pCOWeb for the pCO controllers
PRELIMINARY Manuale d’uso User manual
-
We wish to save you time and money!
We can assure you that the thorough reading of this manual will guarantee correct installation and safe use of the product described Carel code ?????????? rel. 1.0 dated ???????? 2
-
OVERVIEW - 5 HARDWARE INSTALLATION 5 PCOWEB ADMINISTRATION - 5 DEFAULT WEB PAGE - 5 WEB ADMINISTRATOR PAGE - 6 View used/free flashdisk space: 7 Set directory password: 7 Adjust files and directories attributes access: 7 Flush disk cache: - 7 Backup / Upload flash images: - 8 Format flashdisk: 8…
-
Submit Button: - 22 PCO* TO BACNET DATABASE - 22 SUPPORTED BACNET OBJECTS - 23 BIBB SUPPORT - 25 OBJECT SUPPORT OF INTRINSIC ALARMING - 25 - Carel code ?????????? rel. 1.0 dated ???????? 4
-
Overview
The pCOWEB interface card was designed to provide the pco* controller family connectivity to four increasingly used protocols: HTTP SERVER, FTP, SNMP, and BACNET. The card provides a “gateway” connection between the communicated variables from the controller allowing all 199 digital, 127 integer and…
-
This is the default index.html page. It provides you with a link to the administrator
reserved area and displays the current values of all variables that are being read from the controller. This file is stored in usr/local/root/flash/http/ and is also the folder where your custom html files will be stored. Web Administrator Page -6-
-
The adminpage.html gives some useful configuration features
View used/free flashdisk space: Check for the amount of free writable space inside the FLASH memory. Set directory password: Useful to set/change the logins to access the directory in the writable area of the FLASH. Adjust files and directories attributes access: Needed to set the properties of the…
-
loss or corruption if pCOWeb is powered down before the saving in FLASH. This button
lets you to force the save. Backup / Upload flash images: These two items lets you to download an exact copy of the flashdisk to your PC and later to upload again into a pCOWeb. The previous contents of the target pCOWeb flaskdisk will be lost. Note that the flashdisk contains also all the user…
-
To administer the web pages you can use any FTP client, for the following examples we
will use SmartFTP (free) to explore the directory tree of pCOWeb. The user name and password for web administration is: username: password: httpadmin fhttpadmin Note – Changing Passwords: The password can be changed by accessing the pCOWeb html configuration pages. The factory password is simply “f”…
-
The /flash/http directory is the right place to store your html pages and/or directories. The
/flash/http/index.html is the default page that will be served out when you type http://<pCOWeb IP address or name to be resolved by a DNS>[Enter] into a browser. If you need to build some CGI scripts, the right place for those files is: /flash/usr-cgi/. If you put them in a place other than that…
-
<%var(0,1,1)%>
The var tag initiates a polling routine in the pcoWeb. PCOWEB BACNET PROTOCOL FOR PCO2 All tags must be opened and closed with these delimiters. This follows the standard ASP convention. They are necessary for the parser to distinguish pcoWeb code from HTML. For the var tag, these three variables…
-
name=”?script:var(unit,type,index,lo-range,hi-range)”
The Unit ID. Usually zero. Variable type. • 1 = digital • 2 = analogue • 3 = integer The physical index of the variable. The lower range of the variable. • 0 = digital • -10000.0 = analogue • -100000 = integer The upper range of the variable. • 1 = digital • 10000.0 = analogue • 100000 = integer FTP…
-
After configuring the FTP Push setup for your pcoWeb, your screen will look similar to this
You must then power down the unit for the FTP routine to work. It will begin automatically when the unit powers up. - 13 -
-
SNMP PROTOCOL
SNMP TREE for pCOWeb (from the release A1.0.1 – B1.0.0) General OID format: 1.3.6.1.4.1.9839(Carel).A.B[.C.D.[E]] A.B.C.D.E explanation A=1: pCOWeb properties 1.1= AgentRelease (ReadOnly) = A1.0.1 – B1.0.0 pCOWeb sw release 1.2= AgentCode (ReadOnly) = “pCOWeb” A=2: pCO properties 2.0.10 = pCOStatus…
-
pCOWeb is able to send two types of trap: system traps and controller traps
