Инструкция на Программное обеспечение CyberPower PowerPanel® Enterprise
Программное обеспечение CyberPower PowerPanel® Enterprise самое полное централизованное программное обеспечение для управления питанием для центра обработки данных. Руководство пользователя.
Загружаем документ…
Текст инструкции
-
USER’S MANUAL
PowerPanel® Enterprise Basic/ Standard/ Advanced Rev. 5 SAVE THESE INSTRUCTIONS Please read this manual and follow the instructions for installation and use. Copyright © 2020 Cyber Power Systems, Inc. All rights reserved.
-
Chapter 1 Introduction
1.1 Overview PowerPanel® Enterprise software is a centralized power monitoring software designed to monitor and manage a large number of devices in the data center. The software allows users to customize the floor map of data center, and displays the devices and their real-time information in…
-
Dataloader PowerPanel® Enterprise has built in the SNMP OIDs of all attributes of CyberPower devices. The Dataloader program collects the values of the SNMP OIDs or the Modbus data of all devices in the system and saves the historical data of all devices in the local database. It synchronizes with…
-
Figure 1.2 AlertMail
1.2.4 Upgrade Tool Use your PowerPanel® Enterprise account and password to log in to Upgrade Tool (Figure 1.3). The Upgrade Tool allows users to upgrade the PowerPanel® Enterprise software, including the web applications, AlertMail and Dataloader (Figure 1.4). Figure 1.3 Log in to Upgrade Tool 3
-
Figure 1.4 Upgrade Function
1.3 Prerequisites The Prerequisites section describes the recommended hardware and software requirements for users to install and run the PowerPanel® Enterprise software on the server. For the detailed steps on software installation, refer to “PowerPanel® Enterprise Installation Guide”. 1.3.1…
-
Software Requirements Table 1.2 describes the software and operating system required to install the PowerPanel® Enterprise software, and the supported web browsers which allow users to remotely access the system. Table 1.2 Software Requirements Software Requirement Operating System Windows Server…
-
Feature Specification The supported features and specifications of PowerPanel® Enterprise Basic/ Standard/ Advanced are described in Table 1.3. Table 1.3 Feature Specification Software Tier PowerPanel® Enterprise PowerPanel® Enterprise PowerPanel® Enterprise Basic Standard Advanced Unlimited…
-
Chapter 2 Login
Use the default account Admin and password admin to log in to PowerPanel® Enterprise, and change the default password immediately (Figure 2.1). Figure 2.1 Login page 7
-
Chapter 3 Tool Bar
The Tool Bar allows users to change the system language and account password, and log out of the system (Figure 3.1, Table 3.1). Figure 3.1 Tool Bar function Table 3.1 Tool Bar function description Icon Description Click to change the system language. Click to change account password. Click to log…
-
Chapter 4 Tab Bar
The Tab Bar allows users to open the history pages, and it can display up to 15 page tabs (Figure 4.1, Table 4.1). Figure 4.1 Tab Bar Table 4.1 Tab Bar function description Icon Description Click to hide or show the Tab Bar. Click to close all tabs, leaving only the tab highlighted in the Tab Bar.…
-
Chapter 5 Display Panel
The Display Panel displays the main data in table view, chart view, or floor map view, and the major setup operations are also displayed and completed in this area (Figure 5.1). Figure 5.1 Display Panel 10
-
Chapter 6 INFO Panel
The INFO Panel displays the basic information of the page, list, real-time data of equipment or other settings (Figure 6.1). Figure 6.1 INFO Panel 11
-
Chapter 7 Dashboard
The Dashboard page is the default home page after users log in. PowerPanel® Enterprise provides 32 default dashboard templates to display the overall information and the real-time statistics of data center power, PUE, device status, environmental data, energy consumption and CO2 footprints in…
-
Chapter 8 Floor Map
The Floor Map section provides the Map View (❶ in Figure 8.1) and the List View (❷ in Figure 8.1) for users to monitor the status and real-time information of all equipment in the data center. A floor map can be a data center or a server room, and the floor map can be configured from Setting, see…
-
Figure 8.2 Map List
8.2 Map View The Map View shows the plan layout of the data center and displays the status and real-time information of all equipment. Select the floor map you want to monitor in the table on the Map List page, then click “Map View” to open the selected floor map on a new page (Figure 8.3). After…
