OPERATION MANUAL
Packaged air-cooled water chillers EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN
-
General EWAQ
240 Dimensions HxWxD Weight (mm) • machine weight (kg) • operation weight (kg) 260 2311x2000x4833 3150 3189 3250 3292 3" 1/2"G 39 3" 1/2"G 42 50 1.5 50 1.5 3.0 3.0 Connections • chilled water inlet and outlet • evaporator drain Internal water volume (l) Expansion vessel (only for OPSP, OPTP and…
-
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Refrigerant type: GWP(1) value: R410A 1975 (1) GWP = global warming potential Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer…
-
Function of the main components
t> M15F M25F 15 C D M13F D 8 M14F Y21E C M23F 8 11 Y11E 12 M24F 11 12 D D 5 D 5 16 B1PH p > 12 p > B2PH 16 p > S2PH S1PH p > R14T D R17T R34T R37T 12 12 (*) (*) 12 12 B1PL 17 p < B2PL M11C M12C M22C M21C R15T R25T R35T p< 17 R45T 2 PHE A D R3T R2T t> t> 7 22 B D D Figure - Functional diagram 1 Water…
-
Evaporator The main function of the evaporator is to take heat from the water that flows through it. This is done by turning the liquid refrigerant, coming from the condenser, into gaseous refrigerant. ■ Water in/outlet connection The water inlet and outlet connection allow an easy connection of the…
-
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The abbreviations used are listed below: A01P PCB extension A02P ** PCB communication (only for option EKACPG) A4P PCB wired remote controller A5P ** PCB wired remote controller (only for option EKRUPG) A11P,A21P PCB main controller…
-
T1V............... ** ......Voltage transducer (only for option OP57)
TR1 Transfo control circuit (400 V/230 V) TR1A Current measurement transfo (only for option OP57) V1C Ferrite core V1F,V2F Noise filter circuit 1, circuit 2 (only for EWAQ130~210 with option OPIF) V2C Ferrite core (only for option EKACPG) X*A PCB terminal X*Y Connector X1M PCB terminal strip Y11E…
-
OPERATION
Connection of a remote digital controller to the unit The EWAQ units are equipped with a digital controller (located behind the service panel) offering a user-friendly way to set up, use and maintain the unit. This part of the manual has a task-oriented, modular structure. Apart from the first…
-
Switching the unit off
2 Press the Ì key to enter the next screen of the readout menu. • If a remote on/off switch is configured: Press the œ key on the controller or switch the unit off using the remote on/off switch. The LED inside the œ key goes out in the first case and starts blinking in the second case. • • • NOTE…
-
STARTUP: the circuit is ready to start up when extra
cooling load is needed. When none of the above mentioned messages appears, no special functions are active and the compressor is running. 4 The preceding messages are written down in order of priority. The UNIT CAPACITY is written down on the bottom of the first screen. 5 • CAN • 7 Press ‡ to save…
-
Advanced features of the digital controller
This chapter gives an overview and a brief functional description of the screens provided by the different menus. In the following chapter, you will find how you can set up and configure the unit using the various menu functions. All menus are directly accessible using the corresponding key on the…
-
PUMP
Timers menu Ó _v PUMPCONTROL PUMPLEADTIME :020s PUMPLAGTIME :060s DAILY ON:N AT:12h00 To define the pump control settings. _^ DUAL PUMP MODE:AUTO ROTATION OFFSET ON RH :048h To define the dual pump settings. FLOATING SETPOINT _ FLOATING SETPOINT MODE:AMBIENT MAXPOS:03$0¢ NEG:00$0¢ RF:020$0¢…
-
_÷ UNIT HISTORY:002
HP2:019$0b = 050$0¢ LP2:019$0b = -05$2¢ FAN2:OFF To check which were the pressures of of circuit 2 and the status of the fans at the moment of shutdown (only for EWAQ130~260). _÷ UNIT HISTORY:002 C11:OFF SAFETY ACT. C12:OFF SAFETY ACT. UNITCAPACITY:000% To check which was the status of the…
-
_÷CHANG. DIG. INPUTS
DI4 NONE DO1 SAFETY+W.(NO) :O DO2 GEN.OPERATION :O To check the status of the changeable digital inputs and outputs (second screen). _÷CHANG. INP/OUTPUTS DO3 NONE (OPEN) DO4 NONE (OPEN) DO5 NONE (OPEN) To check the status of the changeable digital outputs (third screen). _÷CHANG. INP/OUTPUTS DO6…
