Инструкция на Фанкойлы Daikin
Настенные блоки фанкойлов Daikin серии FWT. Технические данные.
Смотрите также: Технические данные →
Загружаем документ…
Текст инструкции
-
EEDEN07-432
technical data Fan Coil Units FWT - wall mounted unit
-
FWT - wall mounted unit
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. The present publication is drawn up by way of…
-
EEDEN07-432
technical data Fan coil units FWT - wall mounted unit
-
1 Cooling only Heating only Heat pump 2 • Fan coil units • Wall mounted unit • FWT
-
TABLE OF CONTENTS
FWT 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Nominal capacity and nominal…
-
sn yu S l c i i o n c o r nd T ayW •FH Features Wide operating range • High power air flow Quiet operation with auto-swing comfort • Insulated with self-extinguishing class 1 heat insulation • Easy to install and maintain • Removable washable air filter (self-extinguishing class 1) 1 • 3 speed fan…
-
2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Power Input Cooling capacity High W FWT05AT FWT06AT W kW 2.34 2.78 3.22 4.54 5.28 1 2 Total capacity High Medium kW 2.23 2.68 2.74 4.10 4.95 Low kW 2.10 2.20 2.20 3.95 4.25 High kW 1.74 2.03 2.35 3.65 4.33 Medium kW 1.51 1.82 2.00 3.21 3.95 Low…
-
2-2 Specifications TECHNICAL SPECIFICATIONS FWT02AT FWT03AT Notes FWT04AT FWT05AT FWT06AT Rating conditions cooling 2 pipe: air 27 Rating conditions heating 2 pipe : air 20 Sound power level according to ISO3741 1 Sound pressure measured at 1 m in front of the unit and 0.8 m below the vertical…
-
Control systems 3 Control systems for FWC-FWF-FWT Operation mode Controller WRC SRC MERCA Application Manual 2-pipe x 4-pipe x 2-pipe x 4-pipe x 2-pipe x 4-pipe x Automatic x x x Basic Controls Energy saving mode Timer setting Temperature Automatic Fan speed: setting Fan Speed high/medium/low Air…
-
Capacity tables
4-1 Cooling capacity tables Cooling capacities FWT (2 pipe) 1 4 Air temperature (°C DB - °C WB) Water temperature (Entering °C - Leaving °C) Model FWT02AT FWT03AT FWT04AT FWT05AT FWT06AT Air Flow m3/hr 1070 833 748 1121 985 799 22-16 6-11 Total Sensible cooling cooling capacity capacity kW kW 1.77…
-
Capacity tables
4-2 Capacity tables with glycol for process cooling applications 3 Glycol correction factor FWT Cooling capacity Entering water temperature °C 0% 10% 20% 30% 40% 0 1 0.955 0.929 0.898 0.863 20 1 0.969 0.941 0.913 0.882 • Fan coil units • Wall mounted unit • FWT 40 1 0.973 0.955 0.929 0.899 60 1…
-
Capacity tables
4-3 Heating capacity tables Heating capacities FWT (2 pipe) 1 4 Air temperature (°C DB - °C WB) Water temperature (Entering °C - Leaving °C) Model FWT02AT FWT03AT FWT04AT FWT05AT FWT06AT Air Flow m3/HR 1070 833 748 1121 985 799 Heating capacity kW 3.20 2.85 2.48 3.98 3.46 2.78 4.31 3.59 3.00 6.50…
-
Capacity tables
4-4 Capacity correction factor 3 Heating correction factor FWT Entering Air temperature °C 4.4 7.2 10.0 12.7 15.5 18.3 20.0 21.1 23.9 26.7 37.8 1.338 1.257 1.176 1.093 1.010 0.958 0.877 0.824 0.758 0.677 43.3 1.376 1.297 1.221 1.140 1.061 0.999 0.933 0.890 0.819 0.741 45.0 1.388 1.310 1.235 1.155…
-
Piping diagram FWT (Water piping diagram) 1 6 Gate Valve Chiller Gate Valve Three Way Valve FCU Gate Valve Two Way Valve Gate Valve FCU Gate Valve FCU Gate Valve Good Controlling 14 • Fan coil units • Wall mounted unit • FWT Bad Controlling Worst Controlling
-
Wiring diagram 7-1 Wiring diagram 3 1 FWT02~06AATNMV1 FCU 3 VALVE N 2 FCU 2 N1 L VALVE N 2 3W V 7 FCU 1 N1 L VALVE N 2 3WV N1 L 3W V x1 N T S R x2 x3 3WV Chiller 3 way valve x1, x2, x3 Relay (220-240V, 10A) FWT02AATNMV1 / FWT03AATNMV1 / FWT04AATNMV1 ORANGE (LO) BROWN (MED) FM BLACK (HI) BLUE BLUE…
-
Wiring diagram 7-1 Wiring diagram FWT05AATNMV1 / FWT06AATNMV1 ORANGE (LO) 1 BROWN (MED) FM BLACK (HI) AS 7 BLUE RED FAN MOTOR CAPACITOR WIRED CONTROLLER SWITCH BOARD INDOOR COIL THERMISTOR ROOM THERMISTOR SLEEP COOL/HEAT TIMER ION DISPLAY BOARD IR BOARD YELLOW/GREEN CAUTION ! FIELD INSTALLATION FM…
-
Sound data 8-1 Sound power spectrum 3 1 FWT (2 PIPE) Model FWT02AT Freq Hi Me Lo FWT03AT Hi Me Lo FWT04AT Hi Me Lo FWT05AT Hi Me Lo FWT06AT Hi Me Lo Microphone position: 1/1 Octave Sound Power Level (dB, reference 1pW) 1000 2000 4000 8000 FWT Overall (dBA) 1m in front and 0.8m below the vertical…
-
Operation range FWT 1 9 OPERATING RANGE Operating Limits: Thermal carrier : Water Water temperature : 5 ~50°C Maximum water pressure : 16 bar Air temperature : (as below) Cooling Mode Temperature Minimum indoor temperature Maximum indoor temperature Minimum outdoor temperature Maximum outdoor…
-
Hydraulic performance 10 - 1 Water pressure drop curve evaporator 3 FWT FWT (2 PIPE) cooling Water flow m3/hr FWT02AT 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.98 10.98 24.95 43.82 67.51 95.94 129.02 FWT03AT Water pressure drop (kPa) FWT02AT 7.14 19.72 34.27 50.71 68.94 88.87…