-
Figure 8.3 The steps of opening the floor map
Table 8.1 Floor map function description Icon Description Select the attribute to change the status colors for all equipment in the floor map. According to different device category, there are different attributes. The default attributes are as follows: − Health − Connection − Power − Load − Battery…
-
The legend bar shows the different status
colors for the equipment. The default device status settings are as follows: − Green: Normal − Orange: Warning − Light brown: Disconnect (UPS is powered off) − Dark Red: Blackout (Utility power is abnormal) − Red: Severe − Dark gray: Offline − Light gray: Not Supported Click to update the floor map…
-
Figure 8.4 Device group in the floor map
View real-time information of the device Click the color block to view the real-time information of the equipment or the rack in the INFO Panel (❶ in Figure 8.5). Click “Events” (❷ in Figure 8.5) to view the event logs of the selected device. Figure 8.5 Map View – information of the equipment 17
-
View the devices in the rack Click “Show Rack Detail” (❷ in Figure 8.6) to open the rack detail page to view all devices in the rack and the U positon of each device. Click on the device to view the real-time information of the device in the INFO Panel (Figure 8.7). Figure 8.6 Map View – information…
-
View device event logs In the INFO Panel, click “Events” (❷ in Figure 8.5 or ❷ in Figure 8.7) to view the latest 100 records of the device status change log and SNMP Trap log of the selected device. The table at the top of the window shows the device status change events, and the table at the bottom…
-
Figure 8.9 The Daisy Chain Group of the Host device
Figure 8.10 The Parent Device of the Guest device View the outlet details of the device If the device supports “Metered-by-Outlet” function, click on the device and the Outlet Details information will be shown in the INFO Panel (Figure 8.11). Click the “Outlet Details” button to view the real-time…
-
each outlet, and only the Admin users can turn on/ off each outlet (Figure 8.12)
Admin users can select one outlet and click the “Configure” button to rename the outlet and set outlet load thresholds 5 for each outlet (Figure 8.13). Figure 8.11 Outlet Details Information 5 Outlet Load Thresholds: The device has a delay buffer mechanism on the outlet load threshold to avoid…
-
Figure 8.12 Outlet Details windows
Figure 8.13 Outlet Details windows - Configuration 8.3 List View The List View shows all equipment of the selected floor map in a list format. It is very ideal for monitoring the floor map with a large number of devices. Select the floor map you want to monitor in the table on the Map List page…
-
Figure 8.14 The steps of opening the floor map in List View
View device group details Click (❶ in Figure 8.15) to show the equipment list or sub-device group list of the selected device group in a sub-table. Click on the equipment (❷ in Figure 8.15) in the table to show detailed real-time information of the equipment in the INFO Panel (❸ in Figure 8.15).…
-
Chapter 9 Events
The Events section provides the Equipment Status Log and SNMP Trap Log (Figure 9.1) for users to track the events and traps of all equipment. Figure 9.1 Events 9.1 Equipment Status Log The page displays all event logs of the equipment status changes (Figure 9.2) for each floor map. System provides…
-
Figure 9.2 Equipment Status Log
Table 9.1 Equipment Status Log content description 9.2 Content Description Create Time The time when the equipment status changed. Group Name The name of the device group. Rack The name of the rack. Equipment Name The name of the equipment. Outlet No. The outlet number of the equipment. Original…
-
Figure 9.3 SNMP Trap Log
Table 9.2 SNMP Trap Log content description Content Create Time Description The time when the equipment sent out the SNMP trap event. Group Name The name of the device group. Rack The name of the rack. Equipment Name The name of the equipment. Severity The severity of SNMP trap event. Trap Name The…
-
logged in the system (Figure 9.4). System provides user action log filtering (❶ in Figure
9.4) and allows users to export the log as an excel file (❷ in Figure 9.4). The content details are shown in Table 9.3. Figure 9.4 User Action Log Table 9.3 User Action Log content description Content Description Create Time The time when the system operation occurred. Function The function name of…
