RHP PRO2 USER MANUAL
-
1. INTRODUCTION
An air handling unit is a device designed to ensure good ventilation in the premises. An air handling unit removes indoor air containing carbon dioxide, various allergens or dust and replaces it with filtered fresh outdoor air. RHP Pro2 air handling units are designed for ventilation of medium or…
-
• ECONOMY 2 – minimum ventilation intensity (20%), desired air temperature – 19°C. SPECIAL – maximum ventilation intensity (100%), desired air temperature – 21°C. This ventilation mode may also be used to block heating/cooling and other functions. For information on how to select a ventilation mode…
-
2.5. Outdoor compensated ventilation (OCV)
Ventilation intensity, % This function adjusts ventilation intensity according to the outdoor temperature. This saves the energy needed for air heating or cooling. The user sets four outdoor temperatures (two for winter and two for summer) for this function to operate. As long as the outdoor…
-
2.9. Override (OVR)
Override function is activated by closing designated contacts in the controller board, i.e. by connecting a switch, cooker hood or a motion sensor (see “Installation Manual”). This function ignores current ventilation mode and switches to the pre-selected mode or stops it. In the function setup…
-
Internal fire alarm function stops the air handling unit when air temperature increase is detected inside the unit. This can happen, for example, when hot smoke enters the duct system from fire zones both inside and outside the building. This function prevents smoke from spreading inside the…
-
3. OPTIONAL FUNCTIONS
3.1. Recirculation (REC) Extracted air recirculation function is available in units with recirculation sections. Recirculation section is intended for mixing extracted and supplied air for heating or cooling of air flows in order to reduce energy consumption of heaters/coolers. The recirculation…
-
3.3. Additional zone control (ZN)
This function allows controlling up to three different temperature zones with one air handling unit. Temperature of the main zone is maintained by integrated heaters/coolers. Temperature in other zones is maintained by connected additional zone modules, which are used to control duct-mounted…
-
4. CONTROL AND SETTINGS. CONTROL PANEL C5.11
Air handling unit may be conveniently controlled via the following ways: Control panel. Mobile app. Web browser. C5.1 panel has a colour touchscreen. If the unit is connected to the mains, the control panel will display the home screen or screen saver that you can switch off with a single tap. • • •…
-
Explanation of the displayed symbols
Supply air temperature Extract air temperature Supply air volume Extract air volume Supply air humidity Extract air humidity Extract (room) air quality Fan operation Air flow increasing by activated function (see chapter Functions) Air flow decreasing by activated function (see chapter Functions)…
-
4.1. Parameter overview
The following parameters are displayed in the main window and parameter overview windows: air flow, temperatures, air quality sensor data and energy recovery. Use arrows on the sides of the main screen to browse across parameter windows. 16:30 16:30 16:30 16:30 21,9 °C 21,3 °C 12500 m³/h 13100 m³/h…
-
4.2.1. Calibration of the HP evaporator pressure-drop exchanger during commissioning
The first time you turn on your air handling unit, you will have to perform calibration of a HP evaporator (if not performed during installation). This calibration is necessary for proper operation of the antifreeze prevention function. 16:30 °C Start 21,9 HP exchanger calibration? 21,3 °C…
-
Operation program You can set up to twenty operating programs. You can assign a desired operating mode, day of the week and time interval for every program. To create a weekly ventilation schedule: 1. Press “Sheduling” key in the menu window. 2. Press “Operation program”. 3. Press “Add new program”…
-
Recirculation schedule1 When the unit is equipped with a recirculation section, recirculation damper can be controlled according to a user-created weekly schedule (maximum of 5 different schedules) with a user-defined day of the week, hours and recirculation level %. Recirculation schedule Schedule…
-
Efficiency Heat exchanger parameters are displayed in real-time. In this menu you can also calibrate HP evaporator, if not calibrated during the first start-up. If calibration was successful and the display shows “Calibrated”, there is no need to repeat it. During calibration, the unit will run for…
