EEDE05-7
technical data Fan coil units FWV - low wall unit FWL - flexi type unit FWM - concealed flexi type unit FWD - duct unit FWB - small duct unit
-
“ The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy…
-
EEDE05-7
technical data Fan coil units FWV - low wall unit FWL - flexi type unit FWM - concealed flexi type unit FWD - duct unit FWB - small duct unit
-
• Chillers • R-407C • FAN COIL UNITS
-
TABLE OF CONTENTS
FWV/FWL/FWM/FWD/FWB 1 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2 Features 7 3 Specifications Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . .…
-
Features + Low maintenance and high effeciency − Quick removal of washable filter − Removable grilles − Only 4 screws to access the fan motor − Easy access to control valves + Controllers are easy to read and operate! − 3 different controllers: 2 electronic controllers (built-in or remote) 1…
-
Specifications 3 3-1-3 FWD - 2-pipe series 3-1 NOMINAL CAPACITY and NOMINAL INPUT Technical specifications MODEL POWER CONSUMPTION Current input COOLING CAPACITY (1) HEATING CAPACITY (2) W A kW kW kW FWD04A* 177 0.77 3.90 3.08 4.05 FWD06A* 274 1.34 6.20 4.65 7.71 mm kg FWD04A* 280x754x559 33 FWD06A*…
-
Specifications 3-1-4 FWD - 4-pipe series Technical specifications 3 NOMINAL CAPACITY and NOMINAL INPUT MODEL POWER CONSUMPTION Current input COOLING CAPACITY (1) HEATING CAPACITY (2) W A kW kW kW FWD04A* 177 0.77 3.90 3.08 4.49 FWD06A* 274 1.34 6.20 4.65 6.62 mm kg FWD04A* 280x754x559 35 FWD06A*…
-
Specifications 3 3-1-5 FWB 3-1 NOMINAL CAPACITY and NOMINAL INPUT Technical specifications MODEL POWER INPUT COOLING CAPACITY (1) high medium low Total capacity high medium low high medium low high medium low high medium low Sensible capacity HEATING CAPACITY (2) (2-pipe) HEATING CAPACITY (2)…
-
Specifications 3-2-1 FWV-FWL-FWM Electrical specifications 3 ELECTRICAL SPECIFICATIONS MODEL POWER CONSUMPTION high medium low high medium low Current input Required power supply Required fuses Required wire section W W W A A A V / f / Hz A mm FW..01C** FW..02C** FW..02C** FW..03C** FW..04C**…
-
4 Power consumption in function of ESP and speed FWV/FWL/FWM - 2-pipe series FW..01 4-1 Max. Med. Min. ESP Power input Current Power input Current Power input (Pa) (W) (A) (W) (A) (W) Current (A) 0 36 0.161 26 0.112 21 0.091 10 36 0.159 25 0.110 21 0.090 20 35 0.154 25 0.109 20 0.088 30 35 0.150 24…
-
Power consumption in function of ESP and speed FWV/FWL/FWM - 2-pipe series FW..06 Max. Med. Min. ESP Power input Current Power input Current Power input Current (Pa) (W) (A) (W) (A) (W) (A) 0 89 0.386 62 0.283 42 0.190 10 87 0.377 62 0.277 40 0.184 20 85 0.366 59 0.266 40 0.179 30 82 0.354 57 0.255…
-
4 Power consumption in function of ESP and speed FWV/FWL/FWM - 4-pipe series FW..01 4-2 Max. Med. Min. ESP Power input Current Power input Current Power input (Pa) (W) (A) (W) (A) (W) Current (A) 0 36 0.161 26 0.112 21 0.091 10 36 0.159 25 0.110 21 0.090 20 35 0.154 25 0.109 20 0.088 30 35 0.150 24…
-
Power consumption in function of ESP and speed FWV/FWL/FWM - 4-pipe series FW..06 Max. Med. Min. ESP Power input Current Power input Current Power input Current (Pa) (W) (A) (W) (A) (W) (A) 0 89 0.386 62 0.283 42 0.190 10 87 0.377 62 0.277 40 0.184 20 85 0.366 59 0.266 40 0.179 30 82 0.354 57 0.255…