-
Chapter 10
Analysis The Analysis section provides six analysis categories: Environment, PUE, Device, Power, Energy Consumption and CO2 Footprints. It calculates the analytical data from each floor map and displays the data in different types of charts. 10.1 Environment The Environment page displays the…
-
Figure 10.2 PUE
10.3 Device The Device page displays the statistics on the equipment status, assets review and the utilization of the rack spaces of each floor map (Figure 10.3). Figure 10.3 Device 30
-
Power The Power page displays the power consumption, power capacity and power utilization of each floor map (Figure 10.4). Figure 10.4 Power 10.5 Energy Consumption The Energy Consumption page displays the energy consumption, energy utilization and energy cost of each floor map (Figure 10.5). 31
-
Figure 10.5 Energy Consumption
10.6 CO2 Footprints The CO2 Footprints page displays the CO2 emissions of each floor map (Figure 10.6). Figure 10.6 CO2 Footprints 32
-
Chapter 11 Report
The Report section provides Summary Report, Environment Report and Device Group Report that are used to calculate the analytical data of each floor map to provide an overview of the data center (Figure 11.1). Select the “Period” (❶ in Figure 11.1) and choose the “Start Date” (❷ in Figure 11.1) to…
-
2. Month
Select the month to calculate the data. ❸ ❹ 3. Quarter: Select the year and quarter to calculate the data. - Q1: From January to March - Q4: From October to December - Q2: From April to June Q3: From July to September 4. Year: Select the year to calculate the data. Select one or multiple floor maps…
-
Summary Report The Summary Report shows the overall information of the floor map (Figure 11.2). The report contents are shown in Table 11.2. Figure 11.2 Summary Report Table 11.2 Summary Report content description Content Description The power usage of each floor map, including the Total Power…
-
Environment Report The Environment Report shows the Temperature and Humidity information of the floor map (Figure 11.3). The report contents are shown in Table 11.3. Figure 11.3 Environment Report Table 11.3 Environment Report content description Content Description Average Temperature The average/…
-
Device Group Report The device group report shows the total power output and energy consumption of each device group in the selected floor map (Figure 11.4). The report contents are shown in Table 11.4. Figure 11.4 Device Group Report Table 11.4 Device Group Report content description Content Device…
-
Chapter 12 Setting
The functions described in previous chapters are for viewing the information or contents of the data center only, and they are controlled or adjusted through Setting. This chapter describes all the setting functions and how to maintain a normal operation of the data center. 12.1 System The System…
-
representative for the license registration
Click “Activate” (❶ in Figure 12.2) to open the Activate License window (Figure 12.3, Figure 12.4). Choose one method for license registration, enter your license account credentials or license key, and the system will check the CyberPower Cloud Server to verify the license. Once the verification is…
-
Figure 12.3 Activate License window (CyberPower Account)
Figure 12.4 Activate License window (License Key) Table 12.1 License Information function description Icon Description This button is only displayed when no license account is activated. Click to enter your license account and password to activate the license. This button is displayed when the…
-
Figure 12.5 Unbind license server
Table 12.2 License Information content description Content Description Product The system name (PowerPanel Enterprise.). License Type Maximum License Node The license type of installed PowerPanel Enterprise (Basic.) The maximum number of equipment allowed for the license account. The license account…
-
settings, and the related information displayed in the system will also be updated
(Figure 12.6). The function details and the contents are shown in Table 12.3. ❶ Figure 12.6 Parameter Table 12.3 Parameter content description Content Description Unit of Temperature * °C or °F, the default unit is °C. Energy Cost per kWh * The rate of energy consumption. Currency * The currency…
-
allowing users to add a new department to the organization (Figure 12.8). The
