TECHNICAL MANUAL
BOILER MANAGEMENT SYSTEM ELECTRONIC BOARD ETERM-01 ICI CALDAIE S.p.A. - BOILER MANAGEMENT SYSTEM ETERM-01 05-2012 Page 1 of 40
-
ICI CALDAIE S.p.A. - BOILER MANAGEMENT SYSTEM ETERM-01
05-2012 Page 2 of 40
-
WIRING DIAGRAM Display USB P1 P2 P3 P4 Keyboard INPUT 230 Vac N F4 F3 F2 F1 Control T8 T7 T6 Power source 230 Vac LTN Hardware serial number Programmable output R2 Programmable output R1 Modem connector Bus RS1 Bus RS2 0-10 Volt Output 0-10 Volt Input Sensors / digital inputs ICI CALDAIE S.p.A.…
-
TECHNICAL FEATURES POWER SOURCE L T N 230 Vac OPTO-ISOLATED INPUTS F1 Programmable input provided for: Safety intervention signals (when they are not lit it means that the safeties are on) F2 Programmable input provided for: Modulating burners, when lit it means that the burner is turned on…
-
LEAST 24 Vac BETWEEN THE ENDS THEN USE THE CONTACTS TO CONTROL UTILISERS AND/ OR AUXILIARY POWER WITH AT LEAST 24 Vac UP TO 230 Vac SENSOR INPUTS - DIGITAL PT1 Input PT 1000 provided for the boiler probe PT2 Programmable input PT 1000 / Digital PT3 Programmable input PT 1000 / Digital NTC…
-
BUS BETWEEN BOILERS IN CASCADE
-
DISPLAY When the board is powered up, the display indicates the following: Board Type (Device: ) Board serial number (M:... 7-digit number is needed for addressing by PC) Firmware Version (Rev. FW ) BURNER OUTPUT STATUS BOILER TEMPERATURE MODULATION IN RISE DAYS / HOURS / MINUTES / SECONDS EXTERNAL…
-
BURNER STATUS
Burner running at minimum power: Burner running at medium power: Burner running at maximum power: Burner running with increasing power: Burner running with decreasing power: Burner stopped: 4 MENUS AND PARAMETERS displays the available menus Pressing the key The default configuration allows access…
-
To change the level
- Enter the menu "Boiler Status" - Holding the right button simultaneously press both middle buttons - Left the keys and type the access code - Type 1 - 2 - 3 - 4 - 2 - 4 for level 1 - Type 4 - 3 - 2 - 1 - 4 - 3 for Level 2 The menus scroll with the arrow keys To get into the menus and view the…
-
BRIEF LIST OF PARAMETERS AND ABBREVIATIONS USER PARAMETERS - Language - Fix target 1 temperature - Fix target 2 temperature - Program comfort setpoint - Program reduced setpoint - Boiler climatic curve - Comfort room temperature - Reduced room temperature - Cylinder set point temperature - Mix…
-
04.xx OPERATIVE SETTINGS
04.01 Fix target 1 consent 04.02 TF1 Fix target 1 temperature 04.03 Fix target 1 program 04.04 Fix target 2 consent 04.05 TF2 Fix target 2 temperature 04.06 Fix target 2 program 04.07 Program function 04.08 TCO Program comfort setpoint 04.09 TRO Program reduced setpoint 04.10 CCC Boiler climatic…
-
08.xx MIXING VALVE
08.01 Type of mixing valve 08.02 Running mode 08.03 Mixing program 08.04 Mixing consent 08.05 PFC Lowered fixed target 08.06 PFR Comfort fixed target 08.07 CCV Mixing climatic curve 08.08 TMSM Max mixing temperature 08.09 TmSM Min mixing temperature 08.10 Mixing temperature probe 08.11 PCV PID…
-
GENERAL CONFIGURATIONS Parameter: 01.01 Language Unit of measure: / Adjustment range: Italian / English / Spanish / Russian Factory value: Italian Description: Language setting. Parameter: 01.02 Location Unit of measure: / Adjustment range: Alpha numeric value Factory value: Boiler Management…
-
Parameter: 01.08 Boiler / collector differential (DCC)
Unit of measure: °C Adjustment range: OFF / 0 - 30° C Factory value: 10° C Description: Differential that limits the temperature of the boiler in relation to the set point of the cascade header. Parameter is set only for the cascade master; the setting also applies to other boilers in the sequence.…
-
Parameter: 01.15
Collector adjustment ratio (CAC) Unit of measure: Adjustment range: 0.1 – 20.0 Factory value: 0.5 Description: Parameter set only for the cascade master. For details, see "CASCADE MANAGEMENT” Parameter: 01.16 Collector initial adjustment (AIC) Unit of measure: K Adjustment range: 0 - DCC °K Factory…
