Модульные 3-фазные ИБП CyberPower серии HSTP3T10KE / KEBC / KEBCWOB, HSTP3T15KE / KEBC / KEBCWOB, HSTP3T20KE / KEBC / KEBCWOB, HSTP3T30KE / KEBC / KEBCWOB, HSTP3T40KE / KEBC / KEBCWOB с возможностью параллельного расширения, для достижения резервирования питания N+X для корпоративных приложений. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
User’s Manual
HSTP3T10KE / KEBC / KEBCWOB HSTP3T15KE / KEBC / KEBCWOB HSTP3T20KE / KEBC / KEBCWOB HSTP3T30KE / KEBC / KEBCWOB HSTP3T40KE / KEBC / KEBCWOB CyberPower Systems, Inc. www.cyberpower.com
-
This manual contains information concerning the installation and operation of Tower UPS
Please carefully read this manual prior to installation. The Tower UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty. Safety…
-
Move & Install
Danger Warning Attention Keep the equipment away from heat source or air outlets. In case of fire, use dry powder extinguisher only, any liquid extinguisher can result in electric shock. Do not start the system if any damage or abnormal parts founded. Contacting the UPS with wet…
-
in this manual
Battery Safety Danger All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by trained personnel. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. Battery…
-
eyes and your skin may be damaged by the acid. At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace…
-
1.1 System Configuration
The Tower UPS is configured by the following part: Rectifier, Charger, Inverter, Static Switch and Manual Bypass Switch. One or several battery strings should be installed to provide backup energy once the utility fails. The UPS structure is shown in Fig. 1-1. Fig.1-1 UPS Configuration 1.2 Operation…
-
1.2.2 Battery Mode
Upon failure of the AC mains input power, the inverter of power modules, which obtain power from the battery, supply the critical AC load. There is no interruption in power to the critical load upon failure. After restoration of the AC mains input power, the” Normal mode” operation will continue…
-
Fig.1-5 Maintenance mode operation diagram
Danger During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even with all the modules and the LCD turned off. 1.2.5 ECO Mode To improve system efficiency, UPS rack system works in Bypass mode at normal time, and inverter is standby. When the utility…
-
1.2.7 Frequency Converter Mode
By setting the UPS to Frequency Converter mode, the UPS could present a stable output of fixed frequency (50 or 60Hz), and the bypass static switch is not available. 1.3 UPS Structure 1.3.1 UPS Configuration The UPS configuration is provided in Table 1.1 Item Standard Backup Type Long Backup Type…
-
Fig.1-8
20/30kVA System outlook (Long backup type) Fig.1-9 20/30kVA System outlook (Standard backup type) HSTP3T10-40KE/KEBC/KEBCWOB User Manual 5
-
Fig.1-10 10-40kVA front appearance
Fig.1-11 10/15 kVA back appearance 6 HSTP3T10-40KE/KEBC/KEBCWOB User Manual
-
Fig.1-12 20/30kVA back appearance
Fig.1-13 40kVA long type back appearance HSTP3T10-40KE/KEBC/KEBCWOB User Manual 7
-
Fig.1-13 40kVA standard type front appearance
Note The Standard product is configured with single input; the dual-input option is available, with an additional breaker for the main input 8 HSTP3T10-40KE/KEBC/KEBCWOB User Manual
-
2.1 Location
As each site has its requirements, the installation instructions in this section are to act as a guide for the general procedures and practices that should be observed by the installing engineer. 2.1.1 Installation Environment The UPS is intended for indoor installation and uses forced convection…
-
Fig.2-1-1 Size of the 10/15 kVA UPS of Long Backup Type (Unit : mm)
Fig.2-1-2 Size of the 10/15 kVA UPS of standard backup Type (Unit : mm) Fig.2-2-1 Size of the 20/30kVA UPS of Long Backup Type (Unit : mm) 10 HSTP3T10-40KE/KEBC/KEBCWOB User Manual
-
Fig.2-2-2 Size of the 20/30kVA UPS of Standard Backup Type (Unit : mm)
Fig.2-3-1 Size of the 40kVA UPS Long Backup Type (Unit : mm) HSTP3T10-40KE/KEBC/KEBCWOB User Manual 11
-
Fig.2-3-2 Size of the 40kVA UPS Standard Type (Unit: mm)
Fig.2-4 Room reserved for the cabinet(Unit:mm) 12 HSTP3T10-40KE/KEBC/KEBCWOB User Manual
-
The weight for the UPS cabinet is shown in Table 2.1