function details are described in Table 12.4 and the contents are shown in Table 12.5. Figure 12.7 Department Table 12.4 Department function description Icon Description Click to add a new department in the table. Click to delete the selected department in the table. Click to edit the selected…
-
Figure 12.8 Add a department
Company The Company page displays the list of company names (Figure 12.9), allowing users to add a new company (Figure 12.10). The function details are described in Table 12.6 and the contents are shown in Table 12.7. Figure 12.9 Company Table 12.6 Company function description Icon Description…
-
Click to delete the selected company in the table
Click to edit the selected company in the table. Click to input the query condition to filter the data in the table. Table 12.7 Company content description Content Description Company Name * The displayed company name. Invoice No The invoice number of the company. Address The address of the company.…
-
new job title (Figure 12.12). The function details are described in Table 12.8 and
the contents are shown in Table 12.9. Figure 12.11 Title Table 12.8 Title function description Icon Description Click to add a new job title in the table. Click to delete the selected job title in the table. Click to edit the selected job title in the table. Click to input the query condition to…
-
Figure 12.12 Add a title
Level The Level page displays the list of job levels (Figure 12.13), allowing users to add a new job level (Figure 12.14). The function details are described in Table 12.10 and the contents are shown in Table 12.11. Figure 12.13 Level Table 12.10 Level function description Icon Description Click…
-
Click to edit the selected job level in the table
Click to input the query condition to filter the data in the table. Table 12.11 Level content description Content Description Level Name * The displayed name of the job level. Enabled Click to activate the job level. Figure 12.14 Add a level 12.1.4 Account The Account page displays the account list…
-
Figure 12.15 Account
Table 12.12 Account function description Icon Description Click to add a new account in the table (Figure 12.16). Click to delete the selected account in the table. Click to edit the selected account in the table. Click to input the query condition to filter the data in the table. Table 12.13…
-
Title
The job title of the account. Level The job level of the account. Sex The gender of the account. E-Mail* The email address of the account. Mobile Phone The mobile phone number of the account. Telephone The office telephone number of the account. Figure 12.16 Add an account 12.1.5 Authorization The…
-
Figure 12.17 Authorization
Type The Type page displays the list of authorization types (Figure 12.18). Click “Add” (❶ in Figure 12.18) to create a new authorization type to set visible pages and function buttons in the system (Figure 12.19). The function details are described in Table 12.14 and the contents are shown in…
-
Figure 12.19 Add an Authorization Type
Table 12.14 Type function description Icon Description Click to add a new authorization type in the table. Click to delete the selected authorization type in the table. Click to edit the selected authorization type in the table. Click to input the query condition to filter the data in the table.…
-
Type and Account The Type and Account page allows users to manage authorization for each account, assigning different authorization types to the account. There are two main windows on this page, the top window displaying the “Type” table and the bottom window displaying the “Account” table (Figure…
-
Figure 12.21 Slideshow
12.2 Equipment The Equipment section allows users to manage equipment parameters and rack configurations, set the thresholds for each equipment status, and add new equipment by auto-discovery function (Figure 12.22). Figure 12.22 Equipment 54
-
12.2.1 Rack
The Rack page displays the rack list and the rack details in the table. Users can click to add a rack or edit the rack configurations (Figure 12.23). The function details are described in Table 12.16. The method of adding a new rack is described in Figure 12.24 ~ Figure 12.27 and Table 12.17. Figure…
-
Figure 12.24 The steps of adding a rack
Table 12.17 The steps description Step ❶ ❷ ❸ ❹ Description Displays the rack space on the front and back of the rack (Figure 12.24). Enter the basic information of the rack in the INFO Panel (Table 12.18). Enter the total rack units of the rack, and click “Refresh” to update the rack space in the…
