EEDEN08-205
technical data ventilation VAM-FA8VE
-
EEDEN08-205
technical data ventilation VAM-FA8VE
-
TABLE OF CONTENTS
VAM-FA8VE 1 External appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Model series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Nomenclature . . . . . . . . . . . . .…
-
TABLE OF CONTENTS
VAM-FA8VE 10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Reducing operating sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Centralized piping . . . . . . . . . . . . .…
-
Structures VAM150-1000FA Heat exchange elements 3 Ceiling hock Maintenance cover OA (Outdoor air) [Fresh air from outdoor] EA (Exhaust air) [Exhaust air to outdoor] Switch box Duct connection flange Exhaust fan Name plate Air filter (Long life filter) SA (Supply air) [Feed air to room] Air supply…
-
Features
5-1 1. 2. 3. 4. 5. 6. 7. 8. 9. Interlocked operation with VRV (SkyAir) Simultaneous ON / OFF with the indoor unit by the indoor unit remote control. HRV independent operation during air conditioning off season by the indoor unit remote control. Automatic ventilation mode changeover: Auto / Heat…
-
Features
5-2 Energy Saving By heat recovery operation 3 Approx. 20% reduction of heating / cooling load HRV unit recovers the thermal energy during cooling / heating operation of air conditioner. HRV reduces the cooling / heating load drastically and enhances the heating / cooling efficiency. Exhaust Air…
-
Features
5-3 FRESH-UP operation Both the excessive supply mode and the excessive exhaust mode are selectable. This function creates a more comfortable air environment. Detail Major effects 3 Supply Fresh-up (Excessive outdoor air supply) Exhaust Fresh-up (Excessive Exhaust air supply) Supply air volume can…
-
Features
5-5 Easy Installation and service maintenance Downsized Total volume is reduced to 68% of EJ series and the unit fits into a small space. 3 (Comparison with FJ and previous EJ series) Height Model name FJ VAM 500FA EJ Height Difference (mm) Volume compared with EJ series 285 ← 310 –25 68% VAM 800FA…
-
Selection Procedures
Various methods are used to calculate the required ventilating airflow rate according to CO2 generated by inhabitants in a room, waste gas generated by use of fire, and other conditions of a room. Here are 2 patterns of calculating methods. 6-1 Based on inhabitants Required ventilating = air flow…
-
Selection Procedures
6-2 Based on Room size <Table 3> Criteria for Model Selection 3 Required ventilating AFR per person (m3 / h / person) Area per person (m2 / person) Frequency Model Name VAM 150FA VAM 250FA VAM 350FA VAM 500FA 3 VAM 650FA VAM 800FA VAM1000FA VAM1500FA VAM2000FA VAM 150FA VAM 250FA VAM 350FA VAM 500FA…
-
Selection Procedures
6-2 Based on Room size Required ventilating AFR per person (m3 / h / person) Area per person (m2 / person) Frequency Model Name VAM 150FA VAM 250FA VAM 350FA VAM 500FA 3 VAM 650FA VAM 800FA VAM1000FA VAM1500FA VAM2000FA VAM 150FA VAM 250FA VAM 350FA VAM 500FA 40 5 VAM 650FA VAM 800FA VAM1000FA…
-
Product Specification
7-1 Specifications 7-1-1 Technical specifications 3 (50Hz) Model name Power supply VAM150FA Ultra-High High Low Ultra-High High Low Ultra-High High Low Temperature exchanging efficiency Cooling Enthalpy exchange efficiency Heating Heat exchange mode Normal input Bypass mode Heat exchange mode Normal…
-
Product Specification
7-1 Specifications 7-1-1 Technical specifications 3 (50Hz) Model name Power supply VAM500FA Single phase 220 – 240 V / 50Hz Temperature exchanging efficiency Cooling Enthalpy exchange efficiency Heating Heat exchange mode Normal input Bypass mode Heat exchange mode Normal Amp. Bypass mode Casing…
-
Product Specification
7-1 Specifications 7-1-1 Technical specifications 3 (50Hz) Model name VAM800FA VAM1000FA Power supply VAM1500FA VAM2000FA Single phase 220 – 240 V / 220 V, 50 / 60 Hz Temperature exchanging efficiency Cooling Enthalpy exchange efficiency Heating Ultra-High % High % Low % 76 76.5 78 78 Ultra-High %…
-
Product Specification
7-1 Specifications 7-1-1 Technical specifications Test conditions are as follows Condition Indoor unit 3 Outdoor unit °CDB R·H (%) °CDB Cooling condition Heating condition R·H (%) Notes: 1. Operation sound is measured at 1.5 m below the center the body. 2. Air flow rate can be changed over to Low…
-
Product Specification
7-1 Specifications 7-1-2 Electrical specifications 3 Units Model name Power supply 50Hz 60Hz FM MCA MFA kW FLA 0.9 15 0.03 × 2 0.4 × 2 VAM250FA 0.9 15 0.03 × 2 0.4 × 2 VAM350FA 1.35 15 0.03 × 2 0.6 × 2 VAM150FA VAM500FA Power supply Power supply 1.35 15 0.03 × 2 0.6 × 2 VAM650FA max.264V max. 242V…
-
RA
(RETURN AIR FROM ROOM) • Ventilation • Heat Reclaim Ventilation INSPECTION HOLE (FIELD SUPPLY) METAL SUSPENSION BRACKET FOR ABSORBING VIBRATION (FIELD SUPPLY) NOMINAL DIAMETER SUSPENSION BOLT (FIELD SYPPLY) EA (EXHAUST AIR TO OUTDOORS) OA (FRESH AIR FROM OUTDOORS) A GRADIENT OF MORE THAN ONE IN…
-
Product Specification
7-2 Optional accessories Optional Accesories Model 3 Item Controlling device VAM150FA Remote control Wired remote controller Central remote control Centralized controlling Unified On/Off control device schedule timer Duct adapter Nominal pipe diameter (mm) Duct adapter Adapter for discharge…
-
Product Specification
7-2 Optional accessories 7-2-1 BRC301B61: Remote control 7-2-1-1 Remote control mounting instructions 3 1. Remove the upper part of remote control. Insert minus screwdriver into the slots in the lower part of remote controller (2 places), and remove the upper part of remote control. The PC board is…
