Инструкция на Контроллеры Klingenburg серии KR2.
Контроллеры Klingenburg серии KR2. Описание и технические характеристики.
Загружаем документ…
Текст инструкции
-
Brief Description of KR 2 controller
Air is our element energy recovery our passion Page 2 1. S afety and warning information Page 6 2. I ntended use of devices Page 7 3. F unctions of the controller Page 13 4. T echnical data Page 14 5. T erminal layout diagram Page 15 6. C onnections and commissioning Page 17 7. F aults and fault…
-
1. Safety and warning information
Before installing or commissioning the frequency inverter, please read this operating manual carefully and observer all safety and warning notices. Keep this operating manual close to the frequency inverter in a place that is accessible at all times. Risk levels: ! DANGER Imminent danger that could…
-
General
During operation it must be ensured that the mains supply is present at all times. ! WARNING he KR2 controller generates hazardous electrical voltages and controls hazardous rotating T machinery. Failure to observe the information contained in this handbook can result in death, severe bodily injury…
-
WARNING o not work on the wiring while the mains voltage is present. The inverter must not be conD nected to the mains supply while the housing is open and components can be touched. Take particular care if the automatic restart function is activated. To prevent injury from a potentially…
-
! ATTENTION
o ensure that your KR2 controller functions safely and reliably, all applicable safety regulaT tions, e.g. accident prevention regulations, the workplace guidelines of professional associations, VDE regulations, etc. must be observed. Since these provisions are treated differently in different parts…
-
CE EMC INSTALLATION
he KR2 series of controllers are not for household use but are intended solely to be used as T components for further use in an industrial context. They are electrical devices for controlling speed-regulated drives based on three-phase motors and are designed to be fitted into machines or combined…
-
REASONABLY FORESEEABLE MISUSE To minimise the risk of misuse that can be reasonably foreseen, use of this electrical equipment is restricted to the following environmental conditions: For operation only by instructed persons and specialists in an industrial setting For use only in a non-explosive…
-
he rotary heat exchanger motors are protected against overheating by a thermostat. The
T mechanical functioning of the rotor can be monitored using an optional run check feature. Here a magnetic sensor monitors the rotation of the rotor storage mass when there is a demand for heat recovery. The KR2 controller is designed for installation as a compact, easy-to-use controller for small…
-
OPTIONAL ACCESSORY: ROTOR RUN CHECK
Rotor run check in rotor housing Klingenburg run check sensor Manufacturer Klingenburg Type MMG 120BDKX, PNP magnetic switch Protection class IP67 Supply voltage 10-30 V= Contact Magnet Switching gap <=30 mm Colours of connecting wires blue / brown / black Application Rotors, sorption wheels, stroke…
-
INSTALLATION DETAILS
When fitting the housing, the following must be observed: The housing must always be secured at all four fixing points Sufficient ventilation must be available at all times The controller must always be easily accessible The controller must be protected from environmental influences (UV radiation…
-
Rotor run check Fmax 120 - 80 Hz 1 2 2. Offset: To supply the KR2 with 4-20 mA the offset must be set to ON, so that the wheel can be stopped at 4 mA. on 1. Reset: Each change in the switch settings causes a reset of the controller, irrespective of the position of the switch. 3 DIP SWITCH SETTINGS…
-
4. Technical data
Power rating 180 W Fuse (internal) 6.3 A slow-blow (5 x 20 mm) Mains voltage 190-240 Volt / 50-60 Hz 1~ Weight Ambient temperature 1200 g from -10°C to +35°C (at temperatures below 0°C mains power should first be applied to the unit without the motor running to enable the controller to warm up…
-
– + Reference voltage +10 Volt 6 – L1 N PE PE PE W S0 S1 S2 Fault message: In normal operation S0 and S1 closed If a fault is present or power outage S0 and S2 closed U Three-phase motor (3 x 230 V) delta-configured (for standard 230 / 400 V motors) Fuse 6.3 A slow-blow Jumper position 0-10 V DC…
-
6. Connections and commissioning
CONNECTIONS 1 ower input P The KR2/bus controller are connected to the mains supply at 230 V AC, 50 Hz. 2 rotective Earth conductor P The protective earth conductor must be connected at all times. 3 onnections to motors C To avoid interference effects from motor supply lines, these must be laid…
-
ault message contact F In normal operation S0 and S1 closed. If a fault is present or power outage, S0 and S2 closed 7 ontrol signal C For a control signal in the 0-20 mA range the jumper must be positioned as shown on page 14. For a control signal in the range 4-20 mA, DIP switch 2 (offset) must be…
-
nce all connections have been made and the DIP switches have been set to suit the device
O type, the supply power can be switched on. lose the enabler contacts (nos. 7 and 8). Now the KR2 is ready for operation. As supplied, C the controller is designed for signal within the set value range 0-10 V DC. For 0 – 20 mA or 4 – 20 mA (external signal) a jumper must be repositioned. This…
-
LEDs
Fault Controller does not function Power/mains LED lit but controller does not function? Run check fault 18 Cause Remedy No power supply to controller Check mains voltage and microfuse Controller terminals short-circuited Disconnect all conductors from controller (except L1/N/PE) Controller has no…
-
LEDs
Fault Cause Motor has overheated Motor is wired in star mode Motor overtemperature Motor thermostat is defective Remedy Check storage mass; it is rubbing or dirty Motor or rotor has a damaged bearing Motor must be wired 3 x 230 V delta Motor thermostat is defective Replace motor Controller has a…
-
Air is our element
Klingenburg GmbH Boystraße 115 45968 Gladbeck Germany Tel.: +49-20 43-96 36-0 Fax: +49-20 43-7 23 62 E-mail: info@klingenburg.de www.klingenburg.de KR2 deutsch englisch 120118 print energy recovery our passion