Инструкция на Кассетные кондиционеры Fuji Electric. Сервисные инструкции.
Сплит-системы кассетного типа Fuji Electric серии RC-25E3A / RO-25E3A. Инструкция по обслуживанию.
Смотрите также: Сервисные инструкции →
Загружаем документ…
Текст инструкции
-
SPLIT TYPE
AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RC-25E3A RO-25E3A CONTENTS SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 OUTLINE AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CIRCUIT DIAGRAM . . .…
-
MODELS
RO-25E3A CONDITION REFRIGERANT CIRCUIT DISCHARGE PRESSURE 23.0 kg / cm2 G 5.0 SUCTION PRESSURE DISCHARGE TEMP. C 75 REFRIG. PIPE LENGTH m 7.5 DISCHARGE AIR TEMP. C 13 INDOOR ENTERING AIR TEMP. 27.0 / 19.0 DB / WB C OUTDOOR ENTERING AIR TEMP. 35.0 / 24.0 LIQUID PIPING PIPE DIA. SIZE 9.53 mm 15.88 GAS…
-
OUTLINE AND DIMENSIONS
Model : RC-25E3A Unit : mm 298.5 248.5 200 305.5 Model : RO-25E3A (Small pipe) 60 (Drain pipe) 100 (Small pipe) 298.5 248.5 70 (Large pipe) 305.5 235 60 (Drain pipe) Drain inside Dia. ø32 outside Dia. ø37 70 (Large pipe) 830 940
-
REFRIGERANT SYSTEM DIAGRAM
Indoor Unit Outdoor Unit Refrigerant pipe ø9.53mm(3/8" ) Capillary tube Distributor Dryer Evaporator Condenser Compressor Refrigerant pipe ø15.88mm(5/8" ) Charging valve Cooling : Flare coupling 5
-
CIRCUIT DIAGRAM
Model : RC-25E3A THERMISTOR (PIPE TEMP.) CN BLACK 1 1 CN RED RED ORANGE ORANGE YELLOW YELLOW WHITE WHITE BROWN BROWN CN 15 WHITE (L) (N) CN 5 THERMAL GRAY CN 1 CN 6 Use T 3A-250V Fuse on F101 BLACK N GRAY WHITE WHITE 1 1 WHITE 2 2 M STEP MOTOR FLOAT SWITCH L BLACK BLACK FILTER BOARD WHITE GREEN MAIN…
-
INDOOR PRINTED CIRCUIT BOARD
CIRCUIT DIAGRAM Model : RC-25E3A CONTROLLER PCB ASSEMBLY (MAIN PCB) EZ-0007WSE-C ROOM TEMPERATURE THERMISTOR AUTORESTART SWITCHING CUSTOM CODE SWITCHING CUSTOM CODE SWITCHING HEAT EXCHANGER THERMISTOR FILTER SUPPLY PCB EZ-000AHSE-P FAN SWITCHING FLOAT SWITCH 3(L) ZONE CONTROL SWITCHING 2(N) 1 ROOM…
-
When you order parts, please make a photocopy of this page and fill the number of the parts in the "Order" column. INDOOR UNIT [RC-25E3A] Ord. Ref. No. Q'ty Ref. No. Description 117-3 143-1 143-3 Capacitor (Fan Motor) Decoration Plate Grille Hook Holder Filter Hex. Nut w/Spring Washer Louver Support…
-
RO-25E3A
When you order parts, please make a photocopy of this page and fill the number of the parts in the "Order" column. OUTDOOR UNIT [RO-25E3A] Ref. No. Description Part No. Ord. Ref. No. Q'ty Description Part No. 13-2 13-3 15 Fan Cover (Guard) Emblem-Rear Cabinet-A, Painted Connector Cover Wire Assy…
-
[INDOOR UNIT]
-
STANDARD ACCESSORIES
INDOOR UNIT ACCESSORIES Name and Shape Q'ty Application Part No. Coupler heat insulation } 2 For indoor side pipe joint 9350716029 1 each 9352766015 10 For installing the remote control unit cord 313714181904 10 For installing the remote control unit cord clamp 301141153027 2 For installing the…
-
0104K1849
April 2001 Printed in Japan
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.