-
Product Specification
7-2 Optional accessories 7-2-1 BRC301B61: Remote control 7-2-1-1 Remote control mounting instructions 3. Wire the HRV unit. NOTE When wiring, run the wiring away the power supply wiring in order to avoid receiving electric noise (external noise). Connect the terminals on the upper part of the remote…
-
Product Specification
7-2 Optional accessories 7-2-2 KRP50-2: Wiring adapter for remote contact / Humidifier KRP50-2A90: Installation box for adapter PCB Components 1. KRP50-2 PCB (×1) 3 2 KRP50-2 can also be connected to SkyAir indoor unit for the interlocked operation with HRV units. Or to be connected and used for the…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices KRP2A51 (For Europe) KRP2A61 (For General) Accessories Check the following accessories are included in the kit before the installation. Wiring Adapter for Electrical Appendices (1) ´ 1 PCB support ×4 Clamp ×3…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 3 Indoor unit To host computer monitor panel etc. Max. 16 unit Remote controller Max. 64 groups Max. 16 unit To outdoor unit Notes: Individual indoor units connected to the centralized line cannot be displayed…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices Installation Ceiling mounted corner cassette Adapter (KRP2A61 KRP2A51) Electric parts box PCB support P board ass’y (HC0118) 4-way blow ceiling mounted cassette Lid of PCB Box (Option KRP1C98) Adapter…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 2-way blow ceiling mounted cassette 3 Box for adapter PCB (Option KRP1C98) Electric parts box Installation screw PCB support Adapter P board ass’y (KRP2A61 • 51) Note: A separate plate is needed to install the…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices Concealed ceiling unit (large) 3 200 • 250 40-125 PCB support Adapter (KRP2A61 • 51) Adapter (KRP2A61) Indoor PC board P board ass’y PCB support Electric parts box Electric parts box (HC0248) Ceiling suspended…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices (Concealed) floor standing unit 3 P board ass’y PCB support Electric parts box Adapter (KRP2A61 • 51) (HC0250) Electrical wiring 1. First, wire between the indoor and outdoor units, then to the separate power…
-
таблицы и схемы — в просмотре
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 3 Wiring to external units (host computer monitor panel) 1. Remote control input (operation control) Wire as described below. Wiring differs depending on whether using a voltage or non-voltage input. • For…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 2. Setting control mode selector sitch (RS1) 3 Using control mode selector switch (RS1), select the control mode as described below. CONTROL MODE RS1 Factory set: “0” position 1. When operating with only…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices • For demand control from input B Position C D E F Function when input A is ON Remote controller rejected (Same as position “5”) Last command priority (Same as position “6”) 3 Function when input B is ON Forced…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 3. Temperature setting input 3 To enable temperature setting from both the adapter and remote controller, set SS2 to “P”. (Factory set: P) P: Enables temperature setting by both the adapter and remote…
-
Product Specification
7-2 Optional accessories 7-2-3 KRP2A51, KRP2A61: Wiring adapter for electrical appendices 4. Cancelling display signals 3 Operation output terminals (W1 and W2) and malfunction output terminals (W3 and W4) are non-voltage constant contact output. (Allowed electric current per contact is between 10…
-
Product Specification
7-2 Optional accessories 7-2-4 KRP1B61: Interlock adapter of VRV Accessories Check if the following accessories are included in the kit. Adapter X1 PC board support ×4 Clamp ×3 Installation manual ×1 (HC0129) Notes • Kits vary according to applicable models. • A special adapter fixing plate and box…
-
Product Specification
7-2 Optional accessories 7-2-4 KRP1B61: Interlock adapter of VRV Electric Wiring 3 • Refer to the WIRING DIAGRAM attached to the indoor unit before attempting to wire. [Make sure wires to units do not pass over the PC board when wiring.] • Wire the adapter to the indoor unit as shown below, X2A X16A…
-
Product Specification
7-2 Optional accessories 7-2-4 KRP1B61: Interlock adapter of VRV Installation 3 • Installation differs according to models. • Do not bundle low and high voltage wires together. • Bundle any access wires with the attached clamps so as to keep loose wirings off the indoor unit PC board. Concealed…
-
Product Specification
7-2 Optional accessories 7-2-4 KRP1B61: Interlock adapter of VRV Concealed ceiling unit (large) 40 ~ ~ 250 Indoor PC board Electric parts box Adapter Indoor PC board (KRP1B61) PCB support PCB support Adapter (KRP1B61) Electric parts box (HC0137) (HC0138) (Concealed) floor standing unit Indoor PC…
-
Product Specification
7-2 Optional accessories 7-2-5 KRP1B2: Interlock adapter of VRV Contents of kit Prior to installation check whether you have the complete kit of parts as shown below including the installation manual. PC board support Plastic straps Installation manual Adapter PCB for wiring 1 set 4 pieces 3 pieces…
-
Product Specification