-
4 Power consumption in function of ESP and speed FWD -2-pipe series/4-pipe FWD04 4-3 Max. Med. Min. ESP Power input Current Power input Current Power input (Pa) (W) (A) (W) (A) (W) Current (A) 0 234 0.954 173 0.740 130 0.568 10 228 0.946 169 0.740 122 0.550 20 221 0.940 165 0.731 120 0.530 30 211…
-
Power consumption in function of ESP and speed FWD -2-pipe series/4-pipe FWD08 Max. Med. Min. ESP Power input Current Power input Current Power input Current (Pa) (W) (A) (W) (A) (W) (A) 0 443 1.971 336 1.515 261 1.204 10 420 1.915 317 1.475 247 1.186 20 404 1.850 301 1.418 238 1.144 30 382 1.808…
-
4 4-3 Power consumption in function of ESP and speed FWD -2-pipe series/4-pipe FWD12 ESP (Pa) Max. Power input (W) Med. Current (A) 3.210 3.100 3.070 3.020 2.990 2.950 2.895 2.800 2.730 2.650 2.600 2.540 2.450 2.390 2.300 2.225 2.210 Power input (W) Min. Current (A) 2.080 2.070 2.060 2.040 1.970…
-
Power consumption in function of ESP and speed FWD -2-pipe series/4-pipe FWD18 Max. Med. Min. ESP Power input Current Power input Current Power input Current (Pa) (W) (A) (W) (A) (W) (A) 0 1197 5.370 966 4.380 704 3.260 10 1159 5.300 921 4.200 680 3.250 20 1130 5.250 897 4.090 672 3.240 30 1112…
-
4 4-4 Power consumption in function of ESP and speed FWB FWB02-04 Speed AP 7 (Max.) Power input 6 Current Power input 5 Current Power input 4 Current Power input 3 Current Power input 2 Current Power input 1 (Min.) Current Power input Current (Pa) (W) (A) (W) (A) (W) (A) (W) (A) (W) (A) (W) (A) (W)…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 2-pipe FW..04 TN/TV FW..06 TN/TV FW..08 TN/TV FW..10 TN/TV Total cooling capacity W 1090 880 780 1480 1260 1090 2140 1720 1520 2390 1980 1700 3290 2720 2380 4380 3310 2530 Water pressure drop kPa Total cooling capacity W 1370 1180 920 1970 1620 1290…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 2-pipe FW..06 TN/TV FW..08 TN/TV FW..10 TN/TV Total cooling capacity W 1260 1010 850 1750 1520 1210 2440 1970 1460 3590 2670 2060 3970 3200 2580 5590 4320 3230 7320 5650 3600 Water pressure drop kPa Total cooling capacity W 1020 810 680 1450 1260 1000…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 2-pipe FW..04 TN/TV FW..06 TN/TV FW..08 TN/TV FW..10 TN/TV Total cooling capacity W 1540 1240 1040 2090 1810 1450 2930 2380 1760 4330 3270 2510 4770 3870 3170 6710 5270 3970 8710 6780 4490 Water pressure drop kPa Total cooling capacity W 1310 1060 890…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 2-pipe FW..06 TN/TV FW..08 TN/TV FW..10 TN/TV Total cooling capacity W 2440 1960 1640 3190 2740 2200 4450 3620 2700 6630 5030 3910 7280 5920 4870 10160 8040 6190 13090 10260 6910 Water pressure drop kPa Total cooling capacity W 2240 1800 1510 2940…
-
Capacity tables
Heating capacities FWV/FWL/FWM - 2-pipe FW..04 TN/TV FW..06 TN/TV FW..08 TN/TV FW..10 TN/TV Heating capacity W 2840 2310 1900 3690 3070 2530 5030 4070 3020 7420 5690 4360 8410 6900 5630 11240 8960 6890 14590 11370 7670 Water pressure drop kPa Heating capacity W 3710 2990 2470 4760 3950 3250 6460…
-
