Инструкция на Вентиляционные установки с тепловым насосом Komfovent серии RHP Standard
Руководство по монтажу установок RHP Standard со встроенным тепловым насосом: исполнения и типоразмеры, компоненты, транспортировка, монтаж, гидравлические и электрические схемы. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
RHP STANDARD
INSTALLATION MANUAL komfovent
-
1. INTRODUCTION
This Installation Manual is intended for professionals, qualified to install RHP Standard air handling units. Qualified professionals are people with sufficient professional experience and knowledge of ventilation systems and installation thereof, knowledge of electrical safety requirements and…
-
Heat exchangers and heaters (or coolers) are designed to compensate for heat/cool losses during ventilation, therefore, we do not recommend using this unit as the main heating/cooling source. The unit may fail to reach a user-defined supply air temperature when the actual temperature in the premises…
-
Heat pump model and exact refrigerant load capacity is stated on the sticker, that can be found inside of AHU: Air handling unit model / Vėdinimo įrenginio modelis RHP 1600 U Heat pump model / Šilumos siurblio modelis HP 12,5/10,5 Maximum operating pressure Maksimalus darbinis slėgis P max [bar]…
-
During winter operation, when the heat pump is in heating mode, condensate on the evaporator starts freezing and forms frost. Large ice deposits block airflow in the evaporator and may damage the heat pump. Therefore, the evaporator is automatically defrosted during winter use. When the outdoor…
-
1.2.3. Unit types by inspection sides
Also, each unit may be left or right inspection side1. The inspection side indicates which side of the unit contains the air supply duct to the premises. The exact arrangement of the duct connections for the different inspection sides can be found in section “Unit components”. Right inspection side…
-
RHP 900 H
Left inspection side L1 Right inspection side R1 ETA SUP EHA EHA ODA ODA ETA SUP C5 C5 RHP 1200 UH - RHP 1600 UH Left inspection side L1 Right inspection side R1 ETA C5 SUP ODA ODA EHA EHA ETA C5 SUP RHP 1200 UV - RHP 1600 UV Left inspection side L1 Right inspection side R1 SUP ODA ETA EHA ODA ETA…
-
RHP 2500 V
Left inspection side L1 Right inspection side R1 SUP ODA ODA EHA ETA EHA ETA SUP C5 SUP 10 ODA – outdoor air SUP – supply air ETA – extract air EHA – exhaust air C5 ETA EHA 7 7 ODA 1 – Rotary heat exchanger 2 – Supply air fan 3 – Extract air fan 4 – Electrical heater 5 – Supply air refrigerant coil…
-
2. UNIT TRANSPORTATION AND STORAGE
Equipment must be transported and stored in the original packaging. During transportation, equipment must be properly secured and further protected against possible mechanical damage, rain or snow. Forklift truck or crane can be used for loading or unloading. For the crane operation, special lashes…
-
After delivery of the air handling unit, carefully inspect its packaging for damage. If mechanical or other damage is visible (e.g., wet cardboard packaging), notify the carrier immediately. If the damage is significant, do not accept the unit. Inform the selling company or the representative of UAB…
-
3.2. Inspection Area
Based on its type, an air handling unit may be installed indoors or outdoors. When selecting an installation or mounting location, you must foresee sufficient and security compliant access space for repair and maintenance operations. The unit must be installed in a way to allow partial or full…
-
3.3. Duct system installation
The air in and out of the unit flows through the duct system. The duct system should be designed and selected to have low airflow rates and low pressure differentials, ensuring more accurate airflow rates, lower energy consumption, lower noise levels and longer life of the unit. Outdoor vents must…
-
• • • • Ducts connecting the unit to the exterior of the building must be insulated (insulation thickness 50–100 mm) to prevent condensation on cold surfaces. Air intake and exhaust ducts must be fitted with air shut-off dampers (electric with actuators) to protect the unit from exposure to climatic…
-
3.5. Connection of a Condensate Drain
Operation of the heat pump causes condensation that accumulates in specially designed condensate trays. Condensate is removed from condensate trays via drainage pipes, therefore a condensate drainage system must be connected. Drainage piping must be mounted with a slope, without narrowing sections…
-
3.6. Outdoor Units
RHP 1200 - 1600 air handling units are suitable for outdoor installation1. Units for outdoor installation must be additionally protected against environmental effects by installing a protective roof and exhaust air hoods. Air dampers must be mounted on air duct connections on the air intake and…