7-2 Optional accessories 7-2-5 KRP1B2: Interlock adapter of VRV Electrical wiring 3 • Refer to the wiring diagram of the indoor unit for it’s wiring connection. (Make sure all the wiring to the unit should not go over the PC board.) • Connect the wiring to the indoor unit as shown below. · CN33 For…
-
Product Specification
7-2 Optional accessories 7-2-6 KRP1B3: Interlock adapter of VRV Contents of kit Prior to installation check whether you have the complete kit of parts as shown below including the installation manual. 3 Adapter PCB Plastic strap Installation manual 1 set 3 pieces 1 piece CN1 (HC0217) Name of parts…
-
Product Specification
7-2 Optional accessories 7-2-6 KRP1B3: Interlock adapter of VRV 3 Electrical wiring • Refer to the wiring diagram of the indoor unit for its wiring connection. (Make sure all the wiring to the unit should not go over the PC board.) • Connect the wiring to the indoor unit as shown below. CN2 Indoor…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control • When using 1 central remote controller a b g c d e f h • When using 2 central remote controllers a c d e f i j k l b m g BEFORE USE: GENERAL DESCRIPTION OF SYSTEM For a maximum of 64 groups of indoor unit unified operation/stop can be…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 GROUP OF INDOOR UNIT refers to the above. A: A single indoor unit without remote controller B: A single indoor unit controlled by one or two remote controllers C: Maximum of 16 indoor units, group-controlled by one or two remote…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 Fig.1 · CENTRAL REMOTE CONTROLLER · ZONE ZONE · 9 · CODE · SELECT ALL · · No. No. ALL · · · · · · · · ZONE ZONE MONITOR · CIRCUIT SET · GROUP · REF. ZONE GROUP · · TEST · CODE No. · · · C No. REF CIRCUIT HOST OK RESET RESE TEST (HC0147)…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 ALL ALL CENTRAL REM OTE CONTROLLER Fig. 3 ZONE ZONE SET 1·5 SELECT ZONE ZONE ZONE GROUP REF CIRCUIT CODE No. No. OK RESET RESE TEST (HC0149) ALL ALL CENTRAL REM OTE CONTROLLER ZONE MONITOR Fig. CODE No. No. C 2 SELECT ZONE ZONE GROUP…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 ALL ALL CENTRAL REM OTE CONTROLLER Fig. 7 MONITOR GROUP C SELECT ZONE ZONE ZONE GROUP REF CIRCUIT CODE No. No. 1 2 OK RESET TEST (HC0153) ALL ALL CENTRAL REM OTE CONTROLLER Fig. 8 MONITOR GROUP ZONE C TEST SELECT ZONE ZONE GROUP REF…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 ALL ALL CENTRAL REM OTE CONTROLLER Fig. 10 1 MONITOR GROUP SELECT ZONE ZONE ZONE GROUP REF CIRCUIT No. 1 3 CODE No. OK RESET TEST 2·4 (HC0156) ALL ALL CENTRAL REM OTE CONTROLLER Fig. 11 1 MONITOR GROUP C SELECT ZONE ZONE ZONE GROUP REF…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control FEATURES AND FUNCTIONS Operation menu This central remote controller enables the individual operation/stop by zone, and unified operation/stop. ON/OFF operation controlled by timer is possible in conjunction with the schedule timer…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 NAMES AND FUNCTIONS OF THE OPERATING SECTION (Fig. 1,2) “ UNIFIED OPERATION BUTTON 10 1 Press to operate all indoor units. UNIFIED STOP BUTTON Displays the operation timer No. when used in conjunction with the schedule timer. “ 2 No.”…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 “ 18 ”“ ” DISPLAY (TIME TO CLEAN AIR CLEANER ELEMENT/TIME TO CLEAN AIR FILTER) TEMPERATURE SETTING BUTTON 26 Displayed to notify the user it is time to clean the air filter or air cleaner element of the group displayed. Press to set…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control You can set multiple groups under a single zone to control them by zone. This equipment is factory set for 64 zones of 1 group per every zone at the time of shipment. 1 1 Press the ZONE SETTING BUTTON, and “ ZONE SET ” is displayed. Zone…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control OPERATION 4 Press the TIMER ON BUTTON. Press the TIMER ON BUTTON within 10 seconds after the code No. is displayed. The display stops flashing and lights up solidly. OPERATION BY ZONE (Fig. 4) CODE No. Flow of operation by zone CODE No.…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 Cooling mode is selected. 8 Unified operation is not set within the zone. Press the TEMPERATURE SETTING BUTTON. Each time you press the “ ”, the temperature rises by 1°C. Each time you press the “ ”, the temperature falls by 1°C. If you…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control OPERATION MODE The following five operation control modes can be selected along with the temperature setting and operation mode by remote controller, for a total of twenty different modes. These twenty modes are set and displayed with…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 Control by remote controller Operation Unified operation, individual operation by central remote controller, or operation controlled by timer Operation mode Unified stop, individual stop by central remote controller, or timer stop…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control ON/OFF control possible by remote controller 3 SET1 ON OFF PM SET2 ON OFF PM AM PM Operation controlled by timer Centralized Programmed to operate at 8:45 Stop Remote controller Programmed to stop at 5:00 Programmed to operate at 5:20…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control • List of setting operation SETTING OPERATION MODE (Fig. 5) 3 A: Zones