Table 2.1Weight for the cabinet Configuration Weight 10kVA/15kVA Standard Backup Type 52kg(No Batteries Included) 10kVA/15kVA Long Backup Type 31kg 20kVA/30kVA Standard Backup Type 89kg(No Batteries Included) 20kVA/30kVA Long Backup Type 50kg 40kVA Standard Backup Type 140kg(No Batteries Included)…
-
4. Remove the protective foam around the cabinet
Fig.2-7 Remove the protective foam 5. Check the UPS. (a) Visually examine if there are any damages to UPS during transportation. If any, contact to the carrier. (b) Check the UPS with the list of the goods. If any items are not included in the list, contact to our company or the local office. 6.…
-
2.3 Positioning
2.3.1 Positioning Cabinet The UPS cabinet has two way of supporting itself: One is to support itself temporarily by the four wheels at the bottom, making it convenient to adjust the position of the cabinet;The other is by anchor bolts to support the cabinet permanently after adjusting the position…
-
2.4 Battery
Three terminals(positive,neutral,negative)are drawn from the battery unit and connected to UPS system. The neutral line is drawn from the middle of the batteries in series (See Fig.2-9). N + N batteries in series Fig.2-9 Battery string wiring diagram Danger The battery terminal voltage is of more…
-
2.6 Power Cables
2.6.1 Specifications The UPS power cables are recommended in Table 2.2. Main Input Main Output Bypass Input (Optional) Battery Input PE Table 2.2 Recommended cables for power cables Contents 10/15kVA 20/30kVA Main Input Current(A) 18/28A 35/55A A 6 10 Cable B 6 10 Section C 6 10 (mm²) N 6 10 Main…
-
Output
Cables crimped OT terminal M6 7mm 4.9Nm PE Cables crimped OT terminal M6 7mm 4.9Nm 2.6.3 Circuit Breaker The circuit breakers (CB) for the system are recommended in Table 2.4. Installed position Battery CB Table 2.4 Recommended CB 10/15kVA 20kVA 32A,250Vdc 50A,250Vdc 30kVA 63A,250Vdc 40kVA…
-
Fig.2-13 Connections terminals for 40kVA
3. Connect the protective earth wire to protective earth terminal (PE). 4. Connect the AC input supply cables to the Input terminal and AC output supply cables to the Output terminal. 5. Connect the Battery cables to the Battery terminal. 6. Check to make sure there is no mistake and re-install all…
-
Fig.2-14 Dry contact &communication interface
2.7.1 Dry Contact Interface Dry contact interface includes port J2-J11 and the functions of the dry contact are shown in Table 2.5. Table 2.5 Functions of the port 20 Port Name Function J2-1 J2-2 J3-1 J3-2 J4-1 J4-2 J4-3 J4-4 J5-1 TEMP_BAT TEMP_COM ENV_TEMP TEMP_COM REMOTE_EPO_NC +24V_DRY +24V_DRY…
-
J9-1
GENERAL_ALARM_NC Output dry contact, (Normally closed) function is settable. Default: Fault alarming J9-2 GENERAL_ALARM_NO Output dry contact, (Normally open) function is settable. Default: Fault alarming J9-3 GENERAL_ALARM_GND J10-1 UTILITY_FAIL_NC J10-2 UTILITY_FAIL_NO Output dry contact…
-
Remote EPO Input Port
J4 is the input port for remote EPO. It requires shorting NC and +24V and disconnecting NO and +24V during normal operation, and the EPO is triggered when opening NC and +24V or shorting the NO and +24V. The port diagram is shown in Fig.2-16, and port description is shown in Table 2.7. +24V +24V…
-
BCB Input Port
The default function of J6 and J7 are the ports of BCB. The port diagram is shown in Fig.2-18, and description is shown in Table 2.9. +24V +24V +24V J7 B C B V R _ D B C B T N _O C Fig.2-18 BCB Port Port J6-1 J6-2 J7-1 J7-2 B C B L N _ O J6 Table 2.9 Description of BCB port Function BCB contact…
-
Port
Name J8-2 BAT_LOW_ALARM_NO J8-3 BAT_LOW_ALARM_GND Function Battery warning relay (normally open) will be closed during warning Common terminal General Alarm Output Dry Contact Interface The default function of J9 is the general alarm output dry contact interface. When one or more warnings are…
-
Port
Table 2.12 Utility failure warning dry contact interface description Name Function J10-1 UTILITY_FAIL_NC J10-2 UTILITY_FAIL_NO J10-3 UTILITY_FAIL_GND Mains failure warning relay(normally closed) will be open during warning Mains failure warning relay (normally open) will be closed during warning…
-
3.1 Introduction
This chapter introduces the functions and operator instructions of the operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm information. 3.2 LCD panel for Cabinet The…
-
Indicators