-
Table 12.18 Rack content description
Content Description Rack Name * The rack name. Location The location of the rack. Description Any notes or descriptions of the rack. Rack Unit (U) * Multi-col The number of total U space of the rack. The default rack unit is set to 42 (U). The space usage for each U space of the rack. Figure 12.25…
-
Figure 12.26 Set the Multi-col to split the U space
Figure 12.27 Drag & drop the device to the rack 12.2.2 Equipment The Equipment section allows users to add equipment and manage the equipment model library, and perform the mass firmware and configuration updates for the SNMP devices in the system (Figure 12.28). 58
-
Figure 12.28 Equipment
Equipment Model The Equipment Model page shows the system built-in equipment model list in the table. Users can click to add a new equipment model (Figure 12.29). The function details are described in Table 12.19 and the equipment model contents are shown in Table 12.20 ~ Table 12.23. Figure 12.29…
-
Table 12.19 The Equipment Model function description
Icon Description Click to open a new page for adding new equipment model in the table. See Figure 12.30 for the details. Click to delete the selected equipment model in the table. (Note: The system built-in equipment model cannot be deleted by users.) Click to open a new page for editing the…
-
3. 3-Phase PDU (LCD)
3-Phase PDU with LCD panel, supporting the Daisy Chain feature. 4. ATS 5. UPS Manufacturer * The default manufacturer is set to CyberPower. Model Name * The name of the equipment model. The remote outlet control and outlet metering functions supported by the equipment model. Outlet Type - Switched…
-
Front Image
The front image of the equipment model. Rear Image The rear image of the equipment model. Equipment List The Equipment List page displays the list of all equipment in the table, allowing users to add new equipment or maintain the information of the equipment (Figure 12.31). The function details…
-
Click to import an Excel file to update the data in the table
Click to export the table as an Excel file. Figure 12.32 Add new equipment Table 12.25 The Basic info content description Content Description The dropdown list of the equipment categories, built-in by system. The system provides five types of default categories: − PDU (LED): PDU with LED panel −…
-
Currently, PowerPanel® Enterprise supports CyberPower own
brand devices only, and the default manufacturer is set to CyberPower. The dropdown list of the equipment models, built-in by system. It Model Name * can be updated by users in Equipment Model or via Plugins. See Equipment Model and Plugins for the details. Installation Date The installation date of…
-
SNMP data from the equipment
The system provides two default authentication profiles: − SNMP − See Authentication Profile for the details. Table 12.26 The Hardware info content description Content Description Rack Units (U) The occupied Rack Unit of the equipment model. Height The physical height of the equipment model. Width…
-
(Figure 12.36), the contents are described in Table 12.33
❷ ❶ ❸ Figure 12.33 Configuration and Upgrade Table 12.29 Configuration and Upgrade function description Icon Description Select the device category from the dropdown list to filter the equipment in the table. Click to perform the firmware updates for the selected devices. See Figure 12.34 and Table…
-
Category Name
The device category of the equipment. IP Address The IP address of the equipment. MAC Address The MAC Address of the equipment. Version The current firmware version of the equipment. Timestamp The last update time of the equipment. Last Action The last operation that was performed by the equipment.…
-
You can close the tab page during the update process. The update will continue to run. When it is finished, you will see the Complete message. ❷ ❶ ❸ ❹ Figure 12.35 Upload Configuration Table 12.32 The steps of configuration update Step ❶ ❷ ❸ ❹ Description Select the devices which you want to update…
-
Figure 12.36 Action Log
Table 12.33 Action Log content description Content Description Equipment The name of the equipment. IP Address The IP address of the equipment. MAC Address The MAC address of the equipment. Launched Action The operation that was performed by the equipment. Result The result of the operation. Message…
-
12.2.3 Threshold Setting