not displayed Display Setting Contents of setting • The Zone consists of the following two cases. To be set by zone A. Zone without display “ ” The group with master…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control TEMPERATURE SETTING (Fig. 6) 1 GROUP MONITORING (Fig. 7) Utilize the group monitor function in each of the following cases: 1. Check the malfunction code. (See the next page.) 2. Check the group that requires cleaning of the air filter…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control ERROR DIAGNOSING FUNCTION (Fig. 8) SETTING MASTER REMOTE CONTROLLER (Fig. 9) This central remote controller is provided with a diagnosing function, for when an indoor unit stops due to malfunction. In case of actuation of a safety device…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control FUNCTION OF REFRIGERANT SYSTEM DISPLAY (Fig. 10) DISPLAY OF TIME TO CLEAN (Fig. 11) The following information becomes available by utilizing this function. • Indoor group connected with the same outdoor unit • Indoor group with the master…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 UNIFIED OPERATION (Fig. 12) Use this function when executing operation and stop of all the connected indoor units. A Unified operation Press the UNIFIED OPERATION BUTTON. All the displays “ ” of the group No. in operation light up at…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control OPTIONAL ACCESSORIES b a You can perform the normal operation, take off the malfunction contact point and unified operation/stop by contact point, all by connecting this unit with the unification adapter for computerized control. For…
-
Product Specification
7-2 Optional accessories 7-2-7 DCS302C51: Centralized control 3 SPECIFICATIONS Specifications Power supply Single phase, 50 / 60 Hz, 220 – 240 V / 220 V Power consumption Max. 4.5 W Forced ON / OFF input Continuous “a” contact Contact current: approximately 10 mA Size 180 (W) x 120 (H) x 64.5 (D)…
-
Product Specification
7-2 Optional accessories 7-2-8 DCS301B61: Unified ON / OFF control NAMES AND FUNCTIONS UNIFIED OPERATION/STOP BUTTON Starts/stops all indoor units. “UNDER HOST COMPUTER INTEGRATED CONTROL” When this lamp turns on, no other operations are possible. HOST ALL ALL UNIFIED ON/OFF CONTROLLER GROUP NO.…
-
Product Specification
7-2 Optional accessories 7-2-8 DCS301B61: Unified ON / OFF control 3 Put the attached indication sticker on the room name indication plate. 3 In case of serial type In case of serial type Indication plate Indication sticker Put the sticker aligning the lines of the sticker with those of the plate.…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer CAUTIONS DURING USE • Do not tamper with the inner mechanism. Do not remove the front panel. Tampering with the inner mechanism is dangerous and may damage equipment. For inspection and adjustment, contact your DAIKIN dealer. • Avoid places…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer 3 Fig.1 ALL ALL SCHEDULE TIMER PROGRAM START OFF OFF OFF OFF OFF OFF OFF SET 1 ON OFF AM PM ON OFF AM PM AM PM 7 MON TUE WED THU FRI SAT SUN NO. SET 2 MON TUE WED THU FRI SAT SUN 8 AM PM AM PM CLOCK NO. PROGRAM DAY (1 ~ 7) CLOCK DAY OFF HR. (1…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer 3 ALL ALL SCHEDULE TIMER ALL ALL SET 1 OFF OFF SCHEDULE TIMER 6 ON SET 1 5 OFF Fig. 3 6 Fig. 4 7 SAT SUN 5 ON SET 2 FRI CLOCK OFF AM PM PM NO. PROGRAM DAY (1 ~ 7) CLOCK DAY OFF HR. (1 ~ 12 ) MIN. (1 ~ 60) OFF PM ON OFF PM PM PM 18 PROGRAM NO.…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer 3 NAMES AND FUNCTIONS OF THE OPERATING SECTION (Fig. 1,2) OFF AM PM UNIFIED OPERATION BUTTON 11 1 Press this button to perform the unified operation regardless of the No. of programmed time. DISPLAY “ SYSTEM OFF) ” (PROGRAMMED TIME OF Displays…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer OPERATION SETTING PRESENT TIME (Fig. 3) 5 FRI CLOCK PM Set the time to 5:30 p.m.. (Example) In case of setting Friday, 5:30 p.m. 4 1 Press the CLOCK ADJUSTING BUTTON. The present time display flashes. Note: The present time needs adjusting in…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer minute and hour by hour. When the button is kept pressed, the display is put forward continuously. SETTING NO. OF PROGRAMMED TIME (Fig. 4) PROGRAM START SET 1 ON OFF ON OFF AM 1 NO. MON TUE WED THU FRI SAT SUN 5 SET 2 FRI CLOCK (Example) Time…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer 8 Press the PROGRAMMING START BUTTON, and finish the program setting. Notes: • Unless the button is pressed within 20 minutes, the display will automatically revert back to the original state. In this case, setting contents up to the point…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer A. Change/cancel partially B. Cancel the whole 4 Press OK button if you do not want to change the timer on. The display of the next programmed time flashes. Each time you press it, the next area to be set flashes. SET 1 OFF OFF 1 NO. ON OFF PM…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer MANUAL OPERATION (Fig. 6) This schedule timer enables the operation/stop by pressing the UNIFIED OPERATION/STOP BUTTON in addition to the operation controlled by timer (operation/stop according to the programmed time) at any time. Press the…
-
Product Specification
