VERSO PRO 2 USER MANUAL
-
1. INTRODUCTION
An air handling unit is a device designed to ensure good ventilation in the premises. An air handling unit removes indoor air containing carbon dioxide, various allergens or dust and replaces it with filtered fresh outdoor air. VERSO PRO2 air handling units are designed for ventilation of medium or…
-
• • The operation, maintenance or repair of the air handling unit is prohibited for people (including children) with mental, physical or sensory disabilities, as well as for persons without sufficient experience and knowledge, unless supervised and instructed by the person responsible for their…
-
• Room temperature control – the unit automatically selects the temperature of supplied air to ensure that the room temperature is reached and maintained as quickly as possible; room temperature is measured by an optional sensor (0..10 V signal corresponds to the range of 0..50 °C). Room temperature…
-
2.7. Operation on demand (OOD)
This function turns on the AHU as soon as the indoor air quality decreases. In this way, the air handling unit will only run when ventilation is required and will remain stopped when the air quality is good. As the air quality decreases and reaches the user-defined critical limit, the air handling…
-
Electric heater overheat protection consists of several different control algorithms. Integrated thermostats disconnect electric heater’s power supply if its temperature reaches a critical limit (e.g., in case of heater’s control electronics failure). Every electric heater has 2 thermostats: •…
-
3. OPTIONAL FUNCTIONS
3.1. Recirculation (REC) Recirculated air, % Extracted air recirculation function is available in units with recirculation sections. Recirculation section is intended for mixing extracted and supplied air for heating or cooling of air flows in order to reduce energy consumption of heaters/coolers.…
-
3.4. Multi-level frost prevention
When ordering an air handling unit with a counter-flow heat exchanger (CF), you may additionally select a multi-level antifreeze protection function. If this function is ordered, the heat exchanger is fitted with a four-segment damper. If there is a risk of freezing, damper segments close/open in…
-
3.7. Pressure auto balance
When this function is ordered for AHU, extract air damper (air extracted from the premises) is mounted additionally and pressure sensor is installed inside of the C5 controller board. Function maintains constant pressure difference between supply and extract airflows inside of AHU, by regulating…
-
4. CONTROL AND SETTINGS. CONTROL PANEL C5.11
Air handling unit may be conveniently controlled via the following ways: Control panel. Mobile app. Web browser. C5.1 panel has a colour touchscreen. If the unit is connected to the mains, the control panel will display the home screen or screen saver that you can switch off with a single tap. • • •…
-
Explanation of the displayed symbols
Supply air temperature Extract air temperature Supply air volume Extract air volume Supply air humidity Extract air humidity Extract (room) air quality Fan operation Air flow increasing by activated function (see chapter Functions) Air flow decreasing by activated function (see chapter Functions)…
-
4.1. Parameter overview
The following parameters are displayed in the main window and parameter overview windows: air flow, temperatures, air quality sensor data and energy recovery. Use arrows on the sides of the main screen to browse across parameter windows. 16:30 16:30 16:30 16:30 21,9 °C 21,3 °C 12500 m³/h 13100 m³/h…
-
4.2.1. Calibration of the CF heat exchanger during commissioning1
The first time you turn on your CF air handling unit, you will have to perform calibration of a heat exchanger (if not performed during installation). This calibration is necessary for proper operation of the antifreeze prevention function. 16:30 °C Start 21,9 CF exchanger calibration? 21,3 °C…
-
4.4. Scheduling window and ventilation schedule settings
In menu item “Scheduling” you can create your own ventilation schedules so that the ventilation intensity or temperature settings change automatically. Scheduling Operation program Holidays Recirculation schedule • Operation program You can set up to twenty operating programs. You can assign a…
-
Holidays Here you can select a holiday program, set dates for the unit to run in a selected mode or to be stopped (e.g., stopping the air handling unit in the office during Christmas holidays). Holidays Holidays 2 Operation mode STANDBY Holidays 1 From 12/14 Till 12/26 Delete holiday Add new holiday…
-
Operation counters These meters show operating time of individual devices, amount of energy returned and consumed. To reset a meter, press an arrow next to a desired parameter. Operation counters Operation counters Air heater 121 kWh Air heater 121 kWh Supply fan 873 h SupplyReset fan air heater 873…
-
