Инструкция на Чиллеры Daikin EWAQ016–064BAW, EWYQ016–064BAW с воздушным охлаждением
Моноблочные чиллеры с воздушным охлаждением Daikin EWAQ016BAW…EWAQ064BAW и реверсивные EWYQ016BAW…EWYQ064BAW: требования к установке, монтаж, гидравлические и электрические подключения, пуск и эксплуатация. Руководство по монтажу и эксплуатации. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
INSTALLATION AND
OPERATION MANUAL Packaged air-cooled water chiller EWAQ016BAW EWAQ021BAW EWAQ025BAW EWAQ032BAW EWAQ040BAW EWAQ050BAW EWAQ064BAW EWYQ016BAW EWYQ021BAW EWYQ025BAW EWYQ032BAW EWYQ040BAW EWYQ050BAW EWYQ064BAW
-
15 350 kPa 1 EWA/YQ016~025BAWP 2 EWA/YQ032BAWP 3 EWA/YQ040+050BAWP 4 EWA/YQ064BAWP EWA/YQ016~025BAWH 2 EWA/YQ032BAWH 3 EWA/YQ040+050BAWH 4 EWA/YQ064BAWH 450 400 External static pressure 250 External static pressure kPa l/min l/min Water flow Water flow kPa 17 1 EWA/YQ016~025BAWN 2 EWA/YQ032BAWN 3…
-
CE - DICHIARAZIONE-DI-CONFORMITA CE - ¢H§ø™H ™YMMOPºø™H™ CE - ERKLÆRING OM-SAMSVAR CE - ILMOITUS-YHDENMUKAISUUDESTA CE - PROHLÁŠENÍ-O-SHODĚ 01 Daikin Europe N.V. is authorised to compile the Technical Construction File. 02 Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte…
-
esta declaración
настоящее заявление: 19 • Maksimalni dovoljeni tlak (PS): <K> (bar) • Minimalna/maksimalna dovoljena temperatura (TS*): * TSmin: Minimalna temperatura na nizkotlačni strani: <L> (°C) * TSmax: Nasičena temperatura, ki ustreza maksimalnemu dovoljenemu tlaku (PS): <M> (°C) • Hladivo: <N> • Nastavljanje…
-
INSTALLATION MANUAL
How to get the manual? A printed version of the manual is delivered with the unit. ■ Contact your local dealer for an electronic version of the manual. For detailed instructions about how to install and operate the associated products and/or optional equipment, refer to the relevant catalogues…
-
Applicable legislation
3. PREPARE THE INSTALLATION OF THE AIR TO WATER CHILLER 3.1. Check that you have all optional equipment All international, European, national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain. Accessories: Equipment which is…
-
General precautions on installation location 3.2.3. Select an installation site that meets the following requirements: ■ The foundation must be strong enough to support the weight of the unit. The floor must be flat to prevent vibrations and noise generation and to have sufficient stability. ■ The…
-
Take care that the components installed in the field piping can withstand the water pressure (maximum 3 bar + static pressure of the pump). - For units with a standard pump installed (EWA/YQ*BAWP), refer to figure 15 External static pressure= External static pressure Water flow= Water flow - For units…
-
Point of attention regarding quality of the public electric power
supply. 4 This equipment complies with respectively: ■ EN/IEC 61000-3-11(1) provided that the system impedance Zsys is less then or equal to Zmax. ■ EN/IEC 61000-3-12(2) provided that the short-circuit power Ssc is greater than or equal to the minimum Ssc value at the interface point between the…
-
The unit must be installed on a solid longitudinal foundation
(steelbeam frame or concrete) and make sure the base under the unit is larger than the grey marked area in figure 9: ■ Hole for foundation bolt Inner dimension of the base Distance between foundation bolt holes Depth of unit Outer dimension of the base Longitudinal foundation dimension Distance…
-
Overview of the unit 4.4.1. Main components of the outdoor module 4.4.2. Electronic expansion valve (subcooling) (Y2E) Electronic expansion valve (main) (Y1E) Check valve Filter Fan Fan motor (M1F,M2F) Heat exchanger Distributor Pressure regulating valve Refrigerant regulator 4-way valve (heat…
-
Water inlet connection 9. Water outlet connection Switch box of the hydraulic compartment (panel 1) 10. Drain and fill valve 11. Water filter The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator. The water filter must be cleaned on a regular base. See…
-
Perform the water piping work 4.5.1. Connecting the water pipes Water connections must be made in accordance with all applicable legislations and the outlook drawing delivered with the unit, respecting the water in- and outlet. NOTICE Be careful not to deform the unit piping by using excessive force…
-
The default value of pre-pressure (Pg) responds to 7 m height
difference. If the height difference of the system is lower than 7 m AND the volume in the system is less than the maximum allowed value at that pre-pressure (Pg) (see chart above), then NO pre-pressure (Pg) adjustment is required. Example 1 The unit is installed 5 m below the highest point in the…
