Инструкция на ИБП для систем отопления CyberPower серии CPS (600-7500ВА)
ИБП для систем отопления CyberPower серии CPS1500PIE для обеспечения бесперебойной работы котельного и другого инженерного оборудования, систем освещения и видеонаблюдения, различных бытовых приборов. Руководство по эксплуатации.
Загружаем документ…
Текст инструкции
-
EN
User’s Manual CPS1500PIE CyberPower Systems, Inc. Website: www.cpsww.com K01-0000133-03
-
SAFETY AND EMC INSTRUCTIONS
Safety and EMC instructions This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your Emergency Power System (EPS). CAUTION! To…
-
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!
DO NOT use in any circumstance that would affect operation or safety of any life support equipment or with any medical applications or patient care. DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation from the aquarium…
-
INSTALLING YOUR EPS
Installing your EPS UNPACKING Inspect the EPS upon receipt. The box should contain the following: EPS unit x 1; Installation Guide x 1; User manual x 1 AUTOMATIC VOLTAGE REGULATOR When utility power is inconsistent, the EPS would increases low voltage or decrease high voltage to safe 220 volts. The…
-
BASIC OPERATION
B CPS1500PIE DESCRIPTION 1. AC Outlets EPS PIE Series have one general plug-in outlet (UK/Schuko/France) and one IEC (C13 x 4) outlet for connected equipment which ensures temporary uninterrupted operation of the equipment during a power failure. Max. Output of 1a is 16A for terminal block or 10A…
-
5. AC Output Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection. *Note: Circuit breaker 5a provides 1a socket max 16A protection for CPS1500 Series. *Note: Circuit breaker 5b provides max 12A protection for UK socket or 16A for Schuko and France socket. 6. AC…
-
INSTALLATION GUIDE
Note: The installation must be done by professionals. Step 1 1. Remove the cover from the back of the machine. 2. Make sure the POWER SW, Output Selector, and the BATTERY SW. are turned off. (Step1) Step 2 Step 3 3. Connect the AC OUTPUT connections (AC plugs or terminal connections). (Step2) 4.…
-
Step 4
Step 5 5. Connect the batteries to the BATTERY INPUT. (Step4) WIRING FAULT LED will illuminate and make an audible alarm to indicate the wiring polarity is reversed only when the DC circuit breaker is off. *Note: Please make sure the DC circuit breaker is off before connecting the battery to the…
-
DEFINITIONS FOR ILLUMINATED LCD
Definitions for illuminated LCD The LCD Display indicates a variety of EPS operational conditions. All descriptions apply when the EPS is plugged into an AC outlet and turned on or when the EPS is on battery. 1. INPUT VOLTAGE Meter: This meter measures the AC voltage that the EPS is receiving from…
-
EPS Status Inquiry and Functions Setup
p 1. General Mode a. Press the LCD Display Toggle (Selected Switch) to check the status of the EPS. Item Input Voltage Output Voltage Load Capacity Battery Capacity Unit V V % % b. Press and hold the Display Toggle for 4 seconds. – If the machine is in the Battery Mode, it enters/leaves Silent Mode.…
-
b
Battery Capacity: The function adjusts the battery capacity of the used batteries. Default 100AH Choice 50, 75, 100AH, others (0H) Note: The default value would be 100AH unless the capacity of the EPS bundling battery is not 100AH. In this case, the default value changes according to the capacity of…
-
Step 3: Press and hold the toggle for 4 seconds. When the icons blink, the value of each item can be
changed by slightly pressing the toggle. Step 4: To save the value and return to general mode, press and hold the toggle for 4 seconds. Note: If the machine is left idle for over 30 seconds during setup, it will turn off the backlight and return to general mode automatically. Note: If user wants to…
-
CAUTION!
The following statements related to the battery warranty are highly important. Please read and abide by them carefully. Do not set the inappropriate battery capacity. Incorrect charging current will seriously affect the cycle use of the battery. Use LOWEST/LOW current level for setting if the…
-
FAULT WARNING DISPLAY AND ALARM
Fault warning display and alarm 1. The following table shows each corresponding warning message on the LCD display and the alarm reacts during the machine shutdown: LCD Warning Display Alarm Condition Solution Long Beep Overload Check total load to confirm the rating of EPS. Battery missing in Line…
-
The following table shows the information about the error codes on the LCD display AFTER the machine shutdown. The LCD will show the message till the EPS runs out of battery. Error Type Error Code Possible cause Line Mode Error E0 E1 AVR Fail Battery Overcharge AVR broke down Charger broke down…
-
REPLACING THE BATTERY
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Battery service should only be done by qualified professionals. CAUTION! Use only the specified type and number of external batteries. Please see the technical specifications for replacement batteries. Mix usage…
-
TROUBLESHOOTING
Trouble shooting Problem Outlet does not provide power to equipment. Possible Cause Circuit breaker has tripped due to an overload. Batteries are discharged. Recharge the unit for at least 4 hours. Unit has been damaged by a surge or spike. Contact CyberPower Systems or local agent about replacement…
-
TECHNICAL SPECIFICATIONS
Technical specifications Model Capacity (VA) Capacity (Watts) Operation Technology AC Input Input Voltage Range Input Frequency Range AC Output Phase CPS1500PIE 1500VA 1050W AVR (Double Boost & Single Buck) 140Vac – 300Vac 50/60 Hz +/- 5 Hz (auto sensing) Single Phase Output Voltage Nominal Output…
-
For more information, contact us at
CyberPower Systems, Inc. Website: www.cpsww.com Entire contents copyright © 2014 CyberPower Systems, Inc. All rights reserved. Reproduction in whole or in part without permission is prohibited. Copyright © 2014 CyberPower Systems, Inc.
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.