The Threshold Setting page displays the list of the default threshold rules built-in by the system, allowing users to change the threshold value for the status of each attribute to trigger the status changes (Figure 12.37). The function details are described in Table 12.34 and the contents are shown…
-
This field is used for devices on the daisy chain and represents
the order of the device on the daisy chain. The system provides the following sub-device IDs by default. Users can click the Enable checkbox to apply threshold rules to specific devices on the daisy chain. Sub-device ID - All: all devices on daisy chain (host/ guest devices). - 0: Host device. (The…
-
Figure 12.38 Edit the threshold value
Figure 12.39 Duration example of a connected sensor (eg. door sensor) Table 12.36 The default equipment attributes of the status Attributes PDU (LED) Description Health The overall status of all attributes, and it shows the worst status detected by the system. 72
-
Connection
The power output (W) of the equipment. Current The current (A) of the equipment. Temperature environmental sensor connected to the PDU equipment. The temperature (°C/ °F) of the environment, detected by the environmental sensor connected to the equipment. The status of the dry contact#1~4 on the…
-
Outlet Load
Status Humidity Temperature The load status of each outlet. The humidity (%RH) of the environment, detected by the environmental sensor connected to the equipment. The temperature (°C/ °F) of the environment, detected by the environmental sensor connected to the equipment. Contact The status of the…
-
Blackout
Input Voltage The status of the input voltage of the UPS. If the value is equal to 0, the status will shows as Blackout. The UPS output status. Output Mode Load - 1: Severe (Unknown) - 2: Normal (On line mode) - 3: Warning (On battery mode) - 4: Warning (On boost mode) - 5: Warning (On sleep mode)…
-
Table 12.37 The default status
Status Description Offline The network connection failure, detected by the system. Severe The threshold value should be set greater than the upper limit of the warning threshold. The proprietary status of the UPS device used to detect Blackout utility failures or anomalies. Users can monitor the…
-
Figure 12.40 Authentication Profile
Table 12.38 The authentication profile function description Icon Description Click to add new authentication profile in the table. See Figure 12.41 ~ Figure 12.44 for the detail. Click to delete the selected authentication profile in the table. Click to edit the selected authentication profile in…
-
SNMP default port: 161 Timeout * The timeout (ms) of the data polling. Retry * The number of retries. Is Default Enable to apply the profile to newly added equipment. Figure 12.41 Add an authentication profile Figure 12.42 Select the SNMP V1 78
-
Figure 12.43 Select SNMP V3
Figure 12.44 Select Modbus ❷ ❶ Figure 12.45 Apply the authentication to devices 79
-
12.2.5 Auto-discovery
The Auto-discovery section allows users to search the SNMP devices within the specific IP range by running a Discovery Job (Figure 12.48, Table 12.43). All discovered devices will show in “Unassigned devices” table, click the device in the table and fill in the fields in INFO Panel to add it to the…
-
Click to add the selected unassigned devices to the system
Table 12.41 The discovery job table content description Content Description Discovery job Name * IP/ IP Range * Schedule The name of the discovery job. The IP range of the discovery job. − Y: At least one schedule for the discovery job. − N: No schedule for the discovery job. The latest status of…
-
❶ ❸ ❷ ❺ ❹ Figure 12.47 Add a discovery job ❷ ❶ ❸ Figure 12.48 The steps of running a discovery job Table 12.43 The steps of running a discovery job description Step Description ❶ Select the discovery job. 82
-
Run the discovery job. The “Auto-discovery” window opens, showing the progress bar of the device discovery. The required time of the discovery job depends on the amount of the IP addresses within the IP range. Click “Abort” to stop the discovery (Figure 12.49). Figure 12.49 Abort the discovery 12.3…
-
12.3.1 Generate Template
The Generate Template page allows users to generate the default dashboard templates for all floor maps (Figure 12.51, Table 12.44). ❸ ❶ ❹ ❷ Figure 12.51 Generate Template Table 12.44 The steps of generating template Step Description ❶ Select the floor map in the Floor Map table. ❸ Click “Generate”…
-
Figure 12.52 Dashboard List
