Инструкция на Чиллеры SLS с воздушным охлаждением
Модели SLS 1402-8404. Чиллеры SLS с воздушным охлаждением. Руководство по монтажу и эксплуатации.
Смотрите также: Техническая брошюра →
Загружаем документ…
Текст инструкции
-
Installation and maintenance manual
SLS 1402 ÷ 8404 English 293 1646 kW Air cooled chillers with screw compressors IOM SLS134-N.2GB Date : July 2007 Supersedes : IOM SLS134-N.1GB/11.05
-
Pagina 1 English Table of contents Table of contents 1 FOREWORD 1.1 1.2 1.3 1.4 Introduction Warranty Emergency stop/Normal stop An introduction to the manual 7 GENERAL DESCRIPTION SAFETY 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 Foreword Definitions Access to the unit General precautions Precautions against…
-
Pagina 2 Foreword 1 FOREWORD 1.1 Introduction Itelco-Industry units, manufactured to state-of-the-art design and implementation standards, ensure top performance, reliability and fitness to any type of airconditioning systems. These units are designed for cooling water or glycoled water (and for…
-
Pagina 3 2 SAFETY 2.1 Foreword These units must be installed in conformity with the provisions of Machinery Directive 98/37/EC, Low Voltage Directive 73/23/EC, Pressure Vessels Directive 97/23/EC, Electromagnetic Interference Directive 89/336/EC, as well as with other regulations applicable in the…
-
Pagina 4 Safety control operations expressly described in this manual, that must be strictly complied with, without exceeding the scope of the tasks entrusted to him. I use tools in a good state of repair; be sure to have ENGINEER: means a person authorised directly by Itelco-Industry or, in all EC…
-
Pagina 5 I check all the electrical connections, the connecting cables, and in particular the insulation; replace worn or damaged cables I periodically check the board’s internal wiring I do not use cables having an inadequate section or flying connections, even for limited periods of time or in an…
-
Pagina 6 Safety 2.7 Safety labels KEEP LIFT HOOK ON THIS LINE TENERE SU QUESTA LINEA GANCIO DI SOLLEVAMENTO The labels below will be affixed to each unit in the indicated point: Gravity centre - Base Identification of the refrigerant External door Electrical warning Adjacent to the master switch…
-
Pagina 7 INSERIRE LE RESISTENZE DI RISCALDAMENTO OLIO ALMENO 12 ORE PRIMA DI OGNI AVVIAMENTO (SE PREVISTE). 881000215/B ATTENZIONE English Safety PRIMA DELLA MESSA IN TENSIONE ASSICURARSI CHE LE VITI DEI CIRCUITI ELETTRICI SIANO SERRATE COMPLETAMENTE. WARNING ENERGIZE THE CRANCKCASE HEATER FOR AT…
-
Pagina 8 Safety 2.8 Safety regulations Refrigerant data Safety data: R134a Toxicity Low Contact with skin If sprayed, the refrigerant is likely to cause frost burns. If absorbed by the skin, the danger is very limited; it may cause a slight irritation, and the liquid is degreasing. Unfreeze the…
-
Pagina 9 English Safety General precautions Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the professional threshold. Being more weighty than the air, the vapour concentrates on the bottom, in…
-
Pagina 10 Safety Lubricant oil data Safety data: Polyester oil (POE) Classification Not harmful Contact with skin May cause slight irritation. Does not require first aid measures. It is recommended to follow usual personal hygiene measures, including washing the exposed skin with soap and water…
-
Pagina 11 3 TRANSPORT, LIFTING AND POSITIONING Refrigerators are supplied assembled (apart from standard antivibrating rubber supports, that will be installed on site). The equipment are full of refrigerant and oil, in the quantity required for a proper operation. It is recommended to use a spacer…
-
Pagina 12 Transport, Lifting and Positioning Before positioning the unit, make sure that the place of installation is appropriate and sturdy enough to hold the weight and to withstand the stress caused by the operation of the whole assembly. Do not displace the unit on rollers, and do not lift it…
-
Pagina 13 4 INSTALLATION 4.1 Positioning of the unit Before installing the unit, make sure that the structure of the building and/or the supporting surface can withstand the weight of the appliance. The weights of the units are listed in Chapter 8 of this manual. English Installation 4.2 Spring…
-