-
4.6. Functions
In menu item “Functions” you can activate or alter all functions of the unit. Press the function name or an arrow to display the function settings. Menu Overview Functions Scheduling Settings Functions Functions Air quality control Override function Operation on demand Humidity control Outdoor…
-
Outdoor compensated ventilation (OCV) Setting winter and summer outdoor temperature limits for reducing ventilation intensity. When the outdoor temperature is within the range of “Winter compensation start” and “Summer compensation start”, the unit operates in a selected ventilation mode and when…
-
Humidity control (HUM) Setting a desired relative or absolute humidity level. Humidity level is set for two different ventilation modes during which this function will be used and the desired value will change automatically as the mode changes. If the unit operates in a different ventilation mode…
-
Water heater/cooler It is possible to block the water heaters and coolers by removing the check mark next to the related setting. In this case, water heaters and coolers will not be used either for the desired temperature or in any functions (for example during dehumidification). However, the water…
-
Air quality Selected air quality sensor type is used in AQC, OOD and REC functions by air quality. Sensor type CO2 VOCq VOCp RH TMP • Time/data Time and date settings are used for ventilation by weekly, holiday and recirculation schedules. Time/Date Time 09:40 Daylight saving time Enable Day/Month…
-
Heat pump If the heat pump evaporator fails to defrost automatically (see “Troubleshooting”), it can be defrosted manually. Manual defrosting takes about 10-20 minutes, and during it, the air handling unit may supply a slightly lower than desired temperature. Heat pump Manual defrost Off Heat pump…
-
Panel lock The panel can be locked using a four-digit code. To activate a panel lock, enter your PIN code and press Confirm. When the lock is activated, the panel will lock every time a screen saver appears. You will need to enter the same code again to access the main window or other settings. You…
-
5. CONTROL AND SETTINGS. COMPUTER
The unit may be controlled via computer using a web browser. For information on how to connect the unit to an internal network or directly to a computer, see the “Installation Manual”. Enter the device IP address in your web browser (IP address is displayed on the control panel) (see Settings → Air…
-
5.1.1. Operation modes
In this menu item the user can select one of the five ventilation modes for the unit (see Chapter 2.1 “Ventilation Modes”). Selecting the “Program” mode: OPERATION MODES Mode selection Comfort1 Comfort2 Economy1 Economy2 Special Program You can select air volume (for supplied and extracted air…
-
5.2. Functions
Here you can enable/disable ventilation functions and change their settings. 5.2.1. Air quality control (AQC) Selecting air quality limit up to which the air handling unit will operate in a selected mode and above which the ventilation intensity will be automatically increased. Air quality limit is…
-
5.2.5. Override function (OVR)
Selecting conditions for activating the function (all the time, only when the unit is running, only when the unit is stopped) and specifying ventilation mode for the unit to run when the function starts. If the “Standby” ventilation mode is selected, the unit will be stopped. OVERRIDE FUNCTION (OVR)…
-
Control by external signal Recirculation damper position is set for open (main recirculation) and closed (activated recirculation) control signal contacts. RECIRCULATION CONTROL (REC) Enable Default recirculation 0 % Activated recirculation 60 % 5.2.8. Humidity control (HUM)1 Setting a desired…
-
5.3. Alarms/Status
This menu item shows information about the air handling unit and its assemblies. ACTUAL ALARMS ALARM HISTORY OPERATION COUNTERS EFFICIENCY STATUS VAV STATUS CONTROLLER STATUS 5.3.1. Actual alarms This menu item displays relevant messages with identification codes. “A” at the end of the code means…
-
In this menu you can also calibrate HP evaporator, if not calibrated during the first start-up. If calibration was successful and the display shows “Calibrated”, there is no need to repeat it. During calibration, the unit will run for 10 minutes by changing fan speed and will be measuring pressure…
-
5.4.1. Operation program
