38CKM --- 50 Hz
Split System Air Conditioner with Puron Refrigerant 1---1/2 to 5 Tons Installation Instructions SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury…
-
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues. Locate unit away from fresh air intakes, vents, or bedroom windows. Noise may carry into the openings and disturb people inside. Locate unit in a well drained area, or support unit high enough so that water…
-
MAKE REFRIGERANT TUBING CONNECTIONS
Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant--grade tubing of correct size and condition. For tubing requirements beyond 80 ft (24.38 m), consult Residential Split System Long--Line Application Guideline. Connect tubing to fittings on…
-
4. Set room thermostat at desired temperature. Be sure set
point is below indoor ambient temperature. 5. Set room thermostat to COOL and fan control to ON or AUTO mode. Operate unit for 15 minutes. Check system-refrigerant charge. (See Check Charge.) ! WARNING PERSONAL INJURY and ENVIRONMENTAL HAZARD Failure to relieve system pressure could result in…
-
7. If a unit has lower subcooling than charted subcooling, add
refrigerant until charted subcooling is reached. 8. If unit has a higher subcooling than charted subcooling, reclaim refrigerant until charted subcooling is reached. 9. When adding refrigerant, charge in liquid form into suction service port using a flow--restricting device. 10. If outdoor air…
-
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your servicing contractor or Owner’s Manual for proper frequency of maintenance. Frequency of maintenance may vary depending upon geographic…
-
Printed in Mexico Edition Date: 11/17 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 10 Catalog No: 38CKM---X ---Q---01SI Replaces: New