-
Fill the water circuit 1 Connect the water supply to the drain and fill valve (see "4.4.2. Main components of the hydro module" on page 8). 2 Make sure the automatic air purge valve is open (at least 2 turns). 3 Fill with water until the pressure gauge indicates a pressure of approximately 2.0 bar.…
-
Internal wiring – Parts table – Hydro module Refer to the wiring diagram sticker on the hydro module front panel 1 (refer to "4.2.2. Opening the unit" on page 7). The abbreviations used are listed below: A1P Main PCB (master) A2P remote controller PCB A3P Control PCB A4P Demand PCB (optional) A5P…
-
CAUTION Fasten the remote controller on a flat surface. Select all cables and wire sizes in accordance with relevant local and national regulations. WARNING NOTICE After finishing the electric work, confirm that each electric part and terminal inside the electric parts box is connected securely. Be…
-
How to connect for multi unit
7 Refrigerant leak Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak try to repair the leak (recovery, repair, and vacuuming needed). If it is impossible to repair by yourself, call your local dealer. Do not touch any refrigerant which has leaked out of refrigerant…
-
Setting procedure
-
Confirmation of the set mode
5.2.4. The following items can be confirmed by setting mode 1 (H1P LED is off) To change one or more field settings, proceed as follows. Check the LED indication in the field marked 1 . Indication of the present operation state - x, normal - w, abnormal - c, under preparation or under test operation 3…
-
Detailed description For a summary of all field settings refer to "6.1.1. Field settings table" on page 39. [0] Remote control setup ■ [0-00] User permission level The remote controller can be programmed to make certain buttons and functions unavailable for the user. There are 2 permission levels…
-
Method 2
Space heating based on ON/OFF instruction During operation When the schedule timer switches space heating OFF, the controller will be switched off (operation LED will stop working). When pushing the y button The schedule timer for space heating will stop (when active at that moment) and will start…
-
[3] Weather dependent set point
[6] Option setup ■ INFORMATION Only for EWYQ units operating in heating mode. Setback function for cooling does not exist. When weather dependent operation is active, the leaving water temperature is determined automatically depending on the outdoor temperature: colder outdoor temperatures will…
-
[8-04] Freeze-up prevention The unit has a freeze-up prevention functionality for which 3 levels can be selected: ■ [8-04]=0 prevention level 0 (default: no prevention) ■ [8-04]=1 prevention level 1 ■ [8-04]=2 prevention level 2 The freeze-up prevention is only active when the unit is in thermo OFF…
-
5.3.1. Final check and test run Final check Procedure for space heating/cooling 1 Check the leaving water and entering water temperature through the remote controller read-out mode and write down the displayed values. See "Temperature read-out mode" on page 22. 2 Select the operation mode: heating…
-
Service and maintenance 6 In order to ensure optimal operation of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals. ■ A pH-value below 8.0 indicates that a significant portion of the inhibitor has been depleted and that more…
-
UNIT SPECIFICATIONS 6.1. Technical specifications ANNEX Handover of the installation to the user 016 Dimensions (HxWxD) (mm) Weight • machine (kg) • operation (kg) Connections Expansion vessel volume (l) Safety valve water circuit (bar) External static pressure (ESP) • EWA/YQ*BAWP • EWA/YQ*BAWH…
-
OPERATION MANUAL
Accessories: Equipment which is delivered with the unit and which needs to be installed according to instructions in the documentation. Optional equipment: 1. DEFINITIONS 1.1. Meaning of warnings and symbols Warnings in this manual are classified according to their severity and probability of…
-
QUICK START-UP OF THE UNIT 5. OPERATING THE UNIT In this chapter the step-by-step procedure is explained for starting up space cooling/heating. CAUTION The more detailed information of how the unit must be operated is explained in the chapter "5. Operating the unit" on page 26. The quick start-up…
-
Name and function of buttons and icons 13. NOT AVAILABLE n This icon is displayed whenever a non-installed option is addressed or a function is not available. A function not available can mean insufficient permission level or can mean that a slave remote controller is used (see installation manual).…
