OPERATION MANUAL
Packaged air-cooled water chillers EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN
-
Important information regarding the refrigerant used
(1) GWP = global warming potential This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information. Refrigerant type: R407C…
-
Function of the main components
EWAP110~160 Y11S S1PH S14PH B1P R3T M1C Y16S R4T 9 Y15S B2P A S3T 13 M11F M12F M13F M14F R5T EWAP200~340 Y11S S1PH S14PH B1P R3T S3T M1C Y16S 3 2 R4T B2P 7 Y15S 13 A M11F M12F M13F B M14F M21F M22F M23F M24F R5T Figure - Functional diagram 1 Evaporator 10 Expansion valve 2 Condenser 11 Sightglass 3…
-
3 Circuit safety devices Circuit safety devices shut down the circuit they protect. For this reason the unit does not need to be manually put on again after a circuit safety occurred. Part safety devices Part safety devices shut down the part they protect. An overview of all safety devices is given…
-
S8L.........................Flowswitch
8 Refrigerant leak Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer. 9 Oil leak Check the compressor on oil leakage. If there is an oil leak, call your local dealer. 10 Stop valves Open the liquid line, discharge and suction (if provided)…
-
General recommendations
z key, to enter the user settings menu. Before switching on the unit, read following recommendations: e key, to enter the timers menu. 1 When the complete installation and all necessary settings have been carried out, close all front panels of the unit. r key, to enter the history menu. t key, to…
-
Setting the language
NOTE If desired, the operating language can be changed to any of the following languages: English, German, French, Spanish or Italian. 1 Enter the usersettings menu. Refer to chapter "How to enter a menu" on page 6 2 Go to the appropriate screen of the usersettings menu using the g and h keys. 3…
-
Press the h key to enter the next screen of the readout menu. To consult actual operational information about the ambient temperature and the total running hours of the compressor. 5 Press the g key to return to the other readout menus. Adjusting the temperature setpoint The unit provides definition…
-
Advanced features of the digital controller
This chapter gives an overview and a brief functional description of the screens provided by the different menus. In the following chapter, you will find how you can set up and configure the unit using the various menu functions. All menus are directly accessible using the corresponding key on the…
-
Safeties menu
Info menu The "safeties" menu provides useful information for trouble shooting purposes. The following screens contain basic information. '( % '( '( %# & '( % To consult time and date information. ') % " #%! To consult additional information about the unit such as the unit type and the refrigerant…
-
Network menu
Defining the thermostat settings The "network" menu provides useful information regarding the network. When automatic control mode is selected, the unit uses a thermostat function to control the cooling capacity. However, the thermostat parameters are not fixed and can be modified via the & screen…
-
Beside these four groups there is also a holiday period group which is set the same way as the other groups. Up to 12 holiday periods can be entered in the screen. During these periods the schedule timer will follow the settings of the holiday period group. NOTE NOTE The screens of the usersettings…
-
NOTE
Put a unit to when servicing the machine. In this case it is possible to switch ON or OFF this unit without switching ON or OFF the other units of the network. It is also possible then to operate the unit in . Tasks of the timers menu Checking the actual value of the software timers As a protective…
-
Tasks of the safeties menu
Tasks of the input/output menu Listing activated safeties and checking the unit status Checking the status of the inputs and outputs If the alarm buzzer is activated and the user presses the p key, the controller automatically enters the safeties menu. The input/output menu provides a means of…
-
Overview of safety messages
The changeable analog inputs are: ■ & & %7: indicates the status of the analog input ■ & &%&%: indicates the status of the analog input ■ & & %7: indicates the status of the analog input Message safety menu Enter the . (Refer to the chapter "How to enter a menu" on page 6.) The controller enters the…
-
Symptom 4: The circuit does not start up
5.4 Symptom 5.4: Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION POSSIBLE CAUSES One of the following safety devices is activated: Check on the controller and refer to Symptom 5: One of the following safety devices is activated. Mechanical failure (fan is blocked). Check that…
-
Symptom 7: Unit runs continuously and the water temperature remains
higher than the temperature set on the controller POSSIBLE CAUSES CORRECTIVE ACTION The temperature setting on the controller is too low. Check and adjust the temperature setting. The heat production in the water circuit is too high. The cooling capacity of the unit is too low. Call your local…
-
ANNEX I
ANNEX II Thermostat parameters Schedule timer example Inlet water temperature control/Outlet water temperature control The figure below shows the thermostat diagram. c b c c a/2 b c MON Fast load up Slow load up No action Slow load down Fast load down The default value and the upper and lower limits…
-
ANNEX III
ANNEX IV Floating setpoint working Free cooling working The diagram and table below show the default value and the upper and lower limits of the floating setpoint parameters on the evaporator. Free cooling on ambient temperature Max, value free cooling state ON 5°C OFF °C SP D2 ambient temperature…
-
ANNEX V - SOFTWARE STRUCTURE
-
Zandvoordestraat 300, B-8400 Oostende, Belgium
4PW22677-1B