SYSTEM TRAPS To set these traps you have to click onto the link “SNMP System defaults configurations” of the Web Administrator page. Note: all the settings in this page will be active from the next reboot of pCOWeb. Default traps Default trap community The “Community” in SNMP standard is a string…
-
Note – Two Submit Buttons: the page is divided into two half pages (top / down). Each of
these has its own “Submit” button; please note that a “Submit” button will confirm ONLY the parameters/selections of the related half page, with no effect to those of the other half page. Let’s examine the page. Top Half of Trap setup Page The top zone of the top half page is devoted to the settings…
-
Community: the “Community” in SNMP standard is a string useful to filter the access from
a host toward pCOWeb: if the community string of the host is not the same of that of pCOWeb, the access will be denied (it is then somewhat similar to a password). Enabling flag: when this flag is set to “No”, it overrides the settings of the rest of the html page: no controller TRAPS will be sent…
-
same trap one more time, and then it will start waiting for the Acknowledge. This
mechanism will stop as soon as pCOWeb will get the Acknowledge, or after a maximum of 5 further traps after the first sending. Bottom Half of Trap Setup Page This half page lets you to configure the traps related to state changes of each digital variable of the pCO* controller. Variable: 1 ↓SELECT…
-
variables. Until the acquisition you will read “U” (undefined) as the result of a read of a not
acquired variable. You can realize a slow refresh by checking the “status” led in pCOWeb: slow or no blinking means slow or no refresh. Trap OID Trap Object Identifier (a sort of name of the trap). This information will be embedded inside the message when the TRAP SNMP message is formatted before…
-
BACNET PROTOCOL
The BACnet protocol is the ASHRAE building automation and control networking protocol that provides a mechanism by which computerized equipment can exchange information regardless of the particular building function they perform. The pcoweb provides Carel pCO* controllers with a gateway to the…
-
Device Properties
1. BACnet LAN Type: select the protocol to use BACnet/IP or BACnet Ethernet. 2. BACnetIP UDP: if BACnetIP is used then a UDP port must be assigned, the default port for BACnet is “BAC0” hexadecimal. 3. pCOWeb Device Instance: This is the device instance of the pCOWeb on the network. It defaults to…
-
4. Description: A 64 character field that can be used to describe the device
5. Location: A 64 character field that can be used to describe the physical location. 6. APDU Timeout: Indicates the amount of time in milliseconds between retransmission of an APDU requiring acknowledgement for which no acknowledgement has been received. The default setting of this property is…
-
Analog variables are mapped to BACnet Analog Value object type with an instance
number equal to their variable number, e.g. analog variable 17 would appear to be BACnet Analog Value 17. Because analog variables are implicitly scaled "times 10" their conversion to REAL in BACnet is scaled accordingly. So the value "123" which is taken to mean "12.3" is converted to a floating…
-
o
o o o o o o o o o o PCOWEB BACNET PROTOCOL FOR PCO2 Active_Text writable, default to "1" Time_Delay writable Alarm_Value writable (BV only) High_Limit writable (AV only) Low_Limit writable (AV only) Deadband writable (AV only) writable (AV only) Limit_Enable Event_Enable writable Acked_Transitions…
-
BIBB Support
The pCOWeb supports the following specific BIBBs per their relevant definitions in Addenda D/Annex K to BACnet: DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B i.e. act as a server that can execute Read/Write single or multiple properties DM-DDB-B, DM-DOB-B i.e. dynamic device and object binding. Support…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Новая версия программного обеспечения для pCOWeb. Пресс-релиз.PDF · 217.28 Kb
- Разработка html-страниц для pCOWeb. Руководство по эксплуатации.PDF · 127.71 Kb
- PCOWeb - поддержка BACnet. Руководство по эксплуатации.PDF · 40.50 Kb
- Руководство по эксплуатации PCOWeb системы TRAPS (система ловушки). С помощью ловушек pCOWeb может отправлять предупреждения к SNMPPDF · 50.21 Kb
- Руководство по эксплуатации PCO1000W*0 - pCOWeb. Ethernet интерфейса для pCO*PDF · 271.02 Kb
- Руководство по эксплуатации новых смарт-карт PCOWeb для контроллеров рСОPDF · 163.14 Kb