Capacity tables Heating capacities FWV/FWL/FWM - 2-pipe FW..06 TN/TV FW..08 TN/TV FW..10 TN/TV Heating capacity W 2670 2160 1780 3460 2880 2370 4730 3820 2840 6970 5340 4090 7900 6490 5280 10560 8410 6470 13700 10690 7200 Water pressure drop kPa Heating capacity W 3530 2850 2350 4530 3760 3090 6150…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 4-pipe FW..04 FN/FV FW..06 FN/FV FW..08 FN/FV FW..10 TN/TV Total cooling capacity W 1460 1250 1080 2110 1710 1510 2330 1960 1690 3270 2710 2370 4290 3280 2520 Water pressure drop kPa Total cooling capacity W 1350 1160 910 1950 1610 1280 2070 1810 1570…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 4-pipe FW..06 FN/FV FW..08 FN/FV FW..10 TN/TV Total cooling capacity W 1230 990 830 1490 1290 1040 2390 1930 1450 3530 2630 2050 3890 3150 2530 5530 4290 3210 7180 5580 3560 Water pressure drop kPa Total cooling capacity W 1230 1060 870 1970 1550 1290…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 4-pipe FW..04 FN/FV FW..06 FN/FV FW..08 FN/FV FW..10 TN/TV Total cooling capacity W 1500 1210 1020 1790 1560 1260 2870 2330 1730 4260 3230 2480 4670 3810 3110 6640 5230 3930 8550 6690 4450 Water pressure drop kPa Total cooling capacity W 1280 1030 870…
-
Capacity tables Cooling capacities FWV/FWL/FWM - 4-pipe FW..06 FN/FV FW..08 FN/FV FW..10 TN/TV Total cooling capacity W 2380 1920 1610 2780 2400 1950 4360 3540 2660 6510 4970 3860 7130 5830 4790 10050 7990 6140 12870 10130 6850 Water pressure drop kPa Total cooling capacity W 2180 1760 1480 2550…
-
Capacity tables
Heating capacities FWV/FWL/FWM - 4-pipe 20 Water pressure drop kPa Heating capacity W 2230 1890 1620 2070 1840 1610 2910 2530 2060 4510 3750 3110 4670 4100 3560 7910 6830 5690 9300 7950 6120 70 - 60 Water flow !/h Water pressure drop kPa Heating capacity W 2890 2470 2120 2690 2390 2100 4200 3630…
-
Capacity tables Heating capacities FWV/FWL/FWM - 4-pipe FW..06 FN/FV FW..08 FN/FV FW..10 TN/TV Heating capacity W 1560 1320 1130 1440 1280 1110 2200 1910 1540 3160 2620 2160 3710 3260 2840 5640 4890 4080 6610 5670 4380 Water pressure drop kPa Heating capacity W 2120 1800 1540 1970 1750 1530 3090…
-
Capacity tables Cooling capacities FWD - 2-pipe/4-pipe 22 - 16 Water pressure drop kPa Total cooling capacity W 1150 1440 1790 2000 2360 2830 2750 3150 3520 3280 3560 3840 4130 4810 5420 5350 6470 7480 6060 7280 8400 8 - 13 Sensible cooling capacity Water flow W !/h 1150 197 1440 247 1790 307 2000…
-
Capacity tables Cooling capacities FWD - 2-pipe/4-pipe 5 5-3 36 25 - 18 Water pressure drop kPa Total cooling capacity W 1460 2110 2660 2960 3580 4310 3870 4370 4830 4260 4870 5450 6380 7370 8280 8640 10330 11870 9990 11900 13670 8 - 13 Sensible cooling capacity Water flow W !/h 1350 252 1930 364…
-
Capacity tables Cooling capacities FWD - 2-pipe/4-pipe 27 - 19 Water pressure drop kPa Total cooling capacity W 1950 2720 3390 3830 4570 5380 5460 6150 6800 5990 6840 7640 8130 9310 10410 10660 12670 14520 11990 14270 16370 8 - 13 Sensible cooling capacity Water flow W !/h 1620 335 2290 468 2890 583…
-
Capacity tables Heating capacities FWD - 2-pipe 5 5-4 38 20 Water pressure drop kPa Heating capacity W 4970 6700 8200 9490 11170 13080 13030 14520 15920 14730 16530 18230 19380 21970 24400 24740 29220 33350 26890 32040 36810 70 - 60 Water flow !/h 1147 1145 1274 1397 1292 1451 1598 1699 1930 2142…