-
26. PROGRAMMING BUTTON <
This multi-purpose button is used to program the controller. The function of the button depends on the actual status of the controller or on previous actions carried out by the operator. INFORMATION 27. SCHEDULE TIMER BUTTON r/p The main function of this multi-purpose button is to enable/disable the…
-
Leaving water temperature control (default) In this mode, cooling will be activated as required by the water temperature set point. The set point can be set manually or through the schedule timer. 5.5.1. In this mode, heating will be activated as required by the room temperature set point. The set…
-
INFORMATION
■ ■ Press the ba button 1 time to select weather dependent set point operation (or 2 times when the remote controller room thermostat function is used). 1 While room temperature setback function is active, leaving water setback operation is also performed (see "5.5.2. Leaving water temperature…
-
s)
Quiet mode operation (s Automatic setback function 5.6.3. Setback function provides the possibility to lower the room temperature. The setback function can for instance be activated during the night because the temperature demands during night and day are not the same. Quiet mode operation means…
-
Schedule timer operation In schedule timer operation, the installation is controlled by the schedule timer. The actions programmed in the schedule timer will be executed automatically. Operation example: Schedule timer based on temperature set points When setback function is enabled, the setback…
-
Operation example: Schedule timer based on ON/OFF instruction
5.9. When setback function is enabled, the setback operation will have priority over the scheduled action in the schedule timer if ON instruction is active. If OFF instruction is active this will have priority over the setback function. At any time the OFF instruction will have the highest priority.…
-
Programming Programming space Programming space cooling is carried out as follows: INFORMATION Returning to previous steps in the programming procedure without saving modified settings is done by pressing the pr button. 1 Press the < button to enter the programming/consulting mode. 2 Select the…
-
Programming space heating
Programming space heating is carried out as follows: INFORMATION Returning to previous steps in the programming procedure without saving modified settings is done by pressing the pr button. 1 Press the < button to enter the programming/consulting mode. 2 Select the operation mode you would like to…
-
Programming quiet mode
5.9.3. Consulting programmed actions Consulting space heating actions Consulting space cooling heating, space heating or quiet mode is carried out as follows. INFORMATION Returning to previous steps in this procedure is done by pressing the pr button. 1 Press the < button to enter the…
-
Deleting one or more programmed actions
5.10. Operating the optional demand PCB Deleting one or more programmed actions is done at the same time as storing the programmed actions. An optional PCB EKRP1AHTA can be connected to the unit and be used to remotely control the unit When all actions for one day have been programmed, make sure…
-
FIELD SETTINGS 6.1. Procedure To change one or more field settings, proceed as follows. NOTICE The default values mentioned in "6.1.1. Field settings table" on page 39 are the values from factory. The actual initial values shall be selected according to your application. These values shall be…
-
Field settings table Installer setting at variance with default value First code Second code 0 Remote control setup Value Date Value Default value Range Step Unit 00 User permission level 2 2~3 1 — Room temperature compensation value 0 –5~5 0.5 °C 02 Not applicable. Do not change the default value.…
-
Installer setting at variance with default value
First code Second code A Option setup b C d E F Setting name Date Value Date Value Default value Range Step Unit 00 Not applicable. Do not change the default value. 0 — — — 01 Not applicable. Do not change the default value. 0 — — — 02 Not applicable. Do not change the default value. 5 — — — 03…
-
MAINTENANCE 8.1. Error code Failure cause Corrective action 7.1. Important information regarding the refrigerant used A1 Failure of writing memory (EEPROM error) Contact your local dealer. A6 Malfunction water circuit • Make sure waterflow is possible (open all valves in the circuit). • Force clean…
-