Operating manual
HOMA Pump control HSK15 / 25 Ple ase f o llow safet y g u id e line s in ch apt er 2 Version: 03 - 0.06_300704 SW-Version: 1.10c HW-Version: 1.00 Date: 21.10.2004 HSK_operating_manual_English_Ver3.doc HOMA Pump Technology -0-
-
Table Of Contents
1 2 Introduction Safety guidelines 3 3 2.1 Marking of guidelines in the operating manual 2.2 To be observed 2.3 Application in the Ex – endangered areas Load section 3.1 3.2 3.3 5 Main switch Motor protection RCD's (ELCB) Function 4.1 Level measurement method 6 6 4.2 Pump control 4.2.1 Off…
-
General settings 6.5.1 Language selection 6.5.2 Changing password 6.5.3 Number of pumps 6.5.4 Time delay start 6.5.5 Short time start 6.5.6 Forced emptying 6.5.7 Date, time and SW-Version 6.6 System indications 6.6.1 Pump hour indication 6.6.2 Pump cycle counter 6.6.3 Deleting of hour meter / and…
-
1 Introduction
HOMA HSK is a modular pump control for up to two pumps, which has specifically been designed for use in the wastewater sector. The pump control measures and monitors the level of the medium and depending on the level, starts or stops either one or two pumps. In addition, the HSK continually monitors…
-
In such case that not all of the information and instructions are found in this operating manual, please ask the manufacturer, HOMA-Pumpenfabrik GmbH (address see page 2). The manufacturer of this device takes no responsibility in case the operating manual is disregarded. This operating manual…
-
When the controller already features factory-installed isolating amplifiers and/or electrical (zener) barriers, then the permission documents and operating instructions are included with the switchgear and they must be adhered to. Particular attention to applicable regulations concerning wiring is…
-
Motor protection Depending on the layout of the control, each pump features a thermal overload relay or a manual motor starter. Setting of the current values is carried out directly on the thermal overload relay or on the manual motor starter and shall be in accordance with the pump data. The…
-
Current measurement and ampere meter function The control unit measures the current for each pump in a motor phase. The current is indicated in the display. Additionally, the current is monitored and thus an electronic motor overload relay is simulated. Undercurrent monitoring is also carried out.…
-
loss of control voltage • rechargeable battery voltage too low • leakage monitoring • additional "AUX" alarm of each pump • "external" fault (only HSK25 in case of continuous level measurement) Faults are signalled by means of a red LED, an internal buzzer, or with up to three voltage free alarm…
-
Operating the manual motor starters, RCD's or the main switch is effected by using the knobs of the
respective device. 4.5 Rechargeable battery operation The control unit can be operated with a rechargeable battery so that in case of a 230V~ control voltage loss the unit will continue to operate. The battery is recharged by the unit and can be used together with the potential free SPDT contacts of…
-
• 5.2 the operation mode of the pumps in the menu “Operation mode” can be changed,3 one of the system menus can be selected Main display In the standard display, the control will indicate the operational state of the pumps, the current draw of the pumps and the measured level, e.g.: P1:IA 5,7A 074cm…
-
High water indication
P1:IA 5,7A 074cm P1:0A 0,0A HW Failure in measuring system P1:IA 5,7A ???cm P1:0A 0,0A Start delay 3sec 074cm The start delay is effective (after the first initial start or after a mains voltage failure) or when the control has been switched off by the external input; both pumps are switched off.…
-
0M = Manual OFF
IM = Manual ON 0A = Automatic operation mode OFF IA = Automatic operation mode ON It is to be observed: In case the pump is switched to the manual ON operation mode, this pump will only start if there is no fault present. If in a two pump operation mode, one pump is switched to OFF, the control…
-
communication • alarms • system indications By pressing the OK-key the relevant submenus (system menus) can be accessed. Here, specific values can be viewed and/ or changed. By means of the arrow keys (▲▼) scrolling from menu to menu is possible. By pressing the OK key in the menu point "back to…
-
This message is not important for the user and it indicates only the internal configuration for service purposes. Subsequently the copyright message with the SW-version number is indicated for approx. 1sec. After this, the HSK initiates the start delay time. 6 System menus 6.1 Level measurement 6.2…
-
For example, for a HOMA LLS with measuring range of 2,5m - the value of 0250cm is entered
Important information: If values for the measuring range < 0100cm are entered, then the control inserts the minimum value of 100cm , in case of values >1000cm, the control inserts the maximum value of 1000cm. If “3x float switches” has been selected and the unit is subsequently switched to a single…
-
Note: When the filter is active, the level indication can be so inert that the measured
level may deviate greatly from the level in the shaft. The shaft may have already been emptied, the measured value, however, still indicates a level above the cut-out setpoints and the pump may possibly run dry. Therefore, pump capacity, setpoints, and filter values must be well in balance with each…
-
Pump data In this menu all pump relevant parameters are set . The menu has the following structure Run-On Time 0003sec Max. allowable pump run time 0300sec Load rotation after 0300sec Time Start Delay P1->P2 Rated Current P1 06,0 A Rated Current P2 06,0A back to Main Menu 6.2.1 Run-on time In this…
-
Time delay start when using dual pump operation When the level exceeds the second upper setpoint or in case of high water, then both pumps run simultaneously under peak load operation mode. In order reduce possible mains overload caused by the inrush currents of the pumps, the second pump is…