-
Capacity tables Heating capacities FWD - 2-pipe 22 Water pressure drop kPa Heating capacity W 4730 6380 7810 9040 10630 12450 12410 13830 15150 14030 15740 17350 18440 20920 23220 23560 27820 31750 25610 30520 35060 70 - 60 Water flow !/h 1092 1089 1213 1330 1230 1381 1523 1619 1835 2038 2067 2442…
-
Capacity tables Heating capacities FWD - 4-pipe 5 5-5 40 20 Water pressure drop kPa Heating capacity W 3190 3920 4490 5370 5970 6620 8030 8650 9210 8030 8650 9210 13020 14500 15860 16450 18920 21150 16450 18920 21150 70 - 60 Water flow !/h 1141 1271 1393 1444 1660 1854 1444 1660 1854 Water pressure…
-
Capacity tables Heating capacities FWD - 4-pipe 22 Water pressure drop kPa Heating capacity W 3030 3730 4270 5110 5680 6290 7630 8220 8750 7630 8220 8750 12380 13790 15090 15650 18000 20130 15650 18000 20130 70 - 60 Water flow !/h 1087 1210 1325 1372 1580 1764 1372 1580 1764 Water pressure drop kPa…
-
Capacity tables Cooling capacities FWB - 2-pipe 5 5-6 42 25 - 18 Water pressure drop kPa Total cooling capacity W 1410 1710 2150 1760 2320 2830 2000 2640 3270 2700 3560 4300 2910 3360 4450 3620 4830 5920 4600 5390 6130 5380 6340 7240 6710 7960 9160 8 - 13 Sensible cooling capacity Water flow W !/h…
-
Capacity tables Cooling capacities FWB - 2-pipe 27 - 19 Water pressure drop kPa Total cooling capacity W 1710 2250 2740 2150 2790 3400 2370 3130 3860 3480 4460 5340 3420 4690 5780 4430 5800 7080 5740 6670 7540 6580 7710 8770 7900 9350 10750 8 - 13 Sensible cooling capacity Water flow W !/h 1340 293…
-
Capacity tables Heating capacities FWB - 2-pipe 5 5-7 44 20 - 22 Water pressure drop kPa Heating capacity W 4420 5600 6690 4770 6150 7450 5040 6620 8150 8400 10550 12520 9140 11660 14000 9710 12570 15280 13380 15400 17310 14820 17250 19570 16280 19220 22070 70 - 60 Water flow !/h 1098 802 1023 1229…
-
Capacity tables Heating capacities FWB - 2-pipe 20 - 22 Water pressure drop kPa Heating capacity W 4320 5470 6530 4660 6010 7280 4930 6470 7960 8200 10310 12220 8920 11390 13680 9480 12280 14920 13060 15050 16900 14480 16850 19110 15900 18780 21550 70 - 60 Water flow !/h 1072 783 999 1199 832 1077…
-
Capacity tables Heating capacities FWB - Additional heat exchanger 5 5-8 46 19 Water pressure drop kPa Heating capacity W 2750 3220 3610 5270 6140 6870 11520 13120 14600 70 - 60 Water flow !/h 1011 1150 1281 Water pressure drop kPa Heating capacity W 3550 4160 4670 6870 7980 8900 15250 17330 19260…
-
Capacity tables Heating capacities FWB - Additional heat exchanger 20 Water pressure drop kPa Heating capacity W 2680 3140 3520 5140 5990 6700 11250 12800 14260 70 - 60 Water flow !/h 1123 1250 Water pressure drop kPa Heating capacity W 3480 4080 4580 6740 7830 8740 11250 12800 14260 90 - 70 Water…
-
Correction factors 6-1-1 FWV-FWL-FWM Correction factors for cooling & heating capacities FW..08 FW..10 Total cooling capacity Sensible cooling capacity Heating capacity - 2 pipe Heating capacity - 4 pipe TCC SCC HC2P HC40 FW..01 medium low 0.81 0.68 0.81 0.66 0.81 0.66 0.85 0.73 FW..02 medium low…
-