-
In a cascade the master shows two letters "CA" that blinks every 5 seconds to the left of the temperatures. When the letters "CA" are on, the temperature above is the actual temperature of the cascade header and that at the bottom represents the set point of the header. When the letters "AC" are…
-
BURNER PARAMETERS Parameter: 03.01 Burner type Unit of measure: / Adjustment range: Stage / Two-stage / two stage progressive / STAGE / Modulating 3 pt / Modulating 0-10 V Factory value: Modulating 3 pt Description: The parameter used to select the type of burner to be controlled. Single stage The…
-
Figure 1
MAXIMUM POWER PID MODULATION MINIMUM POWER OFF Modulating 0-10 V The operation is similar to that of modulating the burner with three points. The modulation system will not act on the contacts T6-T7-T8, but on the analog output 0-10 Volt. Two-stage / Two stage progressive / Three stage If the…
-
Operating stages
- Two-stage burner / Two-stage progressive o First stage for power demand up to 50% o Second stage for power demand by 50% to 100% - For three-stage burners o First stage for power demand up to 33% o Second stage for power demand from 34% to 66% o Third stage for power demand by 67% to 100% Status…
-
Parameter: 03:05 Higher hysteresis modulation (D2H)
Unit of measure: K Adjustment range: 0 to 10 ° K Factory value: 2 ° K Description: Temperature range, above D1H within which the burner is brought to minimum power (point 2 of the graph in Figure 1) Above this range the burner stops if the minimum time for burner operation has passed Tmin1 (point 3…
-
Parameter: 03.10 PID Integral factor (FIB)
Unit of measure: / Adjustment range: 0-20 Factory value: 2.5 Description: Weight of integral factor which is taken as reference by the PID system of the burner. The integral contribution is required for the precision at steady state. However, if too much weight can cause excessive overshooting…
-
OPERATIVE SETTINGS Parameter: 04.01 Fix target 1 consent Unit of measure: / Adjustment range: OFF / NTC / PT2 / PT3 Factory value: OFF Description: If an input is selected and this input is electrically closed, the boiler will be brought to the set point temperature TF1. Of all the set points active…
-
Parameter: 04.08 program comfort setpoint (TCO)
Unit of measure: °C Adjustment range: 0 ° C - TMC Factory value: 0 ° C Description: Comfort set point for operating with time schedule. Parameter: 04.09 Program lowered setpoint (TRO) Unit of measure: °C Adjustment range: 0 ° C - TMC Factory value: 0 ° C Description: Reduced set point for operating…
-
Parameter: 04.11 Climatic Program
Unit of measure: / Adjustment range: OFF / Prog. 1 / Prog. 2 / Prog. 3 Factory value: OFF Description: If the value of this parameter is OFF, the set point curve is considered with the theoretical ambient temperature of comfort. If a time schedule is set, the theoretical temperature varies between…
-
Parameter: 04.18 Measurement unit input 0-10 Volt
Unit of measure: / Adjustment range: Free field Factory value: Volt Description: The unit of measure for the quantity can be written. Parameter: 04.19 0 Volt input value Unit of measure: / Adjustment range: -999.0 / +999.0 Factory value: 0 Description: Value corresponding to 0 Volt input. Parameter…
-
Parameter: 05.05 Pump minimum temperature (TmP)
Unit of measure: °C Adjustment range: 0° C - TMS Factory value: 0° C Description: Temperature below which the boiler pump cannot start. When this is exceeded TmP the pump can start, it will stop if the temperature drops below Tmp minus 2° C. Parameter: 05.06 Pump post-circulation functions (TPC)…
-
11 DOMESTIC HOT WATER
Parameter: 06.01 Means of requesting DHW Unit of measure: / Adjustment range: OFF / Probe / Thermostat Factory value: OFF Description: Enables the heating function of one cylinder. Probe = it is possible to use a temperature probe NTC / PT on the basis of the available input = Thermostat, a…