Pagina 14 Installation The capacity of the expansion vessel must allow for an expansion of at least 2% of the volume of the fluid in the circuit (evaporator, piping, user circuit and standby tank, if any). The expansion vessel needs not be isolated, because no water can circulate inside it. I A flow…
-
Pagina 15 English Installation Then: I Provide the evaporator with a by-pass circuit equipped with a valve to wash the plant. I Insulate the piping, to prevent the risk of heat loss. I Position a filter on the suction side of the evaporator of the heat recovery condenser. Flow Switch Installation…
-
Pagina 16 Installation 4.6 Power supply Before carrying out any operations on the electrical system, make sure that the unit is deenergised. It is important that the appliance is grounded. The company in charge of the installation shall conform to the standards applicable to outdoor electrical…
-
Pagina 17 English Installation Terminal box - SLS QG - Y1 REMOTE START/STOP SWITCH (SRS) 01 01 (COMMON) 02 02 REMOTE SUMMER/WINTER SWITCH (ONLY HP) (SRHP) 03 03 PHASE VOLTAGE CONTROL (ACCESSORY) (SQZ) DOUBLE SET-POINT (DAY/NIGHT) (SDN) FLOW SWITCH (SF) EXTERNAL INTERLOK (OPTIONAL) CIRC PUMP LOAD…
-
Pagina 18 Installation Terminal box - SLS-R QG - Y1 REMOTE START/STOP SWITCH (SRS) (COMMON) PHASE VOLTAGE CONTROL (ACCESSORY) (SQZ) DOUBLE SET-POINT (DAY/NIGHT) (SDN) FLOW SWITCH (SF) EXTERNAL INTERLOCK (OPTIONAL) CIRC PUMP ETC EXTERNAL INTERLOCK HEAT RECOVERY (1-SLS/OFF) LOAD SHEDDING REMOTE…
-
Pagina 19 English Installation 4.8 Connecting the temperature sen sor of coupled units’ manifold (SLS at 4 circuits) For the SLS units at 4 circuits the two heat exchangers (of shell and tube type) must be connected in parallel through a manifold (to be provided by the customer). The supplied…
-
Pagina 20 Start-up 5 START-UP The unit must be started for the first time by personnel suitably trained by one of ItelcoIndustry’s Authorised Service Centre. Failure to meet this requirement will immediately void the warranty. The operations carried out by Itelco-Industry personnel are limited to…
-
Pagina 21 English Start-up 5.3 Checking the operation Check the following: I The temperature of the water entering the evaporator. I The temperature of the water leaving the evaporator. I The level of the water flow rate in the evaporator, if possible. I The current absorption upon the start of the…
-
Pagina 22 Operation 6 OPERATION The units SLS are equipped with a microprocessor control logic and regulation management system. The system consists of a unit logic board and a liquid crystal control panel which manages the control, starting, shutdown and display functions. 6.1 General Informations…
-
Pagina 23 The connection between the terminal unit and the board is realized by a 6 ways phone cable. The connection between the terminal unit and the main board is not strictly necessary to the normal operation of the controller. menu I/O ? info on-off menu set alarm prog enter Access to the…
-
Pagina 24 Operation 6.3 Functions / Keys / Configurations I Alarms table Code Alarm Description Comp 1 Comp 2 Fan #1 Fan #2 Pump Status Status Status Status Status Notes AL00 Compressor stop Due to auto-reset alarm. Just stored into the historical AL01 Wrong power Off Off AL02 Antifreeze alarm Off…
-
Pagina 26 Operation HOUR_THRES Maintenance alarm threshod 003X1000h I Setpoint Pushing the “Set” key it is possible to access to user’s Setpoint level. The following table contains the details of the parameters which is possible to set with the relevant limitations and default values: User’s…
-
Pagina 27 7 English General Description GENERAL DESCRIPTION 7.1 Introduction The SLS units are water chillers/air-water heat pumps with screw compressors provided with two or four refrigeration circuits. These units are fit for cooling and heating water or intermediate fluids (glycoled water) for…
-
Pagina 28 General Description 7.5 Water heat exchanger Evaporator Desuperheater All SLS R134a units have a “Shell & Tube” water heat exchanger with direct expansion multi refrigerant circuits. The tube bundle can be removed for inspection or maintenance. All units are available with desuperheaters…
-