Correction factors 6-1-2 FWD FWD12 FWD16 FWD18 F1 1.13 1.28 1.37 1.18 1.28 1.38 1.21 1.11 1.08 1.18 1.1 1.07 1.29 1.1 0.96 1.12 1.09 1.06 1.11 1.07 1.05 40 F2 1.09 1.2 1.29 1.13 1.2 1.28 1.15 1.08 1.06 1.14 1.08 1.06 1.21 1.08 0.97 1.09 1.07 1.05 1.08 1.06 1.04 F1 1.08 1.21 1.29 1.09 1.19 1.28 1.13…
-
Correction factors 6-1-3 FWB Correction factors for cooling & heating capacities FWB07 FWB08 FWB09 FWB10 F1 0.51 0.73 0.83 0.51 0.73 0.83 0.51 0.73 0.83 0.64 0.86 0.87 0.64 0.86 0.87 0.64 0.86 0.87 0.71 0.77 0.84 0.71 0.77 0.84 0.71 0.77 0.84 40 F2 0.62 0.76 0.86 0.56 0.75 0.86 0.55 0.74 0.85 0.69…
-
Correction factors Glycol correction factors Glycol percentage in weight Freezing temperature (°C) Capacity correction factor Pressure drop correction factor 1.00 10 -4 0.93 1.09 20 -10 0.84 1.18 30 -16 0.76 1.27 40 -24 0.76 1.36 Glycol percentage in weight Freezing temperature (°C) Capacity…
-
Correction factors 6-3-1 FWV/FWL/FWM Capacity and absorption of electric heater FWV / FWL / FWM 6-3 Power input electric heater Current Absorption Unit Electric heater kW A FW..01 EEH01A6 1.0 4.34 FW..02 EEH02A6 1.5 6.52 FW..03 EEH03A6 1.6 6.95 FW..04 EEH06A6 2.0 8.69 FW..06 EEH06A6 2.0 8.69 FW..08…
-
Water pressure drop 7-1-1 2-pipe series - cooling FWV/FWL/FWM Water flow l/h 1000 1500 2000 2500 3000 4000 5000 FW..01 kPa FW..02 kPa 0.71 2.44 8.25 16.84 27.92 41.33 56.93 94.32 139.51 - 0.41 1.42 4.81 9.81 16.27 24.09 33.19 55.02 81.4 165.77 - FWV / FWL / FWM Water pressure drop FW..03 FW..04…
-
7 7-2 Water pressure drop 7-2-1 2-pipe series - cooling FWD Water flow l/h 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 3000 4000 5000 7-2-2 FWD06 kPa 0.59 2.02 4.12 6.83 10.12 13.94 18.28 23.12 28.45 34.23 40.48 47.17 54.29 61.84 69.81 78.19 86.97 96.15 105.73…
-
Water pressure drop 7-2-3 4-pipe series - heating FWD Water flow l/h 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2500 3000 3500 4000 4500 5000 FWD04 kPa 0.83 2.75 5.55 9.14 13.48 18.51 24.21 30.56 37.52 45.09 53.25 61.98 71.27 81.11 91.5 102.41 - FWD06 kPa 0.71 2.36 4.76 7.84 11.54 15.83…
-
7 7-3 Water pressure drop 7-3-1 2-pipe series - cooling Water flow l/h 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 3000 3500 4000 FWB FWB02 kPa FWB03 kPa FWB04 kPa <1 FWB Water pressure drop FWB05 FWB06 FWB07 kPa kPa kPa <1 <1 <1 <1 FWB08 kPa <1 FWB09 kPa <1 FWB10…
-
Water pressure drop 7-3-2 2-pipe series - heating Water flow l/h 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 3000 3500 4000 4500 5000 FWB FWB02 kPa <1 FWB03 kPa FWB04 kPa <1 FWB Water pressure drop FWB05 FWB06 FWB07 kPa kPa kPa <1 <1 <1 <1 7-3 FWB08 kPa <1 FWB09…
-
7 7-3 Water pressure drop 7-3-3 Additional heat exchanger Water flow l/h 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 3000 3500 4000 4500 5000 FWB FWB Water pressure drop EAH04A6 EAH07A6 EAH10A6 kPa kPa kPa <1 <1 <1 4TW60299-1 (Sheet 3/3) 58 • Hydronic Systems •…
-
8-1 Operation range FWV/FWL/FWM Minimum water temperature Maximum water temperature Maximum operating pressure Minimum air inlet temperature Maximum air inlet temperature Power supply +5°C +95°C 10 bar 5°C +43°C 230V +-10% / 1∼ / 50Hz 8 8-1 4TW60013-1 8-2 FWD Minimum water temperature Maximum water…