When replacing filters with filters from different manufacturers or different filtration class, calibration of clean filters is recommended. During calibration, the unit will operate at a maximum speed for a few minutes, measure the pressure difference upstream and downstream the filter and…
-
Air quality control (AQC) Selecting an air quality limit up to which the air handling unit will run during the activated mode and above which the ventilation intensity will be automatically increased. Air quality limit is set for two different ventilation modes during which the function will be used…
-
Minimum temperature control (MTC) Setting a minimum desired supply air temperature. Minimum temperature Enable Setpoint 15 °C Reset settings • Override function (OVR) Selecting conditions for activating the function (all the time, only when the unit is running, only when the unit is stopped) and…
-
Recirculation control
Recirculation control Enable Enable Setpoint 1 800 ppm Winter stop -20 °C Default recirculation 0% Min. fresh air 1 40 % Winter start -5 °C Activated recirculation 100 % Mode 1 ECONOMY 1 Summer start 25 °C Reset settings 1/2 • Recirculation control Enable Summer stop 40 °C Reset settings Reset…
-
4.7.1. Air handling unit
• Temperature control The user can select a desired temperature control method (see Chapter “Temperature Control”). The user-set temperature will be maintained during ventilation modes according to the selected control method. Temperature control Supply Extract Room Balance • Flow control The user…
-
Connectivity Parameters for connecting the air handling unit to a computer network, the Internet or a building management system. Connectivity Connectivity Controller ID Default BaCnet port 47808 IP 192.168.0.50 BaCnet ID 0000166 IP mask 255.255.0.0 Modbus ID 1 RS-485 19200 1/2 2/2 • Panel sensor…
-
Screen saver Screen saver is activated after 1 minute of inactivity on the control panel. In this menu the user can enable/disable a screen saver and select parameters to be displayed on screen. Screen saver Row 1 Brightness Enable 25% Time Brightness 55% 50% Panel temperature Row 1 Time 75% Panel…
-
5. CONTROL AND SETTINGS. COMPUTER
The unit may be controlled via computer using a web browser. For information on how to connect the unit to an internal network or directly to a computer, see the “Installation Manual”. Enter the device IP address in your web browser (IP address is displayed on the control panel) (see Settings → Air…
-
You can select air volume (for supplied and extracted air separately) and desired temperature for each ventilation mode. Air volume is set in the units specified in the user interface settings. Comfort1 Supply flow 6000 Extract flow 6000 Setpoint 21.0 m³/h m³/h °C “Special“ ventilation mode may also…
-
5.2.2. Outdoor compensated ventilation (OCV)
Setting winter and summer outdoor temperature limits for reducing ventilation intensity. When the outdoor temperature is within the range of “Winter compensation start” and “Summer compensation start”, the unit operates in a selected ventilation mode and when ourdoor temperature is out of range, fan…
-
5.2.7. Recirculation control (REC)1
Displayed function windows depend on the selected recirculation control method (see Chapter 3 “Optional Functions”): By air quality Setting an indoor air quality limit up to which the extracted air is recirculated. The minimum position of the opened recirculation damper is also indicated, i.e. the…
-
5.2.8. Humidity control (HUM)1
Setting a desired relative or absolute humidity level. Humidity level is set for two different ventilation modes during which this function will be used and the desired value will change automatically as the mode changes. If the unit operates in a different ventilation mode than the one set…
-
5.3. Alarms/Status
This menu item shows information about the air handling unit and its assemblies. ACTUAL ALARMS ALARM HISTORY OPERATION COUNTERS EFFICIENCY STATUS VAV STATUS CONTROLLER STATUS 5.3.1. Actual alarms This menu item displays relevant messages with identification codes. “A” at the end of the code means…
-
In this menu you can also calibrate CF heat exchanger1, if not calibrated during the first start-up. If calibration was successful and the display shows “Calibrated”, there is no need to repeat it. During calibration, the unit will run for 10 minutes by changing fan speed and will be measuring…
-
5.4. Scheduling
In this menu the user can set weekly, holiday and recirculation schedules. OPERATION PROGRAM HOLIDAYS RECIRCULATION SCHEDULE Save 5.4.1. Operation program You can set up to twenty operating programs. You can assign a desired operating mode, day of the week and time interval for every program. When…
-
5.5.1. Date/time
In this menu item the used can set the time and date of the unit, used for various functions and operation by a weekly schedule. When the “Daylight Saving Time” function is enabled, the clock will automatically switch between summer time and winter time in spring and autumn. DATE/TIME Day - Month…