You can set up to twenty operating programs. You can assign a desired operating mode, day of the week and time interval for every program. When the “Program” mode is selected in the ventilation mode setup screen, the air handling unit will only operate at a specified time. There is no need to set…
-
5.5.2. Connectivity
Setting IP address, Modbus and BACnet or computer network parameters. CONNECTIVITY IP 192 . 168 . 0 . 50 IP mask 255 . 255 . 0 . 0 Modbus ID 1 RS-485 19200 baud Modbus ID 47808 Modbus ID 166 8E1 5.5.3. User interface Here you can select the user interface language (the same language will be used on…
-
6. CONTROL VIA A SMARTPHONE
“Komfovent C5” app is necessary for controlling your air handling unit via your mobile phone. The unit can be controlled in a local network via mobile phone. Controlling the air handling unit with your mobile device is almost the same as with a C5.1 control panel. Screens and settings are so similar…
-
7. PERIODIC MAINTENANCE
The air handling unit must be serviced by a qualified technician or authorized service representative. • • • • • Before starting any tasks, make sure that the unit is unplugged from the mains. Use caution when performing works near internal or external heaters as their surfaces may be hot. Remove…
-
Frequency
Task Commissioning 3 months X X 6 months 12 months 7.9. Humidifier Operation of the water treatment system Check of humidifier components X Cleaning of the humidifier X 7.10. Silencers Inspection of silencers X Cleaning of silencers X 7.1. Housing Once the unit is installed (and periodically) check…
-
To insert/remove filters, push two handles at the top and bottom of the filter forward to release a filter clamping device. Filters are removed/inserted one by one (number of filters depends on the unit size). Once the filters are replaced/inserted, handles are retracted and the filter clamping…
-
7.7. Direct evaporation cooler/heater (DX)
Check for refrigerant leaks. In a humidity indicator check whether the refrigerant is moisture free; check for sufficient amount of refrigerant. Check operation of the external unit and temperature sensors. Perform regular maintenance works of a direct evaporation cooler/heater in accordance with…
-
4B
Possible cause User‘s actions Contaminated outdoor air filters. Replace the air handling unit filters and clear the message. Change extract air filter Contaminated exhaust air filters. Replace the air handling unit filters and clear the message. 6B-11B Electric heater off Electrical heater…
-
Message
Possible cause User‘s actions 13A External fire alarm A fire alarm received from the building’s fire protection system. Once fire alarm is resolved, the unit must be started using a control panel, computer or a smartphone. 14A External stop The unit stopped by an external device (button, timer…
-
Possible cause
User‘s actions 1. Check if all wires and cables are connected between the unit sections. 2. Contact authorised service. 91A-98A Controller failure Faulty controller electronic or no connection between controller electronics. 99A-103A Supply fan failure Supply air fan or frequency converter not…
-
ANNEX 1
ROTOR CLEANING INSTRUCTIONS 1 2 Loosen the screws on the automation box cover (4 pcs.). Press the indentations on the sides of the box and release the latches holding the cover. Press two latches on the same side of the box at the same time. 4 3 Remove the automation box cover. 5 x4 x4 Loosen 8…
-
Unscrew the brackets at the corners that secure the rotor housing to the top and bottom of the section (brackets may not be used in smaller units). 8 Pull the rotor completely out of the section. 7 Disconnect cable connections from the filters, inspection or recirculation section side. Pull the…
-
ANNEX 2
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-
WARRANTY CONDITIONS
1. The warranty does not apply in the following cases: 1.1. If the product usage or operating conditions, as specified in the installation and operating instructions, are violated; 1.2. If the storage conditions of the unit are violated; 1.3. If there are signs indicating attempts of unqualified…
-
SERVICE AND SUPPORT
PARTNERS LITHUANIA UAB KOMFOVENT Phone: +370 5 200 8000 service@komfovent.com www.komfovent.com AT FINLAND Komfovent Oy Muuntotie 1 C1 FI-01 510 Vantaa, Finland Phone: +358 20 730 6190 toimisto@komfovent.com www.komfovent.com CZ GERMANY Komfovent GmbH Konrad-Zuse-Str. 2, 42551 Velbert, Deutschland…