Table 12.45 The dashboard list function description Icon Description Click to open the edit window to change the refresh time of the dashboard template (Figure 12.53). Click to delete the selected dashboard template in the table. Click to input the query condition to filter the data in the table.…
-
Table 12.46 The dashboard list content description
Content Description Dashboard Name The dashboard name displayed in the list usually begins with the floor map name followed by the default template name. Refresh Time (s) 12.4 The time interval for the dashboard to update data. Floor Map Setup The Floor Map page displays a list of the floor maps.…
-
Click to delete the selected floor map in the table
Click to input the query condition to filter the data in the table. Click to set the map thresholds for the selected floor map in the table (Figure 12.60, Table 12.50). The parameters set here are used in reports and dashboards to evaluate the PUE and power capacity, and display analysis charts with…
-
❷ ❸ ❺ ❶ ❹ Figure 12.55 The steps of adding a map Table 12.48 The steps of adding a map description Step Description ❶ Enter the basic information of the floor map in the INFO Panel (Table 12.49). ❷ ❸ ❹ ❺ ❻ Upload the background image or the floor plan. The image format must be .PNG or .JPEG files…
-
Select the accounts that are allowed to view this
Share View * floor map and its related information (Figure 12.62). Refresh Time(s) * The time interval for data reload. Figure 12.56 Background Image Upload Figure 12.57 Layout Size Figure 12.58 Drag & drop the deivce (Note: In the list, the device that has been placed in the floor map will turn…
-
Figure 12.59 Remove the device from the floor map
Figure 12.60 Map Setting Table 12.50 Map Setting content description Content Description Rated Power (W) * Power Capacity PUE Set the maximum power rating of the floor map. Normal Range * Set the range of the output power values Warning Range * for "Normal", "Warning" and "Severe" Severe Range *…
-
Warning Range *
"Warning" and "Severe" status. (Note: According to DCOI requirement, for the Environment Severe Range * existing data center, the PUE <= 1.5; for the new Temperature (°C) Set the normal range of the temperature Normal Range * values for the floor map. Humidity (%RH) Set the normal range of the…
-
Table 12.51 The steps of adding a device group
Step Description ❶ Click the floor map. ❸ Click the group to rename the device group. ❷ ❹ Click “Add” to create a “New Group” under the floor map. − Select the device in the right table and add it to the selected device group in the left table. − Select the device in the left table and remove it…
-
Figure 12.63 Power Calculation
Figure 12.64 Import Map 12.5 Alarm The Alarm section allows users to configure the alarm events and the asset reminder for the equipment. When an event occurs, the alarm recipients will be notified via E-mail (Figure 12.65). 93
-
Figure 12.65 Alarm
12.5.1 Delivery The Delivery section allows users to manage the alarm group and the recipients in each alarm group (Figure 12.66). Figure 12.66 Delivery 94
-
Group The Group page displays the list of the alarm group, allowing users to add a new group in the table (Figure 12.67). The “Alarm_Group” is the default group built-in by the system. The function details are described in Table 12.52 and the contents are shown in Table 12.53. Figure 12.67 Group…
-
The description of the group
Receive Trap Alarm Click to receive the SNMP Trap Alert Email. Enable Click to activate the group in the system. Figure 12.68 Add a group Recipient The Recipient page allows users to manage the account list for each alarm group. When an alarm event occurs, all of the accounts in the alarm group…
-
Figure 12.69 Recipient
12.5.2 Equipment Monitoring The Equipment Monitoring section displays the list of all system built-in status alarms, allowing users to assign the status alarms to each equipment category to trigger E-mail notifications when equipment status changes (Figure 12.70). Figure 12.70 Equipment Monitoring…
-
Status Alarm The Status Alarm page displays a list of the alarm rules in the table. The status alarm is the alarm rule that defines the Alarm Type, Monitor Status and the Alarm Group. When the equipment status changes to the monitor status, the status alarm will be triggered and the status alarm…
-
Table 12.55 Status Alarm content description
Content Description Alarm Name The alarm name. Attribute The equipment attribute of the alarm. Monitor Status The status of the alarm. Alarm Group The alarm group to send out the alarm notification. Description The description of the alarm. Figure 12.72 Edit a status alarm Category & Status Alarm…
