MAIN PCB. YES Is…
-
Possible trouble 8
Is the unit operating? : Indoor motor does not operate. NO 1. Press power ON/OFF button. 2. Reconnect the power supply. YES Is the output voltage of IC02M's 14PIN on the MAIN PCB 0V? NO 1. Check or exchange IC01M. YES Is the voltage between 1PIN(IN) of CN-FAN(IN) and NEUTRAL 220V? NO 1. Check or…
-
Possible trouble 10
Is the unit operating? : No heating operation performed. NO 1. Press power ON/OFF button. YES Is the heating mode? NO 1. Press heating operation key. 2. After reenergizing power supply, press power "ON/OFF" button. NO 1. Set following. 'Set Temp. > Room Temp.' YES Set Temp. > Room Temp.? YES Is the…
-
Possible trouble 11
Is the heater operation? : No heater operation performed. NO 1. Select heater operation mode. YES Is the heater LCD "ON"? NO 1. Reconnecting power supply. Press Heater Key. NO 1. Set following. 'Set temp. > Room temp.' YES Set temp. > Room temp.? YES Is the output voltage of IC02D on the MAIN PCB…
-
Features of Controller
1. Main Controller Circuit Diagram — 45 —
-
2. Feature of Main Controller
-
3. Feature of Remote-Controller PCB ASS'Y
4. Feature of Remote-Controller LCD — 47 —
-
5. Error Mode & Corrective Method
Error mode Cause of error Sensing condition of error F01 OPEN/SHORT of Voltage of sensing: Over 4.8V room temp. Voltage of sensing: Less than sensor 0.5V F02 OPEN/SHORT of Voltage of sensing: Over 4.8V indoor pipe temp. Voltage of sensing: Less than 0.5V sensor Communication Error Method of SVC…
-
9. Explanation of principal function
■ Flow Chart START(Power supply) YES 1. Initialize "micom". 2. A/D convert. 3. Main PCB: Waiting cooling operation. 4. Remote controller: Waiting input. Dehumidification Mode? A NO Heater operation mode? YES YES Power ON? YES NO Dehumidification operating NO Set Temp. > Indoor Temp. YES YES NO…
-
Exploded View and Replacement Parts List
-
PART NO
-
2. LK-0880HH/0880CH
• Exploded View — 53 —
-
PART NO
-
3. LK-1080HH/1080CH
• Exploded View — 57 —
-
PART NO
-
4. LK-1580HH/1580CH
-
PART NO
-
5. LK-2080CH
• Exploded View — 65 —
-
PART NO
-
таблицы и схемы — в просмотре
-
Specification of Components
-
LK-1080CH
-
October, 2000 Printed in Korea
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.