AS2 Cleaning Device for
Cleaning Rotary Heat Exchangers E N E R G Y R E C O V E R Y Page 2 1. Cleaning Options Page 3 2. Cleaning Device Page 6 3. Cleaning Sensors Page 10 4. AS2 Cleaning Control System Page 16 5. Menu navigation Page 23 6. Troubleshooting Page 25 7. Technical Data
-
1. Cleaning options
Self-cleaning effect Under the usual conditions for the operation of ventilation systems and air conditioning systems, rotary heat exchangers do not tend to become contaminated. This is due to the laminar airflow in the rotor mass and the counter-current circuitry. Counterflow Circuit: Outside air…
-
2. Cleaning device
If strongly adhesive contamination is present in the air, the installation of an automatic cleaning apparatus may be sensible. Usually, blowing out with compressed air is sufficient. Cleaning with high-pressure warm water is necessary only with tenacious viscous and greasy contamination. Please note…
-
The slide is moved by an AC motor, and the power transmission is through a toothed belt
Contactless proximity switches send an alert when the slide reaches either end position. Another proximity switch is installed in the rotor casing and records the rotor speed. 1 B C A C B 2 *S ensors are installed on the inside of the cleaning track A A A slide travels on a track over the radius of…
-
Following each rotation of the rotor, the cleaning apparatus advances by the width of a nozzle stream. This allows gap-free cleaning. When the cleaning apparatus is switched off, the carriage is positioned on the periphery of the rotor. The cleaning procedure can be started either by a built-in…
-
3. Cleaning Sensors
Manufacturer Klingenburg Model MMG 120BDKX, PNP Switch magnetic IP code IP67 Power supply 10-30 V= Contact Magnet Sensing distance <=30 mm Connect. wire colours blue / brown / black Usage Rotors Sorption wheel, Pulse sensor cleaning device Klingenburg Secatec Connection to controller: KR4/7 KR15 and…
-
Steute
Manufacturer Steute Model EEX-RC-M 14W Chanceover contact Reed contact IP code IP67 Atex Power supply changeover contact up to 250V AC/DC Contact Magnet Sensing distance <=7 mm Connect. wire colours gr-yel / grey / brown / black Usage Rotor, End position switch slide, pulse sensor cleaning device…
-
Schmersal
Model IFL-N4-12-10P PNP N/O Inductively IP code IP67 Power supply 10-30 Volt = Contact Steel contact tabs Sensing distance <=3 mm Connect. wire colours blue / brown / black Usage Cleaning device standard Connection to controller 8 KR4/7 KR15 and Premium KS 4/7/15 clamp 4 = blue; clamp 5 = brown…
-
Pepperl & Fuchs
Manufacturer Pepperl & Fuchs Model NBB 8-18GM50-E2-3G-3D PNP N/O Inductively IP code IP67Atex Power supply 10-30 Volt= Contact Steel contact tabs Sensing distance <=7 mm Connect. wire colours blue / brown / black Usage ATEX cleaning decice, Rotors Connection to controller KR4/7 KR 15 and Premium KS…
-
4. AS2 Cleaning Control System
Functional characteristics Processor-controlled monitoring of the cleaning sequence Coloured display Detailed error messages Menu navigation Cleaning takes place from the inside to the outside (the contaminated water runs towards the outside) 10
-
Functional description
The cleaning control system enables the automatic, electronic cleaning of the contaminated thermal mass of a rotary heat exchanger. tandby indicates readiness for operation. A start signal from an external contact, the start button or an S optional time switch activates the cleaning procedure. F…
-
Scope of delivery
The standard version of the cleaning device includes the following: Control box for AS 2 cleaning control system, degree of protection IP 54 (dimensions: see dimension sheet: page 25 Cleaning mechanism for compressed air cleaning Standard guide rail with covering on the inlet side Carriage with…
-
In the inspection window, the display shows the status of the cleaning procedure
-
3.4 Connection and commissioning
T he mechanical components (rail, carriage, motor, supports, and sensors) are pre-mounted and must be attached to the frame with screws. The frame is also prepared with rivet-down nuts. Adjust the pneumatic nozzles and, if necessary, the high-pressure nozzles so that these end around 20 - 30 mm…
-
tart the cleaning procedure with the Start button. The cleaning carriage must continuously drive towards the S centre of the rotor. If this is not the case, stop cleaning and reverse the direction of rotation of the motor by switching two phases of the motor. When the direction of travel is correct…
-
5. Menu navigation
The operational readiness of the AS2 is indicated by: S t a n d b y P a r k i n g p o s i t i o n To access the menu hold down the Stop button ( ) and press the Reset and the Enter buttons ( ). Attention: The cleaning procedure can be stopped and then started again with these buttons. When the…
-
Holding down the Stop button (
-
Starting times
-
Runtime
-
Tolerance limit
-
During the cleaning procedure the displays are as follows
-
Cleaning completed, return to park position
-
leaning carriage positioned in the centre of the rail
C Check the step sensor in the rotor (switching distance) Rotate the magnet in front of the sensor and measure whether there is 24 Volt DC between the blue and black. If not, replace the sensor. check the timing belt Check the rotor regulator: is there a fault? is the regulator released? is the…
-
7. Technical data
Dimensions of cleaning device AS2 25
-
Technical data
-
Terminal connection plan for AS 2
3 The PTC contact is already bridged from works (do not remove it). If the equipment will be installed in an ATEX-Area then the motor has to be monitored with a PTC relays. Please see the conection plan „AS2 with PTC Relays“. external setpoint Sensor cycle value brown / black / blue 0 - 10 Volt 1)…
-
3-phase AC motor (3x230 Volt) in delta connection with standard motors 230/400 Volt + Dedusting input { { Thermal contact/ resistor V Exhaust air temp. sensor reference External voltage control signal AS2 with 4-20mA control signal Jumper position in AS2 to the right for mA input For Rotor control…
-
Terminal connection plan for AS 2
Connected to a ATEX-PTC-Relay external setpoint Sensor cycle value brown / black / blue 0 - 10 Volt 1) LED yellow: Start 2) LED yellow: Sensor middle 3) LED green: in Operation 4) LED yellow: Sensor Extend 5) LED yellow: Sensor Cycle 6) LED yellow: Motor thermo safety contact 7) LED yellow: Solenoid…
-
ATEX-PTC-Relay