Bypass indicator Inverter indicator State Off Steady green Steady red Flashing red Off Steady green Flashing green Steady red Flashing red Off Steady green Load indicator Status indicator Steady red Flashing red Off Steady green Steady red Description Battery and battery converter normal, battery…
-
3.2.3 LCD Screen
After the monitoring system starts self-test, the system enters the home page, following the welcome window. The home page is shown in Fig.3-2. Home page consists of System Information Window, Menu Window and Current Command and Record Menu. Fig.3-2 Home page The description of LCD icons is shown in…
-
HOME
A I/P MAIN B NEXT C 220.1 V 45.0 A 50.01 Hz 0.99 PF 220.1 V 45.0 A 50.01 Hz 0.99 PF 220.1 V 45.0 A 50.01 Hz 0.99 PF Fig.3-3 Main input page Select the icon of HOME , it will display the information of battery, as shown in Fig.3-4. BATTERY P.1 Batt Volt Batt Curr Batt Number Dischag Times Status NEXT…
-
Table 3.5 Description of System Information Window
Content Description UPS mode:3-phase in 3-phase out 20kVA,standard HSTP3T20KE backup type 16:30 Current time 3.4 Menu Window The Menu Window displays the menu name of data window, while the data window displays the related contents of selected menu in menu window. Select UPS menu and data window to…
-
Menu
name Menu item Meaning formats can be selected Date & Time Language set Communication set Control password 1 set Battery maintenance test Command Battery self-check test Stop testing UPS system information Monitoring software version Rectified software version Inverted software version Serial No.…
-
15 Generator Input-Clear Incident above disappears 16 Utility Abnormal-Set Utility (Grid) Abnormal 17 Utility Abnormal-Clear Incident above disappears 18 19 Bypass Sequence Error-Set Bypass Sequence Error-Clear Bypass voltage Sequence is reverse Incident above disappears 20 Bypass Volt Abnormal-Set…
-
On UPS Inhibited-Set Inhibit system transfer from bypass to UPS (inverter) 57 On UPS Inhibited-Clear Incident above disappears 58 Manual Transfer Byp-Set Transfer to bypass manually 59 Manual Transfer Byp-Set Cancel to bypass manually 60 Esc Manual Bypass-Set Escape transfer to bypass manually…
-
95 Relay Connect Fail-Set Relay in open circuit 96 Relay Connect Fail-Clear Incident above disappears 97 Relay Short Circuit-Set Relay shorted 98 Relay Short Circuit-Clear Incident above disappears 99 No Inlet Temp. Sensor-Set The inlet temperature sensor is not connected or abnormal 100 No Inlet…
-
4.1 UPS Start-up
The UPS must be started up by commissioning engineer after the completeness of installation. The steps below must be followed: 1. Ensure all the circuit breakers are open. 2. Close the output circuit breaker (CB) and then the input CB and the system starts initializing. If the system has dual…
-
4.2 Procedure for Switching between Operation Modes
4.2.1 Switching the UPS into Battery Mode from Normal Mode The UPS transfers to Battery model immediately after input circuit breaker disconnects from the utility. 4.2.2 Switching the UPS into Bypass Mode from Normal Mode Follow the path by selecting the icon of the system to Bypass Mode. and then…
-
Waring
Once the cover on the maintenance bypass breaker is removed, the system will transfer to bypass mode automatically. Waring Before making this operation, confirm the messages on LCD display to be sure that bypass supply is regular and the inverter is synchronous with it, so as not to risk a short…
-
BACK
FUNCTION END ManualByp/Esc Batt. Test Fault Clear Maint Test Manual INV Stop Test Fig.4.3 Battery maintenance 4.4 EPO The EPO button located in the operator control and display panel (with cover to avoid disoperation, see Fig.4-5) is designed to switch off the UPS in emergency conditions (e.g.…
-
4.5 Installation of Parallel Operation System
4.5.1 Parallel system diagram Up to four UPS could be paralleled,with a diagram as shown in Fig.4-6. Power Supply UPS1 UPS2 UPS3 UPS4 Output Power Supply Load Connected Fig. 4-6 Parallel diagram The parallel board is located at the back of the UPS cabinet, as is shown in Fig.4-7.…
-
A
Fig.4-7 Location of the Parallel board All the parallel cables are designed to be shielded and double insulated, and are connected between the UPS to form a loop as shown below in Fig. 4-8. Fig.4-8 Parallel connection 40 HSTP3T10-40KE/KEBC/KEBCWOB User Manual
-
4.5.2 Parallel system setting
