ENGLISH
ITALIANO ESPAÑOL FRANÇAIS INSTALLATION MANUAL AIR CONDITIONER P/NO : 3828A22231A GREEK TYPE : WALL MOUNTED DEUTSCH • Please read this installation manual completely before installing the product. • Installation work must be performed in accordance with the national wiring standards by authorized…
-
This symbol indicates the possibility of death or serious injury
This symbol indicates the possibility of injury or damage to properties only. ■ The meanings of the symbols used in this manual are as shown below. Be sure not to do. Be sure to follow the instruction. ■ Installation Do not use damaged power cords, plugs, or a loose socket. For electrical work…
-
Be cautious when
unpacking and installing the product. For installation, always contact the dealer or an Authorized Service Center. Do not install the product on a defective installation stand. • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator. •…
-
Grasp the plug to remove
the cord from the outlet. Do not touch it with wet hands. Do not place a heater or other appliances near the power cable. • There is risk of fire or electrical shock. • There is risk of fire or electrical shock. • There is risk of fire and electric shock. Do not allow water to run into electric…
-
Do not open the inlet grill of
the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) When the product is soaked (flooded or submerged), contact an Authorized Service Center. Ventilate the product from time to time when operating it together with a stove, etc. • There is risk of…
-
Use two or more people to
lift and transport the air conditioner. Do not install the product where it will be exposed to sea wind (salt spray) directly. • It may cause a problem for your neighbors. • Avoid personal injury. • It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins…
-
Always insert the filter
securely. Clean the filter every two weeks or more often if necessary. Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in. Do not drink the water drained from the unit. • A dirty filter reduces the efficiency of the air conditioner and could…
-
Introduction
Introduction This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that may cause harm to the air conditioner. NOTICE This symbol indicates special notes. Features Air Filter Signal Receptor Front Panel Plasma Filter Power Cord Air Discharge Air Intake Vents…
-
Read carefully, and then follow step by step
Installation Parts Installation guide map Type "A" screw and plastic anchor Type "B" screw Remote control holder Installation Tools Figure 10 Room Air Conditioner Name Figure Name Screw driver Ohmmeter Electric drill Hexagonal wrench Measuring tape, Knife Ammeter Hole core drill Leak detector…
-
Installation Map
ENGLISH NOTICE Installation parts you should purchase. More than 20cm More than 50cm (Left and right are identical) Sleeve Bushing-Sleeve Putty(Gum Type Sealer) Bend the pipe as close as possible on the wall but be careful so that it may not break. Vinyl tape (Wide) Saddle • To carry out the…
-
Select the best Location
Indoor unit 1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit. 3. Make sure that condensation drainage can be conveniently routed away. More than 50cm More than 20cm 4. Do not install near a doorway. 5. Ensure that the interval…
-
Piping Length and Elevation
GAS LIQUID Standard Length (m) 9k, 12k 3/8" 1/4" 7.5 14k 1/2" 1/4" 7.5 Indoor unit Additional Max. Max. Elevation B (m) Length A (m) Refrigerant (g/m) Outdoor unit Outdoor unit A B A Outdoor unit Indoor unit Oil trap B A Indoor unit B If piping length is more than 5m CAUTION: Capacity is based on…
-
Preparing Work for Installation
Open panel front 1. Pull the upper part of the front panel. 2. Lift up the panel. 3. To detach the front panel, remove the two screws at the lower part. 4. Detach the front panel from the body. 5. To detach the panel, disconnect the connector at the upper part. Panel Front Connector Cover pipe and…
-
Fixing Indoor Unit
INSTALLATION GUIDE MAP 2. Look at suited horizon by horizontal meter on the horizontal setting line, and fix lightly the map by adhesive tape. Horizontality 3. Make a hole with a diameter of 6mm and depth of 30-35mm by piercing a screw point. IN ST AII AT IO N IN ST AL LA TIO N GU ID EM AP 4. Drill…
-
Flaring Work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. Cutting the pipes and the cable. 1. Use the piping kit accessory or the pipes purchased locally. 2. Measure the distance between the indoor and the outdoor unit. Copper pipe…
-
Check
1. Compare the flared work with the figure by. Smooth all round Inside is shiny without scratches = Improper flaring = Inclined Surface Cracked Uneven damaged thickness Even length all round Connecting the Piping Indoor Preparing the indoor unit's piping and drain hose for installation through the…
-
Connecting the piping with the indoor
unit and drain hose with drain pipe 1. Align the center of the pipings and sufficiently tighten the flare nut by hand. Indoor unit tubing Flare nut Pipings 2. Tighten the flare nut with a wrench. Outside diameter mm inch Ø6.35 1/4" Ø9.52 3/8" Ø12.7 1/2" Ø15.88 5/8" Ø19.05 3/4" Torque kgf.m 1.8~2.5…
-
CAUTION: Installation Information
For right piping. Follow the instruction below. • Press on the upper side of clamp and unfold the tubing to downward slowly. Bad case • Following bending type from left to right may cause damage to the turbing. Installation Manual 19 ENGLISH Good case
-
Outdoor
Align the center of the pipings and sufficiently tighten the flare nut by hand. Finally, tighten the flare nut with torque wrench until the wrench clicks. Outdoor unit • When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Outside…
-
Connecting the Cables
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) CAUTION: • The above…
-
Outdoor
1. Remove the control cover from the unit by loosening the screw. Connect the wires to the terminals on the control board individually. Outdoor Unit CASE 1 1(L) 2(N) 3 CASE 2 4 1(L) 2(N) 3 4 2. Secure the cable onto the control board with the cord clamp. 3. Refix the control cover to the original…
-
Checking the Drainage
ENGLISH To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Drain piping 1. The drain hose should point downward for easy drain flow. Downward slope 2. Do not make…
-
Forming the Piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes. Seal small openings around pipings with a gum type sealer. • If you want to connect an additional drain hose, the end of the drain outlet should be routed above…
-
Air Purging
The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5. Water may lead…
-
Soap water method
1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. 3. To open the 2-way valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 sec, and close it. 4. Apply a soap water or a liquid neutral detergent on the indoor unit…
-
Panel Front Assembly
ENGLISH 1. First, Check the side cover assembly exactly, and fix the power cord in the bottom groove of cover side left. 2. Assemble connecting lead wire with controller, fix the upper part of panel front, and match the lower part of panel front. Panel Front Connector 3. Screw up panel front, and…
-
Test Running
1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction. 2. Insert new batteries making sure that the (+) and (–) of battery…
-
NOTICE
PUMP DOWN This is performed when the unit is relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant. CAUTION: Be sure to perform Pump Down procedure in the cooling mode. Pump Down Procedure 1. Connect a…
-