7-2 Optional accessories 7-2-9 DST301B61: Schedule timer 3 SPECIFICATION SPECIFICATIONS Display of time 12-hour digital display Clock cycle type Quartz clock type Clock accuracy Within • 30 sec. / month (environmental temperature from 15°C to 35°C) Timer programming Two pairs of programmed time for…
-
Product Specification
7-2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill 3 Model name K-DGL100A K-DGL150A K-DGL200A K-DGL250A VAM150FA VAM250FA VAM500FA VAM 800FA VAM350FA VAM650FA Applicable model VAM1000FA VAM1500FA VAM2000FA Nominal pipe diameter (mm) φ 100 φ 150…
-
Product Specification
7-2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill 3 Dimensions K-DGL100A K-DGL150A 300 (Hook hole pitch) 350 (Hook hole pitch) – 5.5 × 9.5 slot (HC0242) K-DGL200A K-DGL250A 415 (Hook hole pitch) φ (Hook hole pitch) φ (Hook hole pitch) φ – 5.5 ×…
-
Product Specification
7-2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill 3 Installation procedure Before starting installation, attach the supplied packing to the adapter provided in the same package. (Attach the packing to the adapter flange so that it will be set…
-
Product Specification
7-2 Optional accessories 7-2-10 K-DGL100A, K-DGL150A, K-DGL200A, K-DGL250A: Air suction / discharge grill 3 Installing the ceiling material and gluing the wall paper Common works Duct connection and ceiling board installation 1. Put the duct into the adapter and fix them by winding tape around the…
-
Product Specification
7-2 Optional accessories 7-2-11 KDDM24A50, KDDM24A100: Silencer 3 Part No. KDDM24A50 KDDM24A100 Applicable model VAM500FA VAM650FA Nominal pipe diameter φ 200 mm φ 200 mm Noice suppression effect VAM800FA, VAM1000FA, VAM1500FA, VAM2000FA φ 250 mm Approx. 6 dB Applications and features Installation…
-
Product Specification
7-2 Optional accessories 7-2-12 YAFF323F15, YAFF323F25, YAFF323F35,YAFF323F50, YAFF323F65, YAFF323F100: Air filter replacement YAFF323F65 YAFF323F100 Applicable model VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA, VAM800FA VAM1500FA VAM1000FA VAM2000FA 3 Dimension Q’ty 2 A B Part No. YAFF323F15…
-
Product Specification
7-2 Optional accessories 7-2-14 K-FDS101C, K-FDS151C, K-FDS201C, K-FDS251C, K-FDS102C, K-FDS152C, K-FDS202C, K-FDS252C: Flexible Duct 3 Part Name: 1 m K-FDS101C K-FDS151C K-FDS201C Part Name: 2 m K-FDS102C K-FDS152C K-FDS202C K-FDS252C VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM 800FA VAM1000FA…
-
Product Specification
7-2 Optional accessories 7-2-16 BRP4A50: Heater control kit Operation range of the HRV is “ –10°C to 50°CDB 80% RH or below.” When operating the HRV units at or below –10°C of the outdoor air temperature, use preheater (field supplied) to preheat outdoor air. This kit is required to have ON / OFF…
-
Product Specification
7-2 Optional accessories 7-2-16 BRP4A50: Heater control kit Installation example 3 Return Air Exhaust Air HRV Preheater (Field supply) Supply Ai Outdoor Air Adapter BRP4A50 Temperature thermostat (Field supply) (Heater ON when the temperature is at or below – 10°C) Temperature thermostat (Field…
-
Product Specification
7-2 Optional accessories 7-2-16 BRP4A50: Heater control kit Heater control kit Accessories See the right for componens. Fixing Screw 2 pcs. Clamp 2 pcs. 3 Installation Install the Heater control kit to the outside of switch box for HRV unit as shown below. Fixing Screw Heater Control kit Switch Box…
-
Product Specification)
7-3 The correction ratio of exchange efficiency 3 Correction factor for the heat exchange efficiency 1.2 1.1 1 0.9 Exchange efficiency less than 50% 0.8 0.7 70% 0.6 90% 0.5 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 Supply air flow rate / exhaust air flow rate C: 4D023764 + 4D023764…
-
Product Specification)
7-4 Dimensions VAM150FA Maintenance space for the heat exchange elements, the air filters and fans Switch box 3 Ceiling hook 4-14x40 oval hole Inspection hole Supply air fan Maintenance cover SA Supply air to room OA Fresh air from outdoors (Outdoor air) RA Return air from room EA Exhaust air to…
-
Product Specification)
7-4 Dimensions VAM350FA 3 Maintenance space for the heat exchange elements, the air filters and fans Switch box Ceiling hook 4-14x40 oval hole Inspection hole Supply air fan Maintenance cover OA Fresh air from outdoors (Outdoor air) SA Supply air to room EA Exhaust air to outdoors RA Return air from…
-
Product Specification)
7-4 Dimensions VAM650FA Maintenance space for the heat exchange elements, the air filters and fans Switch box 3 Ceiling hook 4-14x40 oval hole Inspection hole Supply air fan Maintenance cover OA Fresh air from outdoors (Outdoor air) SA Supply air to room EA RA Return air from room Exhaust air to…
-
Product Specification)
7-4 Dimensions VAM1000FA 3 Maintenance space for the heat exchange elements, the air filters and fans Switch box Ceiling hook Inspection 4-14X40 oval hole hole Supply air fan Maintenance cover OA Fresh air from outdoor (Outdoor air) SA Supply air to room EA Exhaust air to outdoors RA Return air from…
-
Product Specification)
7-4 Dimensions VAM2000FA Maintenance space for the heat exchange elements, the air filters and fans Switch box Inspection hole 3 Ceiling hook 4-14X40 oval hole Supply air fan (2 pieces) Maintenance cover SA Supply air to room OA Fresh air from outdoor (Outdoor air) RA Return air from room EA Exhaust…
-
Product Specification)
7-5 Wiring diagram VAM150-1000FA 3 Wiring diagram Power supply single phase 220-240/220V 50/60Hz External output terminals Adapter for wiring (optionl accessories) (KRP50-2) Switch box Terminals for the input from outside Terminals for the centralized control Remote control (optional accessories) L…