-
9 9-3 Dimensional drawings FWD FWD04∼10 FWD04 FWD06 FWD08+10 A 754 964 1174 B 707 917 1127 C 676 886 1096 D 646 856 1066 4TW60224-1 (Sheet 1/2) FWD12∼18 FWD12 FWD16+18 A 1174 1384 B 1127 1337 C 1096 1306 D 1066 1276 4TW60224-1 (Sheet 2/2) 62 • Hydronic Systems • Fan Coil Units
-
Dimensional drawings FWB 9 FWB 9-4 N° 2 x 3/4″ Female connections 4TW60294-1 • Hydronic Systems • Fan Coil Units 63
-
Wiring diagrams
10-1 FWV/FWL/FWM 10 10-1 SYMBOLS BK Black = maximum speed BU Blue = medium speed GNYE Yellow/Green = earth connection RD Red = minimum speed WH White = common Field wiring F Protection fuse (field supply) IL Main switch (field supply) M Fan motor PE Earth connection 4TW60016-1 64 • Hydronic Systems…
-
Wiring diagrams
10-2 FWD 10 10-2 SYMBOLS BK Black = maximum speed BU Blue = medium speed GNYE Yellow/Green = earth connection RD Red = minimum speed WH White = common Field wiring F Protection fuse (field supply) IL Main switch (field supply) M Fan motor PE Earth connection 4TW60226-1 • Hydronic Systems • Fan Coil…
-
Wiring diagrams
10-3 FWB 10 10-3 SYMBOLS BK Black = maximum speed BU Blue = medium speed GNYE Yellow/Green = earth connection RD Red = minimum speed WH White = common Field wiring F Protection fuse (field supply) IL Main switch (field supply) M Fan motor PE Earth connection 4TW60296-1 66 • Hydronic Systems • Fan…
-
Sound power data
-
таблицы и схемы — в просмотре
-
Sound power data
-
таблицы и схемы — в просмотре
-
Sound power data
-
таблицы и схемы — в просмотре
-
Sound power data
11-3 FWB 11-3-1 2-pipe series 11 FWB02-04 1000 2000 4000 8000 Global dB dB dB dB dB dB dB dB/A Global Inlet - Speed 7 Outlet - Structure - Global Inlet - - Structure - Global - - Structure - Global Inlet - - Structure - Global Inlet - 6 Outlet Inlet 5 Outlet 4 Outlet 3 Outlet - Structure - Global…
-
Sound power data
11-3 FWB 11 11-3-1 2-pipe series 11-3 FWB05-07 1000 2000 4000 8000 Global dB dB dB dB dB dB dB dB/A Global Inlet - Speed 7 Outlet - Structure - Global Inlet - - Structure - Global - - Structure - Global Inlet - - Structure - Global Inlet - 6 Outlet Inlet 5 Outlet 4 Outlet 3 Outlet - Structure nm…
-
Sound power data
11-3 FWB 11-3-1 2-pipe series 11 FWB08-10 1000 2000 4000 8000 Global dB dB dB dB dB dB dB dB/A Global Inlet - Speed 7 Outlet - Structure - Global Inlet - - Structure - Global - - Structure - Global Inlet - - Structure - Global Inlet - 6 Outlet Inlet 5 Outlet 4 Outlet 3 Outlet - Structure - Global…
-
Installation
12-1 Controller 12 Cool/heat changeover Options Basic control functions 7 12-1 ✔ ✔ ✔ 2-pipe ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 4-pipe ✔ ✔ ✔ Control features ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ Manual cool/heat changeover. Automatic cool/heat changeover…
-
Installation
12-2 Installation precautions 12-2-1 FWV/FWL/FWM 12 Fan coil units should be installed in a position where they heat and cool the room evenly, on walls or ceilings that can bear their weight. Fit any accessories on the standard unit before installing it. Read the relevant technical sheets for the…
-
Installation
