Инструкция на Контроллеры Klingenburg серии KR15.
Контроллеры Klingenburg серии KR15. Описание и технические характеристики.
Загружаем документ…
Текст инструкции
-
Brief description of KR 15 controllers
E N E R G Y R E C O V E R Y Page 2 1. Function of the controller Page 4 2. Terminal connections Page 5 3. Technical data Page 6 4. Initial operation Page 9 5. Manual mode / external mode Supply air temperature regulation Page 20 6. Trouble-shooting and fault messages Page 24 7. Safety and…
-
1. Function of the controller
KR15 = 1500 Watt – for wheel diameter from 5000 mm Special features: the controllers are usable worldwide all known regulations are taken into account by us for construction of the controller it is therefore the most modern generation of controllers by far the controllers are operated using only…
-
T he latest processor technology
CE - tested Housing IP 54 Short-circuit-proof output EN 55011 tested EN 61000-3 tested EN 61000-4-2 tested EN 61000-4-4 (Burst) tested EN 61000-4-5 (Surge) tested EN 61800-3 tested Every individual module is tested Detailed error message Thermal contact monitoring / PTC-resistor Two-row, colour…
-
to terminals 4, 7 and 9. +15 volts DC is applied to terminal 11. Dedusting input Changeover contacts shown in de-energised position Priority/ summer speed 0-10V DC analogue output 0-10 V 0-20 mA 4-20 mA Running Control control unit release Thermal contact/ resistor bl br + sch +10 V DC is applied to…
-
Technical Data
Controller typ KR 15 Output 1,5 kW Fuse (internal) 16 A Mains voltage 220-240 Volt / 50-60 Hz 1~ Weight 8000 g Environmental temperature from -10°C bis +40°C (for temperatures lower than 0°C it is necessary to switch on the mains voltage to the device without the motor running so that the controller…
-
4. Initial operation of the KR 15 controller
-
Manual operation
The following appears: M a n . f r e q u e n c y : 0 0 H z A frequency can be set using the selection button, which is used as soon as programming has been carried out and the start command has been given (using ). External control: The following appears: S t a r t p o i n t : 0 5 % The starting…
-
The control unit has a programmable priority frequency, which is also controlled with the contact
closed (terminal 4 and 5) and a 0-10 volt signal. This contact can easily be used to operate at frost speed, for example, or for summer operation. 3 Example: Optional: Frost protection thermostat 4 5 Controller KR 15 N N Frost protection thermostat AC 250V 16 (4) A <J Temp (+) <J 10 Temp (-) 4 5
-
Otherwise, you set the summer circuit using the sensor supplied
-
Definition of terms
Summer operation Your rotational heat exchanger can, of course, not only be used for heat recovery, but also as a „cooler“. If the exhaust air is colder than the external air in summer, the rotor can save valuable cooling power if it runs at maximum speed and pre-cools the external air. The KR 15…
-
Enthalpy comparison switch
If the external air enthalpy is higher than the exhaust air enthalpy, the rotor can use the exhaust air to cool the incoming external air. Two enthalpy sensors are required for the enthalpy comparison circuit. ϕ ϑ J/kg Temperature changeover When a pre-determined external air temperature is…
-
Supply air temperature regulation
The supply air temperature required can be set between 0°C - 40°C. The active ThermasGard MWTM temperature sensor is required to determine the supply air temperature. The Premium control unit can regulate the supply air temperature required through the PI control. The display during supply air…
-
Sequential circuit
-
Continuation of the menu description from page 11
-
The rotation of the rotor can be monitored with the running control
-
In order for the changes entered to take effect, it is necessary to save them
-
T est thermal contact/PTC resistor
-
6. Error codes
In addition to a fault in the running control and the motor overheating, the control unit recognises 7 different faults. These faults are indicated by means of a two-digit error code on the display: H a r d w a r e e r r o r : E : x x ! 01 Overvoltage (motor / rotor blocked, short circuit between U…
-
10 minutes. If it is reset within 10 mins., the control unit continues to work in normal mode. If the KR Premium is unable to reset itself as a result of a longer fault, the error message is triggered through the error message output after 10 mins. and the error code appears on the control unit…
-
7. Safety and precautions
Before installation and initial operation of the frequency converter, please read through the product handbook carefully and observe all warnings and safety precautions. Make sure that the product manual is easily reachable in the area of the frequency converter. Definition of tips: Warning! Failure…
-
P ay special attention when the automatic restart is activated. To avoid injury from possible uncontrolled restart of the frequency converter after a power outage, install a switch element on the grid side that de-energises in a power outage and can only be turned on after return of voltage by…
-
You can enter the values you have set here
Mode of operation Manual set point Starting point Min. frequency Max. frequency Priority input Cleaning mode Running control DC brake Braking torque Supply air temp. [°C] P factor I time 26