-
Parameter: 06.07 Cylinder inertial unload
Unit of measure: \ Adjustment range: YES / NO Factory value: YES Description: If the boiler temperature TC exceeds the maximum allowed temperature TMC (despite the burner shutting down) it activates the loading pump of the cylinder. The loading pump of the cylinder stops when the boiler temperature…
-
Cascade pump
The function is programmable when the boiler is set as master. The output is active in parallel to any request in progress. After the end of the request and the shutdown of the burner, the output remains active for the time of post circulation (TPC). Alarm If you set this parameter, the contact will…
-
Parameter: 07.05 Anti-lock pumps R1
Unit of measure: / Adjustment range: ON / OFF Factory value: OFF Description: The output is activated for 10 seconds after 24 hours of inactivity. The time counter is stopped in a case of power failure. When given power the output is activated for 10 seconds. Parameter: 07.06 Anti-lock pump R2 Unit…
-
MIXING VALVE Parameter: 08.01 Mixing valve type Unit of measure: \ Adjustment range: OFF / 0-10 Volt / 3 points Factory value: OFF Description: Type of valve actuator, the valve actuator with three points is only possible if using a single-stage or modulating burner 0-10 Volt. The valve 0-10 Volt is…
-
Parameter: 08.09 Min mixing temperature (TmSM)
Unit of measure: °C Adjustment range: 0 ° C - TMSM Factory value: 0 ° C Description: Minimum temperature manually settable and/ or calculable from the temperature curve and/ or that can be set as a set point and/ or settable on the basis of input 0-10 Volt. Parameter: 08.10 Mixing temperature probe…
-
Parameter: 08.17 Boiler / mixing differential (DCM)
Unit of measure: °C Adjustment range: 0 - 30° C Factory value: 10° C Description: When there is a request from the "mixing area" circuit, the set point TSC is calculated by adding this value to the mixing area temperature set point (TSM). TSC may not exceed TMS (Maximum temperature of the boiler set…
-
Parameter: 09.07 Overrides enable
Unit of measure: Adjustment range: YES / NO Factory value: None Description: Selecting YES will enable all the forcing selected. Leaving the forcing menu, forcing ceases unless it is set at a time out in parameter 09.07 Parameter: 09.08 Overrides Duration Unit of measure: Seconds Adjustment range…
-
BOILER STATUS Screen "inputs" Parameter PT1 probe PT2 probe PT3 probe NTC probe External temperature Input 0-10 V Value Temperature °C / OPEN-CLOSED Temperature °C / OPEN-CLOSED Temperature °C / OPEN-CLOSED Temperature °C / OPEN-CLOSED External temperature °C - m ay coincide with or be taken from…
-
16 DATE / TIME / SEASON
Local settings (changeable if not taken from the system - or from a master): 10.01 Year 10.02 Month 10.03 Day of month 10.04 Day of the week – given as read-only which depends on the date set 10.05 Hour 10.06 Minutes 10.07 Seconds 10.08 Configuring season (manual/ automatic) 10.09 Current season…
-
17 TIME SCHEDULES
Menu displays the three schedules and shows the functions associated for each schedule Select the program to view or edit using the arrow keys and press . Entering each schedule displays the day of the week and the letters ESC. you enter the selected day or to return to the previous With the arrow…
-
18 ACTIVE ALARMS
Choosing the ALARMS menu displays the alarms currently active. The possible alarms are: Probes shorted or open (if the inputs are not provided as digital inputs) Burner locked. Lack of phase in safety input. Temperature thresholds (programmed via PC) Analog input thresholds value 0-10 Volt…
-
Member of Finluc Group, registered in Bus. Reg. VR No. 02245640236
Via G. Pascoli, 38 - 37059 Zevio - sect. Campagnola - VERONA - ITALY Tel 045/8738511 - Fax 045/8731148 info@icicaldaie.com - www.icicaldaie.com ICI CALDAIE S.p.A. - BOILER MANAGEMENT SYSTEM ETERM 01 05-2012 Page 40 of 40