-
6. CONTROL VIA A SMARTPHONE
“Komfovent C5” app is necessary for controlling your air handling unit via your mobile phone. The unit can be controlled in a local network via mobile phone. Controlling the air handling unit with your mobile device is almost the same as with a C5.1 control panel. Screens and settings are so similar…
-
7. PERIODIC MAINTENANCE
The air handling unit must be serviced by a qualified technician or authorized service representative. • • • • • Before starting any tasks, make sure that the unit is unplugged from the mains. Use caution when performing works near internal or external heaters as their surfaces may be hot. Remove…
-
Frequency
Task Commissioning Refrigerant leak 3 months 6 months X X X X Cleaning of the heat exchanger Operation of an external unit 12 months X 7.9. Electrical heater Wiring X Operation of overheat protection X X X Cleaning of heating elements X 7.10. Gas heater Gas leakage X Gas leakage protection (if…
-
Fig. 4. Filter clamping device
To insert/remove filters, push two handles at the top and bottom of the filter forward to release a filter clamping device. Filters are removed/inserted one by one (number of filters depends on the unit size). Once the filters are replaced/inserted, handles are retracted and the filter clamping…
-
7.4. Rotary heat exchanger
Check whether the rotor drum rotates freely, is not touching any metal parts of the housing, and its bearings are intact. Check the actuator and motor. Rotary heat exchanger shall rotate at approx. 12rpm. Check the drum brushes for wear. Replace, if needed. Check the drum belt. Due to the natural…
-
7.11. Humidifier
Regular cleaning is required for good operation of the humidifier. Cleaning intervals depend on water quality. Humidifier must be inspected at least every three months and cleaned every six months. If water contains high levels of calcium and salts, the humidifier inspection intervals must be…
-
8. TROUBLESHOOTING
Device automation continuously monitors the operation of various nodes and function algorithms. If something goes wrong, the device informs you with a message and an audible alarm from a control panel. Messages are divided into critical messages and notifications. Critical messages occur when the…
-
Code
Message Possible cause User‘s actions 3A, 4A Extract air temp. sensor failure Not connected or faulty extract air temperature sensor. Check whether the sensor is connected. If a sensor needs to be replaced, contact an authorized service representative. 5A, 6A Outdoor air temp. sensor failure Not…
-
Code
Message Possible cause User‘s actions 41A,42A Supply air temp. sensor failure Not connected or faulty temperature sensor inside the unit, measuring supply air temperature downstream the heat exchanger. Check whether the sensor is connected. If a sensor needs to be replaced, contact an authorized…
-
APENDIX 1
ROTOR CLEANING INSTRUCTIONS 1 Loosen the screws on the automation box cover (4 pcs.). 2 Press the indentations on the sides of the box and release the latches holding the cover. Press two latches on the same side of the box at the same time. 3 Remove the automation box cover. UAB KOMFOVENT we…
-
Loosen four screws at the corners of the automation panel. Carefully pull the panel to yourself and disconnect cable terminals on the back of the panel. Also disconnect the earthing cable fixed to the top panel of the section. 5 Disassemble the main circuit breaker box and disconnect the power cord.…
-
Loosen the screws holding the door struts (6 pcs.). 8 Unscrew the brackets at the corners that secure the rotor housing to the top and bottom of the section (brackets may not be used in smaller units). UAB KOMFOVENT we reserve the right to make changes without prior notice VERSO PRO2_user…
-
11 Pull the rotor completely out of the section. Rotary heat exchangers shall be cleaned with high-pressure washers (pressure up to 10bar). Before washing, the rotor motor and electronics must be additionally protected against moisture or dismantled. Neutral or mild alkaline detergents and…
-
APENDIX 2
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-
WARRANTY CONDITIONS
1. The warranty does not apply in the following cases: 1.1. If the product usage or operating conditions, as specified in the installation and operating instructions, are violated; 1.2. If the storage conditions of the unit are violated; 1.3. If there are signs indicating attempts of unqualified…
-
SERVICE AND SUPPORT
PARTNERS LITHUANIA UAB KOMFOVENT Phone: +370 5 200 8000 service@komfovent.com www.komfovent.com AT FINLAND Komfovent Oy Muuntotie 1 C1 FI-01 510 Vantaa, Finland Phone: +358 20 730 6190 toimisto@komfovent.com www.komfovent.com CZ GERMANY Komfovent GmbH Konrad-Zuse-Str. 2, 42551 Velbert, Deutschland…