Инструкция на Чиллеры с водяным охлаждением Carrier серии 30HXC/30GX
Чиллеры с водяным охлаждением конденсатора с винтовыми компрессорами Carrier серии 30HXC 080-375/30GX 082-358. Инструкции по установке, эксплуатации и техническому обслуживанию.
Загружаем документ…
Текст инструкции
-
30HXC 080-375
30GX 082-358 Screw Compressor Water-Cooled Liquid Chillers and Air-Cooled Liquid Chillers 30HXC Nominal cooling capacity 290-1325 kW 30GX Nominal cooling capacity 285-1205 kW 50 Hz GLOBAL CHILLER Installation, operation and maintenance instructions
-
The cover photograph is for illustrative purposes only and is not part of any offer for sale or contract.
-
1 - INTRODUCTION
Prior to initial start-up of the 30HXC and 30GX unit, those involved in the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data. This book provides an overview so that you may become familiar with the control system before…
-
3 - DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION
600 3.1 - 30HXC 080-190 30HXC080 30HXC090 30HXC100 30HXC110 C E A 500 D 3 1 Evaporator 2 Condenser 3 Clearances required for operation and maintenance 4 Clearances required for heat exchanger tube removal. Clearances D and E can be either on the left or on the right hand side. Water inlet Water…
-
3 - DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)
600 3.2 - 30HXC 200-375 C 3 D 1 Evaporator 2 Condenser 3 Clearances required for operation and maintenance E A Clearances required for heat exchanger tube removal. Clearances D and E can be either on the left or on the right hand side. Water inlet 4 Water outlet B 4 Power supply 700 kg: total…
-
3 - DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)
3.3 - 30GX 082-182 Clearances required for operation and maintenance 2 Clearances required for evaporator tube removal. Clearances can be either on the left or on the right hand side. 2287 1 Water inlet Water outlet 30GX-082 30GX-092 30GX-102 30GX-112 30GX-122 30GX-132 30GX-152 30GX-162 30GX-182…
-
DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.) 3.4 - 30GX 207-358 Clearances required for operation and maintenance 2 Clearances required for evaporator tube removal. Clearances can be either on the left or on the right hand side. 2287 1 Water inlet Water outlet 30GX-207 30GX-227 30GX-247…
-
4 - PHYSICAL DATA 30HXC
30HXC 1119 1222 1326 kg 2447 2462 2504 2650 2846 2861 2956 2971 3283 3438 4090 4705 4815 4985 5760 5870 6105 kg HFC-134a 39/36 39/36 37/32 38/38 57/55 59/50 56/50 59/52 58/61 60/70 110/58 118/63 120/75 120/75 108/110 110/110 110/120 l Polyolester oil CARRIER SPEC: PP 47-32 15/15 15/15 15/15 15/15…
-
Compressors
Reference Size I nom. MHA LRA LRA (Y) LRA (S) 1 cp. LRA (S) 2 cp. 06NW2146S7N 06NW2174S7N 06NW2209S7N 06NW2250S7N 06NW2300S5N 06NW2300S5E 80+ Legend: 06NW N E INOM MHA LRA LRA (Y) LRA (S) 1 cp. LRA (S) 2 cp. 10 - Compressor for water-cooled units - Non-economized compressor - Economized compressor…
-
6 - ELECTRICAL DATA FOR UNITS WITH HIGH CONDENSING TEMPERATURES
30HXC 150 and 150A Options 30HXC Power circuit Nominal power supply (Un) Voltage range V-ph-Hz 400-3-50 V 360-440 Control circuit supply The control circuit is supplied via the factory-installed transformer Max. power input** Circuit A Circuit B kW kW kW 104 - 117 - 131 - 145 - 159 - 174 - 194 - 211…
-
7 - PHYSICAL DATA 30GX
30GX Net cooling capacity* kW 1003 1103 1207 Operating weight kg 3116 3157 3172 3515 3531 3633 3920 3936 4853 5540 5570 6134 6365 7354 7918 8124 kg HFC-134a 55/55 58/50 54/53 55/53 60/57 63/60 75/69 75/75 80/80 130/85 130/85 155/98 170/104 162/150 162/165 175/175 l Polyolester oil CARRIER SPEC: PP…
-
Compressors
Reference Size I nom. MHA LRA LRA (Y) LRA (S) 1 cp. LRA (S) 2 cp. 06NA2146S7N 06NA2174S7N 06NA2209S7N 06NA2250S7N 06NA2300S5N 06NA2300S5E 80+ 1226 1265 Legend: 06NA N E INOM MHA LRA LRA (Y) LRA (S) 1 cp. LRA (S) 2 cp. - Compressor for air-cooled units - Non-economized compressor - Economized…
-
9.4 - Variable flow evaporator
9.6 - Cooler flow rate (l/s) Variable evaporator flow can be used in standard 30HXC and 30GX chillers. The chillers maintain a constant leaving water temperature under all flow conditions. For this to happen, the minimum flow rate must be higher than the minimum flow given in the table of…
-
Pressure drop, kPa
-
Pressure drop, kPa