-
Figure 12.73 Category & Status Alarm
12.5.3 Alarm Center Setup The Alarm Center Setup page allows users to set up alarm event settings for all devices and upload an alert audio file to the system (Figure 12.74). When the system detects alarm events, the alarm banner will appear at the top of the current web page and the alert audio…
-
Figure 12.74 Alarm Center Setup
Figure 12.75 Alarm banner 101
-
Figure 12.76 Alarm Center window
System Alarm The system provides the System Alarms of Low Disk Space Alarm. It is detected by the system automatically. Users can set up the thresholds for system to send out alerts, and the alerts will be sent to all Admin account users. See Low Disk Space Alarm for the details. Equipment Alarm…
-
Figure 12.77 Asset Reminder
Table 12.56 Assets Reminder function description Icon Description Click to edit the selected reminder in the table (Figure 12.78, Table 12.58). Table 12.57 Assets Reminder content description Content Description The reminder type name. Assets Reminder − Warranty expiration date of the equipment −…
-
Figure 12.78 Reminder Setting
Table 12.58 Reminder Setting content description Content Description Click “Yes” to enable the reminder, and the system will run Enable this reminder * the schedule to check the warranty expiration date or replacement date for all equipment. Enter the number of days ahead of the warranty expiration…
-
Figure 12.79 SMTP Server
Table 12.59 The SMTP Server content description Content Description SMTP Server Address * Enter the host name of the SMTP server. Enter the port number. Service Port * (Note: The Service Port 465 is not supported by the system. It’s recommended to set the service port to 25 or 587.) Sender E-mail…
-
12.5.6 Low Disk Space Alarm
The system provides the low disk space alerts to help users monitor the hard disk usage of the PowerPanel Enterprise Server (Figure 12.80, Figure 12.81) and send out the Low Disk Space Alarm E-mail to all Admin accounts (Figure 12.86). User can set the low disk space thresholds through AlertMail’s…
-
Table 12.60 The steps of setting low disk space threshold
Step ❶ Description Log in to your PowerPanel Enterprise Server and find the installation folder of “ PowerPanelEnterprise_AlertMail “ (Figure 12.82). Edit the configuration file of “ PowerPanelEnterprise_AlertMail.exe “ and enter the value of “ LowDiskSpaceThresholdPercent “ to set the free disk…
-
12.5.7 Alarm E-mail
The following pictures (Figure 12.84 ~ Figure 12.86) show the E-mail content of Status Alarm E-mail, Trap Alarm E-mail and Low Disk Space Alarm E-mail. Figure 12.84 Status Alarm E-mail Figure 12.85 Trap Alarm E-mail 108
-
Figure 12.86 Low Disk Space Alarm E-mail
-
Chapter 13 Plugins
The Plugins section provides the system scalability, allowing users to install plugins to support more equipment categories, new dashboard templates and charts. This page displays the list of new plugins in the top window, and the installed plugins in the bottom window. Users can select the new…
-
SmartQuery: Add new analysis charts. − Dashboard: Add new dashboard templates. − Equipment Model: Add new equipment models. System Requirements The supported system version of the plugin. Release Date The release date of the plugin. Installed By The name of the account who installed the plugin.…
-
Chapter 14 System Version
The System Version section displays the current version of the system in the upper right corner of the screen (Figure 14.1). When a new system version is available, the version icon turns green to remind users to upgrade (Figure 14.2). Users can use the Upgrade Tool on the PowerPanel® Enterprise…
-
Figure 14.2 New system version is available
Table 14.1 System Version function description Icon Description The icon indicates your system is up to date. Click to view the detailed information (Figure 14.3). The icon indicates new system version is available. Click to view the detailed information of new version (Figure 14.4). Figure 14.3…
-
Figure 14.4 Upgrade to new system version
Table 14.2 System Version content description Content Description Current Version The current system version of PowerPanel® Enterprise. Last Updated The last time the system was upgraded and upgraded by whom. Last Update Check The last time the system checked for the new version. 114
-
Cyber Power Systems, Inc