Parallel system connection For field installation, please connect the cables according to Fig.4-6 and Fig.4-8. In order to assure that all units are equally utilized and to comply with relevant wiring rules, the following requirements apply: 1. All units shall be of the same rating and must be…
-
Fig.4-12 Connectors on Control board (PS1203_CT1) 42 HSTP3T10-40KE/KEBC/KEBCWOB User Manual
-
1. Parallel boards settings
A. For single UPS, no need parallel board. When a parallel board is installed, connectors of J33 to J42 should be shorted by the jumpers. B. For 2 UPS in parallel, short the connectors of J33/J35/J37/J39/J41 by jumpers on each board, keep connectors of J34/J36/J38/J39/J42 open C. For 3 or 4 UPS in…
-
This chapter introduces UPS maintenance, including the maintenance instructions of power
module and monitoring bypass module and the replacement method of dust filter. 5.1 Precautions 1. Only certified engineers are authorized to maintain the UPS. 2. The components or PCBs should be disassembled from top to bottom, so as to prevent any inclination from high gravity center of the…
-
Warning
If a battery has leakage or is damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations. The waste lead-acid battery is a kind of hazardous waste and is one of the major contaminants controlled by government. Therefore, its…
-
3.Connect the battery cable according to the series number
4.Recover the cover Fig.5-1 Installation of inner battery for10/15K standard UPS Fig.5-2 shows the installation of batteries for 20/30K standard UPS. There are 8 groups of batteries in series, with 5 cells for each group. The interconnection among groups is via cable with Anderson Socket. L5 L1 L4…
-
Layer 1. The positive of the battery 1# is connected to battery breaker CB4-2, via the cable
labeled L1, and the negative of battery 40# is connected to CB4-6, via the cable labeled L2, as shown in Fig.5-2-2. L1 L4 L4 Fig.5-2-2 Cable connection of Lay 1 Layer 2. The positive of the battery 6# is connected to the negative of battery 5#, via the cable labeled L4, and the negative of battery…
-
L4
L4 L4 L4 Fig.5-2-4 Cable connection of Lay 3 Layer 4. The positive of the battery 16# is connected to the negative of battery 15#, via the cable labeled L4, and the negative of battery 25# is connected to the positive of battery 26#, via the cable labeled L4. The negative of 20# and the positive of…
-
For 40kVA the battery bank has four layers. Each lay has four packages with 5 batteries
contained in one package.Fig5-3 shows the connection of each layer. Fig. 5-3 battery connection of each layer HSTP3T10-40KE/KEBC/KEBCWOB User Manual 49
-
After the connected as shown in Fig 5-3, connect the connectors as following as zoomed in Fig
5-4 Terminal+: W01-1 and W01-2 Terminal N: W03-1, W03-2, W03-4, W03-4 Terminal-: W02-1 and W02-2 Fig. 5-4 Battery terminal connection After connect the terminal, recover the cover as shown in the following Fig. 5-5 Fig. 5-5,Recover the cover Warning Make sure the polarity of the battery is correct…
-
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics. 6.1 Applicable Standards The UPS has been designed to conform to the following European and international standards: Table 6.1 Compliance with European and International Standards Item Normative reference General safety…
-
Color
Protection Level IEC(60529) N/A BLACK,RAL 7021 N/A IP20 Model Dimension W×D×H Weight Color Protection Level IEC(60529) Unit 20/30KE 20/30KEBC 20/30KEBCWOB mm 250*680*770 350*738*1335 350*738*1335 kg N/A 50 Model Dimension W×D×H Weight Color Protection Level IEC(60529) Unit 40KE 40KEBC 40KEBCWOB mm…
-
6.4.2 Electrical Characteristics (Intermediate DC Link)
Table 6.6 Battery Items Battery bus voltage Quantity of lead-acid cells Float charge voltage Temperature compensation Ripple voltage Ripple current Equalized charge voltage Unit Vdc Parameters Rated:±240V Nominal 40=[1 battery(12V)] ,240=[1 battery(2V)] V/cell (VRLA) 2.25V/cell(selectable from…
-
6.4.4 Electrical Characteristics (Bypass Mains Input)
Table 6.8 Bypass Mains Input Item Unit Value 380/400/415 (three-phase four-wire and sharing neutral with the bypass) 125% Long term operation; 125%~130% for 10min; 130%~150% for 1min; 150%~400% for 1s; >400% ,less than 200ms Rated AC voltage Vac Overload % Current rating of neutral cable A 1.7×In Hz…