1 MASTER DEVICE
The Master device is a centralised unit for the reading and management of NEREIX zone modules. They are used for adjustment and heat metering for heating and DHW production systems. After appropriate setting and configuration, the Master board enables to dialogue with the individual metering units…
-
2 MASTER ELECTRICAL BOARD
FROM SUPPORT TERMINAL BOARD IMPULSE COUNTER EXT PROBE F=Phase N=Neutral 230 VAC POWER SUPPLY (P – N) Connect the power supply (phase, neutral and earth) to the support terminal board Important: as can be seen, the earth does not and must not be carried directly on the board. On the board, the…
-
USB and RS232 CONNECTORS
allows board interfacing to a PC MODEM CONNECTOR allows the connection of the Master board to a specific optional GSM - GPRS modem (code CB 926) LED DESCRIPTION Every 10 seconds, the Master board interrogates all the boards to which it is connected. Meaning of LED 1: Green on flashing every 10”: The…
-
4 TYPICAL BUS CONNECTION LAYOUTS
IMPORTANT INFORMATION ON THE BUS CONNECTION - Respect the A and B polarity on the whole system - Respect the layouts carried on the following pages - Use a shielded and twisted 2 x 0.35 mm2 cable - Connect the screen to the Master board only (C terminals) and not to the metering units (slaves)…
-
MORE BRANCH SYSTEM WITH AMPLIFIERS (OPTIONAL)
MASTER IN Signal Amplifier OUT 2 IN To other branch Signal Amplifier OUT 1 OUT 2 OUT 1 Module 1 Module 4 Module 1 Module 4 Module 2 Module 5 Module 2 Module 5 Module 3 Module n Module 3 Module n R=330 Ohm R=330 Ohm A signal amplifier must be installed on each branch after having overcome the length…
-
6 BUS CONNECTION
Depending on the model, there may or may not be a support terminal board. The layouts show boards in the middle of a bus branch and therefore they are wired with input and output cables. For a terminal board connection (with one input cable), it could be necessary to put a termination resistance…
-
7 GENERAL BUS AND ELECTRICAL POWER SUPPLY LAYOUT
screen module module screen + screen screen module module screen + screen screen screen + screen THERMAL CONTROL UNIT + screen Circuit breaker switch and differential Outside temperature probe 230 Vac condominium power supply meter IMPORTANT: While wiring the Bus, remember that every branch and…
-
8 VERIFICATIONS ON BUS
If there is no communication between the Master and slave board, voltage verifications can be carried out to see if there is a short circuit on the bus line or if a slave board does not work. If the values indicated below are found, communication is not certain. However cable interruptions or that…
-
Via G. Pascoli, 38 - 37059 Zevio - fraz. Campagnola - VERONA - ITALIA Tel. 045/8738511 - Fax 045/8731148 info@icicaldaie.com - www.icicaldaie.com The data in this booklet is supplied on an indicative and not a binding level for our company. The company can at any moment modify the models for ongoing…