-
Product Specification)
7-5 Wiring diagram VAM1500,2000FA 3 Wiring diagram Power supply Single phase 220-240/220V 50/60Hz Adapter for wiring (optional accesories) (KRP50-2) External output terminals Terminals for the input from outside Terminals for the centralized control Remote control (optional accessories) Switch box L…
-
таблицы и схемы — в просмотре
-
Product Specification)
-
таблицы и схемы — в просмотре
-
Product Specification)
7-6 Sound level data 7-6-3 Sound pressure spectrum Approximate threshold hearing for continuous noise Octave band center frequency (Hz) Octave band center frequency (Hz) Approximate threshold hearing for continuous noise Approximate threshold hearing for continuous noise Approximate threshold…
-
Product Specification)
7-6 Sound level data 7-6-3 Sound pressure spectrum Octave band center frequency (Hz) dB (0dB=0.0002μ bar 4D036883 dB (0dB=0.0002μ bar Approximate threshold hearing for continuous noise Approximate threshold hearing for continuous noise Octave band center frequency (Hz) 4D036890 Approximate threshold…
-
Product Specification)
7-6 Sound level data 7-6-3 Sound pressure spectrum VAM1500FA Approximate threshold hearing for continuous noise dB (0dB=0.0002μ bar Octave band sound pressure level Octave band sound pressure level Octave band sound pressure level 50Hz 220V dB (0dB=0.0002μ bar 3 VAM2000FA dB (0dB=0.0002μ bar…
-
Product Specification)
7-7 Fan performance VAM150FA VAM250FA Exchange efficiency 3 Exchange efficiency VAM150FAVE VAM250FAVE Temper ature ex Enthalpy efficiency efficiency exchange (heating) efficiency (cooling) Ultra-High High ø 100 Pipe length Low change exchange Enthalpy External static pressure (Pa) External static…
-
Product Specification)
7-7 Fan performance VAM800FA VAM1000FA Exchange efficiency Exchange efficiency 3 VAM800FA5VE rature rature nge e fficien cy Entha lpy ex c h a nge e Entha fficien lpy ex cy (he chang ating) e effic iency (Cooli ng) Ultra-High External static pressure (Pa) VAM1000FA5VE Tempe excha exchan Enthalp ge…
-
Product Specification)
7-8 Installation method VAM150FA 3 MAINTENANCE SPACE SUSPENSION BOLT POSITION INSPECTION HOLE AIR DISCHARGE GRILLE K-DGL100A OA (FRESH AIR FROM OUTDOORS) VAM150FA HEAT INSULATOR (FIELD SUPPLY) ROUND SHAPE HOOD (FIELD SUPPLY) EA (EXHAUST AIR TO OUTDOORS) AIR SUCTION GRILLE K-DGL100A SUSPENSION BOLT…
-
Product Specification)
7-8 Installation method VAM350FA MAINTENANCE SPACE 3 INSPECTION HOLE AIR DISCHARGE GRILLE K-DGL150A SUSPENSION BOLT POSITION OA (FRESH AIR FROM OUTDOORS) ROUND SHAPE HOOD (FIELD SUPPLY) HEAT INSULATOR (FIELD SUPPLY) VAM350FA EA (EXHAUST AIR TO OUTDOORS) SUSPENSION BOLT POSITION AIR SUCTION GRILLE…
-
Product Specification)
7-8 Installation method VAM650FA MAINTENANCE SPACE 3 INSPECTION HOLE OA (FRESH AIR FROM OUTDOORS) HEAT INSULATOR (FIELD SUPPLY) VAM650FA ROUND SHAPE HOOD (FIELD SUPPLY) EA (EXHAUST AIR TO OUTDOORS AIR DISCHARGE GRILLE K-DGL200A SUSPENSION BOLT POSITION AIR SUCTION GRILLE K-DGL200A SUSPENSION BOLT…
-
Product Specification)
7-8 Installation method VAM1000FA MAINTENANCE SPACE 3 AIR DISCHARGE GRILLE K-DGL200A INSPECTION HOLE SUSPENSION BOLT POSITION SILENCER KDDM24A100 (FRESH AIR FROM OUTDOORS) OA FLEXIBLE DUCT K-FDS252C ROUND SHAPE HOOD (FIELD SUPPLY) HEAT INSULATOR (FIELD SUPPLY) SUSPENSION BOLT POSITION VAM1000FA…
-
Product Specification)
7-8 Installation method VAM2000FA 3 Maintenance space Air discharge grille Suspension bolt position Suspension bolt position Silencer Inspection hole Flexible duct Maintenance space Round shape hood Field supply Branch duct EA (Exhaust air to outdoors) Nominal diameter Field supply Branch duct Field…
-
Operation
8-1 Method of operation 8-1-1 Operation with the remote control exclusively for Air conditioning operation HRV units. (BRC301B61) 3 For non-independent systems, starting / stopping operation and timer operation may not be possible. Use the air conditioner remote control or the Centralized control in…
-
Operation
8-1 Method of operation 8-1-2 Operating the HRV unit using the remote control of the VRV- system air conditioner When the VRV-system air conditioner is connected with the HRV unit with a direct duct, the remote control of the air conditioner cannot be used to select the VENTILATION mode. To use the…
-
Operation
8-2 Cautions in use 8-3 Maintenance (for a qualified service person only) ! WARNING Never inspect or service the unit by yourself. Ask a qualified service person to perform this work. (The qualified service person) ! CAUTION Only a qualified service person is allowed to perform maintenance. During…
-
Operation
8-3 Maintenance ! 3 CAUTION 1. Do not wash the air filter in hot water. 2. Do not dry the air filter over a fire. 3. Do not subject the air filter to direct sunlight. 4. Do not use organic solvent such as gasoline and thinner on the air filter. 5. Be sure to install the air filter after servicing.…
-
Control System
9-1 Introduction of control system The control systems introduced here is for the HRV unit adopting the high speed and high performance transmission system (DIII-NET), the same as the VRV systems and SkyAir series, 3 Description of system Control system Independent • Basic method to operate HRV unit…
-
Control System