12-2 Installation precautions 12 12-2-1 FWV/FWL/FWM 12-2 ELECTRICAL CONNECTIONS Carry out the electrical wiring after having turned the power off in compliance with the relevant local and national regulations following the relevant wiring diagram. Check that the power supply corresponds to the rated…
-
Installation
12-2 Installation precautions 12-2-2 FWD 12 12-2 BEFORE THE INSTALLATION The equipment is to be installed and serviced exclusively by technical personnel who are qualified for using this type of machine, in compliance with the relevant local and national regulations. On receiving the equipment…
-
Installation
12-2 Installation precautions 12 12-2-2 FWD 12-2 A few rules to follow Carry out the heat exchanger’s air exhaust, with pumps stopped, by means of the air valves located adjacent to the attachments of the heat exchanger itself. When implementing a duct system, it is advisable to place the…
-
Installation
12-2 Installation precautions 12-2-3 FWB 12 12-2 BEFORE THE INSTALLATION The equipment is to be installed and serviced exclusively by technical personnel who are qualified for using this type of machine, in compliance with the relevant local and national regulations. On receiving the equipment…
-
Installation
12-2 Installation precautions 12 12-2-3 FWB 12-2 A few rules to follow Carry out the heat exchanger’s air exhaust, with pumps stopped, by means of the air valves located adjacent to the attachments of the heat exchanger itself. When implementing a duct system, it is advisable to place the…
-
Installation
12-3 Installation & service distance 12-3-1 FWD 12 1. Ducted unit with filter only 12-3 Consider at least: - 500 mm free space on water connections side (piping & connections) - 200 mm free space on the opposite side (to unscrew heat exchangers or fan deck in case of repairing) - Possibility to…
-
Installation
12-3 Installation & service distance 12 12-3-1 FWD 12-3 3. Ducted unit with filter and valves Consider also: - 500 mm free space on water connections side (piping & connections), measured from the valve piping (refer to option technical leaflet for details - total around 720 mm) - 200 mm free space…
-
Options
13-1 FWV / FWL / FWM Option list Reference Additional single-row heat exchanger ESRH..A6 Electric heater EEH..A6 2-pipe ON-OFF 3 way motor driven valve complete with mounting kit pre-assembled E2MV..A6 4-pipe ON-OFF 3 way motor driven valve complete with mounting kit pre-assembled E4MV..A6 Fan stop…
-
таблицы и схемы — в просмотре
-
Options
13-2 FWD Option list Kit EDEHS18A6 - X EDEHB12A6 EDEHB18A6 - X ED2MV10A6 ED2MV12A6 ED2MV18A6 - X ED4MV10A6 2 x ED2MV12A6 2 x ED2MV18A6 - X - X - X - X - X Neglecting the absolute requirement to install an additional interface (EPIA6 or EPIMSA6) to FWD06→18 may cause fire or other damage to the…
-
таблицы и схемы — в просмотре
-
Options
13-3 FWB Option list Description 02 Additional heat exchanger EAH04A6 EAH07A6 09 E2MV307A6 E2MV310A6 2-way valve add. h/e E2MV207A6 E2MC210A6 YFSTA6 - - - No insulation needed Same as other model EPIA6 In combination with ECFWER6, EPIMSA6 or EPIA6 must be installed for FWBOS-10 Master slave…
-
таблицы и схемы — в просмотре
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.