-
Submenu: Pump
NOTE To activate manual control mode, select MANUAL CONTROL as present mode. To deactivate the manual control mode, select an other mode as present mode. Defining the pump control settings For units in a DICN configuration: The PUMPCONTROL screen of the usersettings menu allows the user to define…
-
Submenu: Language
• Defining the language unit however, will only come into operation if: another unit is in alarm another unit is in DISCONNECT ON/OFF mode the setpoint is not reached when all other units have been running on full capacity for some time If more than one unit is defined as STANDBY, only 1 of the…
-
Defining controller settings
To check the actual value of the software timers, proceed as follows: 1 Enter the TIMERS MENU. (Refer to the chapter "How to enter a menu" on page 8.) The controller displays the actual value of the GENERAL TIMERS: the loadup timer, the loaddown timer, the flowstart timer, the flowstop timer (when…
-
Tasks of the info menu
Consulting additional unit information 1 2 Enter the INFO MENU through the main menu. (Refer to the chapter "How to enter a menu" on page 8). The controller enters the TIME INFO screen which contains the following information: the TIME and DATE. Press Ì to consult the first UNIT INFO screen. This…
-
Tasks of the login/logout menu
TROUBLESHOOTING Changing the user password This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit. Access to the usersettings menu and the setpoints menu is protected by the user password (a 4-digit number between 0000 and 9999). After the…
-
Message safety menu
UNIT WARNING NETWORK SAFETY Symptom 0AE:FLOW HAS STOPPED 0C9:INL SENSOR ERR 1E3:HP SETBACK 153:FAN OVERC. ST1 153:FAN OVERC. ST2 153:FAN OVERC. ST3 2E3:HP SETBACK 253:FAN OVERC. ST1 253:FAN OVERC. ST2 253:FAN OVERC. ST3 0C9:INL SENSOR ERR 0U4:PCB COMM.PROBLEM 0U4:SW VERSION ERR 5.2 7 5.7 5.4 5.4 5.4…
-
5.9b Symptom 5.6: Superheat temperature is not correct (1A9/2A9:SUPERHEAT ERR) POSSIBLE CAUSES Symptom 5.9b: Compressor safety (only for SJ161-4) (1E6/2E6:COMPR 1/2 SAFETY) CORRECTIVE ACTION Superheat temperature is too high. Superheat temperature is too low. The sensed suction temperature is more…
-
Symptom 6: Unit stops soon after operation
Symptom 13: The NETWORK SAFETY alarm message shows 0U4:SW VERSION ERR 6 POSSIBLE CAUSES CORRECTIVE ACTION One of the safety devices is activated. Check safety devices (refer to Symptom 5: Safety devices are activated and alarm messages are displayed). Voltage is too low. Test the voltage in the…
-
Water supply • • ■ NOTES Check if the water connection is still well fixed. Check the water quality (refer to the installation manual of the unit for specifications of the water quality). Water filters • • Make sure to clean the water filter in front of the evaporator water inlet once every 4…
-
NOTES
EWAQ080~260DAYN Packaged air-cooled water chillers 4PW35556-1C Operation manual 24
-
ANNEX I
Thermostat parameters Water temperature control The figures below show the thermostat diagram in case of inlet water temperature control. ■ Stand alone thermostat(1) (inlet or outlet) ■ DICN thermostat(1) (inlet) Load up request of 4 compressors Load up request of 1 compressor Load up request of 3…
-
ANNEX IV
>READOUT MENU SETPOINTS MENU USERSETTINGS MENU TIMERS MENU HISTORY MENU INFO MENU I/O STATUS MENU LOGIN/LOGOUT MENU NETWORK MENU COOL/HEAT MENU ----STARTUP BUSY---- ªÒµ® †Úæ∂Ï _v¶ … ≤0U4 ∞11 ∞12 ≠H ∞21 ∞22 ≠H 013£6¢ 012$0¢ ENTER PASSWORD PASSWORD: 0000 TO LOGIN ENTER PASSWORD PASSWORD: 0000 TO…
-
_÷ C1 ACT. PRESSURES
HP1:019$0b = 050$8¢ LP1:004$4b = -05$2¢ FAN1:OFF TIME AND DATE FREE COOLING DICN ADVANCED _÷ C2 ACT. PRESSURES HP2:019$0b = 050$8¢ LP2:004$4b = -05$2¢ FAN2:OFF _÷ UNIT STATUS C11:OFF SAFETY ACT. C12:OFF SAFETY ACT. UNIT CAPACITY:000% _ TIME AND DATE TIME: 22h35 DATE FORMAT:DD/MM/YY DATE: WED…
-
4PW35556-1C
Copyright © Daikin