9-2 Basic patterns 9-2-1 List of control system Control with two remote controllers Independent system Operation by main switch Control system Purposes and applications Description of system Optional accessories required BRC301B61 Liquid crystal remote controller • Basic method to operate HRV unit…
-
Function
BRC301B61 • ON / OFF • Ventilation mode (Auto / Heat Exchange / Bypass) • Ventilating rate (High / Low) • Fresh up mode (On / Off) BRC301B61 • ON / OFF • Ventilation mode (Auto / Heat Exchange / Bypass) • Ventilating rate (High / Low) • Fresh up mode (On / Off) • Timer setting (On / Off) •…
-
Control System
9-2 Basic patterns Interlocked operation system with VRV systems and SkyAir series 3 Interlocked operation with 2 or more groups Control system Purposes and applications Optional accessories required Description of system KRP2A61 • When the HRV unit is interlocked to 2 or more groups of indoor…
-
Function
Nos. of the unit controlled and length of wiring • The HRV unit operates of one of the indoor units connected to the central control transmission line is in operation. • The various setting for the operation of HRV unit should be set by the remote controller for the indoor unit. • A maximum of 64…
-
Control System
9-2 Basic patterns 9-2-2 Independent system Operation by main switch 3 Purposes and functions • Basic method to operate HRV unit The remote control for HRV unit is installed on each HRV unit for its operation. [When you use remote control for HRV unit] Cautions 1. The remote control for HRV unit…
-
Control System
9-2 Basic patterns 9-2-2 Independent system Control with two remote controls Purpose and functions • For control of one HRV unit (Also one group control is possible) Sophisticated operation and indication output are possible from either local place or remote place by two liquid crystal remote…
-
Control System
9-2 Basic patterns 9-2-3 The interlocked operation system Single-group interlocked operation (Basic pattern) 3 Purposes and functions • The remote control for indoor unit can control the interlocked operation with the HRV unit, and it can make an initial setting of the ventilation flow rate, the…
-
Control System
9-2 Basic patterns 9-2-3 The interlocked operation system Interlocked operation with 2 or more group of VRV system Purposes and functions • When the HRV unit is interlocked to 2 or more group of indoor units, the HRV unit operates, if one of indoor unit in groups is in operation. The HRV unit can…
-
Control System
9-2 Basic patterns 9-2-4 Centralized control system Collective / individual control [Unified On / Off control DCS301B61] 3 Purposes and functions • One control can control the operation of “ON / OFF” of 16 groups of the units collectively or individually. Also up to 4 controls can be installed in…
-
Control System
9-2 Basic patterns 9-2-4 Centralized control system Zone control system (Central remote control DCS302B61) 3 Example of control wiring Multi-function centrailized Power supply Zone 1 F1 F2 J1 J2 JC SS1 X9A P1 P2 HRV unit Indoor unit P1 P2 P1 P2 Remote control for indoor unit J1 J2 JC X9A •…
-
Control System
9-3 Applicable patterns 9-3-1 Additional functions Operation by power supply [HRV unit] Example of control wiring Purposes and functions • The HRV unit is operated by “On / Off” of the main power breaker. This is possible only for the independent operation system. (When the main power is…
-
Control System
9-3 Applicable patterns 9-3-1 Additional functions Fresh-up operation by external input [HRV unit] Purposes and functions When the operation is interlocked with the local ventilating fan (such as the one for toilet or kitchen), the HRV unit performs the over-supply operation to prevent the reverse…
-
Control System
9-3 Applicable patterns 9-3-1 Additional functions Precool / preheat operation 3 Purposes and functions • The operation of HRV unit is delayed when the air conditioner begins operation. Cautions 1. The precool / preheat function is possible only when the operation of HRV unit is interlocked to…
-
Control System
9-3 Applicable patterns 9-3-2 To connect the remote control to the HRV unit (Part 1) single-group interlocked operation Purposes and functions When the HRV unit is interlocked to the single-group control system, the remote control for HRV unit will be connected to change the setting mode at the HRV…
-
таблицы и схемы — в просмотре
-
Control System
9-3 Applicable patterns 9-3-3 Central control system (DCS302B61) Collective operation (Schedule timer DST301B61) Purposes and functions • A maximum of 128 units can be controlled the collective operation / stop by weekly schedule. Cautions 1. The setting of group number for central control is not…
-
Control System
9-3 Applicable patterns 9-3-3 Central control system (DCS302B61) Collective operation [Adapter PCB for remote control KRP2A Series] 3 Purposes and functions A maximum of 64 groups can be controlled the operation of “ON / OFF” collectively. (For the individual control, use the central remote control…
-
Control System
9-3 Applicable patterns 9-3-3 Central control system (DCS302B61) Multi function central control + Unified On / Off Control 3 Proper control should be selected according to the functions required. System description Zone setting (Collective operation for plural group) Power supply RC1 Central remote…
-
Control System