9.9 - Condenser pressure drop curve Water flow rate, l/s 30HXC 080-090-100-110 30HXC 200 30HXC 120-130 30HXC 230-260-285 30HXC 140-155 30HXC 310-345-375 30HXC 175-190 16
-
9.10 - Flow controllers
10 - INSTALLATION 9.10.1 - Cooler flow switch and chilled water pump interlock 10.1 - Check equipment received IMPORTANT It is mandatory to install cooler flow switch and also to connect chilled water pump interlock on 30HXC and 30GX. Failure to this instruction will void Carrier guarantee. The…
-
11 - LIFTING INSTRUCTIONS
-
11.2 - 30HXC 200-285
This diagram is shown for information only. Refer to “certified drawings”. 2800 mm min. 1035 1200 mm min. 425 2075 36 39 Ø 13.5 11.3 - 30HXC 310-375 3500 mm min. Z 1200 mm min. Y X mm Y mm Z mm 2195 2195 2205 1085 1085 1025 36 Ø 13.5 39 30HXC310 30HXC345 30HXC375 X NOTE When all lifting and…
-
11.4 - 30GX 082-162
-
11.6 - 30GX 207-267
-
11.8 - Piping connections
Refer to the certified dimensional drawings for the sizes and positions of all water inlet and outlet connections. The water pipes must not transmit any radial or axial force to the heat exchangers or any vibration to the pipework or building. The water supply must be analysed and appropriate…
-
12 - ELECTRICAL CHARACTERISTICS
• • • • • The 30HXC 080-190 and 30GX 082-182 have only one power disconnect/isolating switch. The 30HXC 200-375 and 30GX 207-358 have two power disconnect/isolating switches. The control box incorporates the following as standard: - Starters and motor protection devices for each compressor and the…
-
13 - RECOMMENDED WIRE SECTIONS
-
IMPORTANT
Before connection of the main power cables (L1 - L2 - L3) on the terminal block, it is imperative to check the correct order of the 3 phases before proceeding to the connection on then terminal block or the main disconnect/isolator switch. 13.1 - Field control wiring Refer to the Controls IOM and…
-
14 - MAJOR SYSTEM COMPONENTS AND
OPERATION DATA 14.1 - Geared twin screw compressor • 30HXC and 30GX units use 06N geared twin screw compressors • 06NA are used on 30GX (air-cooled condensing application) • 06NW are used on 30HXC (water-cooled condensing application) • Nominal capacities range from 39 to 80 tons. Economized or non…
-
desired liquid level in the cooler (as is done for NonEconomized chillers). The float valve maintains a liquid level in the bottom of the economizer. Liquid refrigerant is supplied from the condenser to the bottom of the economizer. As the refrigerant passes through the EXV, its pressure is reduced…
-
14.11 - 30GX fan arrangement
-
15 - MAINTENANCE
15.1 - Refrigerant charging - adding charge IMPORTANT These units are designed for use with R-134a only. DO NOT USE ANY OTHER refrigerant in these units. CAUTION When adding or removing charge, circulate water through the condenser (HX) and cooler at all times to prevent freezing. Freezing damage is…
-
15.3 - Pressure transducers
15.3.1 - Discharge pressure (circuits A & B) This input is used to measure the high side pressure of each circuit of the unit. It is used to provide the pressure to replace the discharge pressure gauge and to control the head pressure. 15.3.2 - Suction pressure (circuits A & B) This input is used to…
-
To minimize the opportunity for reverse rotation, the following
procedure must be applied. Rewire the power cables to the compressor terminal pin as originally wired. For replacement of the compressor, a low pressure switch is included with the compressor. This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the…
-
Check condenser system (30HXC)
All condenser water valves are open All condenser piping is connected properly All air has been vented from the system Condenser water pump (CWP) is operating with the correct rotation. Condenser water pump amperage: Rated: Actual……… Unit start-up CWP starter has been properly interlocked with the…
-
Check pressure drop across the condenser (30HXC only)
Entering condenser = (kPa) Leaving condenser = (kPa) (Leaving - entering) = (kPa) WARNING Plot condenser pressure drop on performance data chart (in product data literature) to determine total liters per second (l/s) and find unit's minimum flow rate. Total l/s = l/s / nominal kW = Total l/s is…
-
Order No: 13173-76, 03 1999 - Supersedes No: 13173-76, March 1998
Manufacturer reserves the right to change any product specifications without notice. Manufacturer: Carrier s.a., Montluel, France. Printed in the Netherlands on chlorine-free paper.