-
5. UNIT DIMENSIONS
-
6. ELECTRICAL INSTALLATION
Only qualified professionals may perform electrical installation works in accordance with the manufacturer’s instructions and applicable legal acts and safety requirements. Before installation of any electrical components: • • • • Make sure the unit is unplugged from the mains. If the unit has been…
-
Terminals for the external elements of the controller board are numbered and are used only to connect external components. These may remain empty if no additional features are required. B9 Exhaust air pressure sensor ~24V N 0..10V ~24V Humidifier control Cold water mixing valve / DX capacity control…
-
Fig. 19. Supply air temperature sensor
For the most accurate temperature measurement, sensor in a duct must be installed after all heating/cooling devices at least two duct diameters away from the nearest coil. >2D D Fig. 20. Installation of a supply air temperature sensor TG3 (13–14) – for connecting control signal (0..10 V) of an…
-
Additional connection terminal block1 (L1,N) – auxiliary devices that require a 230V power supply, for example heating cable for condensate drain or laptop charger can be connected here during AHU repair or maintenance. Fig. 21. Additional connection terminal block All cables from external…
-
Control panel cable shall be installed further away from other power supply cables or high voltage electrical equipment (electrical enclosure, electrical water heating boiler, air conditioning unit, etc.). The cable can be pulled through openings in the back or bottom part of the control panel…
-
An air handling unit connected to a network router can be controlled by a computer via wireless connection (Wi-Fi). The unit may also be controlled wirelessly in a local network using a smart phone with the Komfovent app. Once the unit is connected to the network router, you should assign a free IP…
-
7. FILTERS
Air filters are intended for removing dust, bacteria and other fine particles from the supplied and extracted air. RHP Standard air handling units use compact filters. Filters are made of synthetic fabric and can have different filtration classes1, i.e., intended for removing particles of different…
-
8. COMMISSIONING AND INSPECTION OF THE UNIT
Before switching on the device, check for foreign objects, debris or tools inside the unit. Make sure that air filters are installed and condensate drainage is connected (if necessary), fill the siphon with water. Make sure that the ductwork is free from obstructions such as fully closed diffusers…
-
To start an air handling unit or change a ventilation mode
Change operation mode? During the first minute of starting the unit, the unit automation checks the settings, automation components and opens air dampers. Later, a signal is sent to fans and a heat exchanger, and the unit starts operating at a selected ventilation mode. The first time you turn on…
-
8.2. Starting the Unit With a Computer
If the unit was ordered without a control panel or it is not used, you can start it with your computer. In this case the unit is controlled via a web browser. Connect your computer directly to the AHU or to the same computer network as described in Chapter 6.4. Run the Internet browser on the…
-
To start the unit and change the ventilation mode settings
1. Press button “Modes”. 2. Select a desired ventilation mode from the list. 3. Enter desired air flow and temperature in the selected mode settings. 4. Press “Save” button at the bottom of the screen. You can stop the unit by pressing ON/OFF button in the “Overview” window. 30 UAB KOMFOVENT we…
-
8.3. Quick Inspection
The first time you start your device, make sure that: Task Yes No Comments Control panel is working, responds to touch, no error messages All air filters are installed Air dampers fully open There are no unusual noise or vibrations Changing the ventilation modes changes the fan speed The unit is…
-
APENDIX NO.1
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-
WARRANTY CONDITIONS
1. The warranty does not apply in the following cases: 1.1. If the product usage or operating conditions, as specified in the installation and operating instructions, are violated; 1.2. If the storage conditions of the unit are violated; 1.3. If there are signs indicating attempts of unqualified…
-
SERVICE AND SUPPORT
PARTNERS LITHUANIA UAB KOMFOVENT Phone: +370 5 200 8000 service@komfovent.com www.komfovent.com AT FINLAND Komfovent Oy Muuntotie 1 C1 FI-01 510 Vantaa, Finland Phone: +358 20 730 6190 toimisto@komfovent.com www.komfovent.com CZ GERMANY Komfovent GmbH Konrad-Zuse-Str. 2, 42551 Velbert, Deutschland…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.