9-3 Applicable patterns 9-3-4 Examples of mistakes in wiring and system designing It is necessary to install the remote control for the transmission The centralized transmission line should be connected to line. the indoor unit. <Part 1> • When you connect the transmission line for the remote…
-
Control System
9-3 Applicable patterns 9-3-4 Examples of mistakes in wiring and system designing Setting of Remote Control for HRV unit 3 List of Settings Mode no. Group settings Individual settings Setting switch no. Approx. 2500 hours Approx. 1250 hours No counting — — — — Off On — — — 30 min 45 min 60 min…
-
таблицы и схемы — в просмотре
-
Control System
9-5 Fan operation setting With remote controller for indoor unit With remote controller for HRV unit With remote controller Centralized control system Independent system Centralized control system Independent system Interlocked operation system Initial setting by the remote controller for indoor…
-
Control System
9-7 Operation mode change over 1. In case of cooling operation 3 Outdoor temp.(O.T.) 1 zone: Free cooling (cooling by outdoor air) in bypass mode.* Set temp. of A / C 2 zone: Room temperature to be achieved to set temperature by heat exchange mode. Heat exchange Cooling 3 zone: Room temperature to…
-
Installation
10-1 Reducing operating sound 1 Use a sound-insulating (low-permeability-to-sound) ceiling. Note: Some sound-insulating ceilings are not very effective in reducing low-frequency element of the operating sound. The air suction and discharge grille may give out operating sound higher by 8 to 11 phons…
-
Installation
10-1 Reducing operating sound 10-1-4 Effect of remedy for sound Caution 1. Be sure to connect a flexible duct (2 m) to an outlet of the main body in the indoor air supply side. 2. Do not connect a spiral duct and an alminium bellows directly to the outlet of the main body. * A silencer is effective…
-
Installation
10-2 Centralized piping Fig.2: Install a duct for each HRV unit. Wherever possible, avoid centralized OA and EA pipings for two or more HRV units, and install ducts for each body of the unit. (Fig. 2) : Direction of air flow (Indoor side) Because the air flow shown in Fig.1 is generated when…
-
Installation
10-3 Cautions When a smoke back flow prevention damper is installed 1. Install the unit on a rigid and stable place. Refer to the specification and weight of the unit. 3 Smoke back flow prevention damper Use suspension bolts for installation. Confirm that the place for installation can stand the…
-
Installation
10-3 Cautions OA SA RA Note: If the outdoor discharge air exceeds 95% RH, please preheat the outdoor suction air before it goes through the heat exchanger. Absolute humidity (kg / kg) RH y =< nc ie fic f e y B% alp ling h t o En co in Sa tu rat ion 95 cu rve % 1) Operation in highly humid areas (in…
-
Installation
10-4 Cautions in installation 10-5 Do not use a HRV or an air suction / discharge grille in the following places. 3 • Place such as machinery plant and chemical plant where gas, which contains noxious gas or corrosive components of materials such as acid, alkali, organic solvent and paint, is…
-
Installation
10-6 Duct Work 10-6-2 Going through the external wall 1. Hole diameter 10-6-1 Caution Duct dia. + 50 or 75 (I.D. depends on the core drill specification) • Do not install ducts as shown below. 3 <e.g.> (2) Multi bend (1) Extreme bend Duct diameter φ 100 + 50 φ 150 + 50 Do not bent the duct over…
-
Installation
10-7 Electrical wiring procedure ! Before obtaining access to terminal devices, all power supply circuits must be interrupted. Connection of Wiring 3 • Connect the wires in accordance with the diagram of each system. • All wiring must be performed by an authorized electrician. • All field supplied…
-
Installation
10-7 Electrical wiring procedure ! PRECAUTIONS 1. Do not connect wires of different gauge to the same power supply terminal. Looseness in the connection may cause overheating. When connecting more than one wire to the power supply wiring, use a 2 mm2 (φ 1.6) gauge wire. View seen from VRV Terminal…
-
Installation
10-7 Electrical wiring procedure 10-7-1 Opening the switch box 3 VAM1500,2000FA VAM150-1000FA Electrical compartment mounting base (Electrical compartment cover) Printed circuit board Electric component mounting base Grounding terminal Electric component mounting base Terminal board slide Printed…
-
Installation
10-8 Initial setting 10-8-1 Initial setting by the remote control for indoor unit Purpose Controller • Interlocked operation Operating procedure for initial setting The following describes the operating procedure and settings. 햲 When in the normal mode, press • Remote control for indoor unit 3 the “…
-
Installation
10-8 Initial setting 10-8-2 Setting procedure of group no. for centralized control The following shows the procedure how to set the group number for the centralized control by the remote control for indoor unit 3 Purpose Control Operating procedure The following describes the operating procedure and…
-
Installation
10-8 Initial setting 10-8-3 Initial setting for “Central zone control” When HRV unit is connected to the central transmission line (terminal connector no. (F1) and (F2)), it is necessary to make a initial setting of “collective zone interlock” by the remote control for indoor unit. (Factory set…
-
Daikin Europe N.V. is approved by LRQA for its
Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. ISO14001 assures an effective environmental management system in order to help protect human health and…