-
Alarm Auto reset
mask: FFFFFF00 Mask REL1 7FFFFFFF Alarm Buzzer ON Mask REL2 0007FF00 Alarm Relais 1 NC Mask REL3 7FF00000 Alarm Relais 2 NC allowed T1-Alarms: Alarm Relais 3 NC High water alarm delay 0000sec 3 back to Main Menu In some parts of the alarm menus, it is required that a “mask word” be entered. Here…
-
Due to the graphic limitations of the display, the single bits can not be entered as series of 32 zeros and ones. Four bits at a time are compiled in a group (groups 1…8). In each group, four fault bits (0000, 0001, 0010, … 1000) are coded, which must be compiled and must be converted into a…
-
19 P1aux2
5 0100 (reserved) external resetting of faults (only HSK25) 20 external 5 1000 Input SCHW2 has switched x Fault pump 2 (only HSK25) 21 P2T1 6 0001 Thermo contact 1 has tripped x 22 P2nxT1 6 0010 Thermo contact 1 has tripped several times n 23 P2T2 6 0100 Thermo contact 2 has tripped n 24 P2MS 6 1000…
-
Resetting alarms When a fault (alarm) occurs, these alarms must be reset by pressing7 the OK key in the main display twice. The display shows “reset alarms” for approx. 1sec. and then returns to the main display. In case of a fault and the OK key in the main display is pressed only once, then only…
-
Alarm buzzer In this menu, the internal alarm buzzer of the HSK can be switched on or off. If the buzzer is activated, an alarm is sounded in case of any fault occurrence. 6.4.6 Allowed T1 alarms If during operation a T1 alarm frequently occurs (possible systematic fault), for example due to…
-
Language selection In this menu, the language to be used can be selected. Selection is effected by the ▲- or ▼-key. The selected language is confirmed with the OK-key. All text messages appear in the selected language. 6.5.2 Changing passwords In this menu the password of the controller can be…
-
Short time start In case pumps have not run for a long period of time, it may be desired to start the pumps regularly for a short time. By means of the short time start up, it is possible to start the pump every x hours for y seconds. The values for x and y may be entered in this menu. If the pump…
-
System indications In the system indications menu the operation indications are displayed. The menu has the following structure: 6.6.1 Pump hour indication In the menu point “Operating hours”, the operating hours of the respective pump is displayed. The operating hours are counted when the…
-
Switching behavior The switching levels determine when the pump(s) is (are) switched on or off. When the controller is operated using a continuous level measuring system (level sensor or impact pressure method), then the measured levels are directly processed and evaluated. When the controller…
-
Float switch state
Pump state float 1 Float 2 Pump 1 Pump I 0 I 0 I I I 0 All other states: sensor fault 0 0 Switching behavior in a two float switch operation with two pumps Float switch state Pump state Float switch 1 Float switch 2 Float switch 3 pump1 pump I -> Unchanged I -> 0-> I Unchanged -> I All other states…
-
open again, then the controller starts with the set time delay. If this function has been activated, then "external OFF" appears in the second line of the display. 8.3 External alarm13 Should the controller not be operated with float switches, the possibility to give an external alarm using the SW2…
-
P1MS Motor protection has tripped The manual motor protection of the pump 1 has tripped. The pump is switched off. If AUTO in the menu "Alarm Reset ” has been selected, then the controller automatically restarts after switching the manual motor starter on again. 13 P1FI RCD (ELCB) has tripped The…
-
There are three (HSK25) or two (HSK15) voltage free relays (SPDT) as alarm outputs available
10 Standard settings The control is delivered with the following factory standard default settings: Parameter Value Parameter Value Number of pumps 2 Start time delay 3 sec Measuring method Level sensor Load rotation after 0(Off) Minimum pressure 0 cm T1-Alarm after 3x Cut-out level Pump 1 10 cm…
-
Connection of thermo contacts
11.2 Pumps with PTC In such cases where pumps feature a cold conductor (PTC) to monitor temperature, the conductor must be connected to a PTC motor protection relay (for Ls A1 Y1 Y2 21 example Scharco FTM BV97-230V). It is recommended to 13 adjust the relay for automatic reset and to carry out the…
-
(in the second line the measured rechargeable battery voltage and the internal control voltage are displayed). The control shall continue to operate only when the rechargeable battery voltage or the control voltage have reached their rated values again. It takes approx. 50h until the rechargeable…
-
Wiring diagram examples
HSK_operating_manual_English_Ver3.doc HOMA Pump Technology - 34 -
-
The connection diagrams above explain the principal connecting possibilities using various level
measuring methods: 1. Float switch 2. Level sensor with high water float switch 3. Bubbler system with high water float switch (float switch – connection to an electrical (Zener) barrier) 4. Float switch connected to an electrical (Zener) barrier 5. Level sensor with high water float switch…
-
after ▼-key
1.12: P1MS 10.12.99 16:10 after ▼-key 1.10: P1MS 10.12.99 16:10 after ▼-key 1.1: HW 10.12.99 16:10 after ▲-key again 1.10: P1MST1 10.12.99 13:07 and so forth The fault occurrences can be browsed backwards by means of the ▲-key or forwards by means of the ▼-key. The first number in the fault memory…
-
Operation temperature range
-
12.4 Mounting
The control has been foreseen for wall mounting. For mounting purposes, 4 mounting holes for screws with a max. diameter of ∅6mm must be available. For installing, please open the cover and screw the control to the wall or to the mounting plate tightly with the four screws 180 mm. (Dimension of the…