Pagina 29 Total heat recovery condenser 7.6 Air heat exchanger All units are available with total heat recovery condenser (THRC). THRC is refrigerant / water heat exchanger shell and tube type, according to chiller size. THRC is fitted on the compressor discharge pipe in parallel with the standard…
-
Pagina 30 General Description 7.8 Power supply and control system All units are provided with a microprocessor and a “Chiller Control” system. The electrical connection of the controls and the startup units for the motor are carried out and tested in the factory. The power supply and control…
-
Pagina 31 8 English Technical data TECHNICAL DATA 8.1 Pressure drops Evaporator SLS STD K 10 kPa/(l/s)^2) Min. water flow rate l/s Nominal water flow rate l/s Max. water flow rate l/s Min. pressure drops kPa Nominal pressure drops kPa Max. pressure drops kPa 1402 141,4 8,7 14,0 23,3 10,8 27,7 77,0…
-
Pagina 32 Technical data Desuperheater SLS STD K 10 kPa/(l/s)^2) Min. water flow rate l/s Nominal water flow rate l/s Max. water flow rate l/s Min. pressure drops kPa Nominal pressure drops kPa Max. pressure drops kPa 1402 2027,4 1,0 1,7 2,6 2,0 5,6 14,2 1602 2027,4 1,1 1,9 3,0 2,5 7,1 18,1 1802…
-
Pagina 33 Evaporator SLS HE K 10 kPa/(l/s)^2) Min. water flow rate l/s Nominal water flow rate l/s Max. water flow rate l/s Min. pressure drops kPa Nominal pressure drops kPa Max. pressure drops kPa 1402 141,4 9,1 14,5 24,2 11,7 29,8 82,9 1602 141,4 10,1 16,1 26,9 14,4 36,9 102,4 1802 65,9 11,3 18,1…
-
Pagina 34 Technical data Desuperheater SLS HE K 10 kPa/(l/s)^2) Min. water flow rate l/s Nominal water flow rate l/s Max. water flow rate l/s Min. pressure drops kPa Nominal pressure drops kPa Max. pressure drops kPa 1402 2095,8 1,0 1,7 2,8 2,3 5,9 16,4 1602 2095,8 1,2 1,9 3,2 3,0 7,6 21,0 1802…
-
Pagina 35 8.2 Technical data SLS STD-BLN/STD-LN/STD-ELN Nominal voltage 1602 1802 1902 2002 V/ph/Hz Number of circuits Number of steps Capacity steps 1402 % 2202 2502 2702 3002 3202 3402 3602 400-3-50 Refrigerant Type Charge (1) R134a kg 39+39 43+43 50+50 54+54 58+58 59+59 61+61 64+64 68+68 71+71…
-
Pagina 36 Technical data SLS STD-BLN/STD-LN/STD-ELN Nominal voltage 4602 4802 5004 5404 V/ph/Hz Number of circuits Number of steps Capacity steps 4202 % 5704 6004 6404 6804 7204 8404 400-3-50 Refrigerant Type Charge (1) R134a kg 86+86 95+95 100+100 61+61/ 64+64/ 64+64/ 68+68/ 71+71/ 74+74/ 78+78/…
-
Pagina 37 SLS-R STD-BLN/STD-STD-LN/STD-ELN Nominal voltage 1602 1802 1902 V/ph/Hz Number of circuits Number of steps Capacity steps 1402 % 2002 2202 2502 2702 400/3/50 58+58 59+59 61+61 64+64 Refrigerant Type Charge (1) R134a kg 39+39 43+43 50+50 54+54 Compressors Type Screw Number Start-up type 2…
-
Pagina 38 Technical data SLS-R STD-BLN/STD-STD-LN/STD-ELN Nominal voltage 3202 3402 3602 V/ph/Hz Number of circuits Number of steps Capacity steps 3002 % 4202 4602 4802 400/3/50 86+86 95+95 100+100 Refrigerant Type Charge (1) R134a kg 68+68 71+71 74+74 78+78 Compressors Type Screw Number Start-up…
-
Pagina 39 SLS HE-BLN/HE-LN/HE-ELN Nominal voltage 1602 1802 1902 2002 V/ph/Hz Number of circuits Number of steps Capacity steps 1402 % 2402 2602 2802 3002 3202 3402 3602 400-3-50 Refrigerant Type Charge (1) R134a kg 40+40 45+45 51+51 56+56 64+64 73+73 75+75 78+78 82+82 87+87 92+92 97+97 Compressors…
-
Pagina 40 Technical data SLS HE-BLN/HE-LN/HE-ELN Nominal voltage 4602 4802 4804 5204 V/ph/Hz Number of circuits Number of steps Capacity steps 4202 % 5604 6004 6404 6804 7204 7804 8404 400-3-50 Refrigerant Type Charge (1) R134a kg 103+103 105+105 108+108 73+73/ 75+75/ 78+78/ 82+82/ 87+87/ 90+90/…
-
Pagina 41 SLS-R HE-BLN/HE-LN/HE-ELN Nominal voltage 1602 1802 1902 V/ph/Hz Number of circuits Number of steps Capacity steps 1402 % 2002 2402 2602 2802 400/3/50 64+64 73+73 75+75 78+78 Refrigerant Type Charge (1) R134a kg 40+40 45+45 51+51 56+56 Compressors Type Screw Number Start-up type 2…
-
Pagina 42 Technical data SLS-R HE-BLN/HE-LN/HE-ELN Nominal voltage 3202 3402 3602 V/ph/Hz Number of circuits Number of steps Capacity steps 3002 % 4202 4602 4802 400/3/50 Refrigerant Type Charge (1) R134a kg 82+82 87+87 92+92 97+97 103+103 105+105 108+108 Compressors Type Screw Number 2 Start-up…
-
Pagina 43 8.3 Electrical data - Standard Unit SLS STD-BLN Nominal voltage 1402 1602 1802 V(%)-ph-Hz 1902 2002 2202 2502 2702 ±10% / 3 / 50 Nominal power input kW 156 174 Max power input kW Nominal current A Max. current (FLA) A Max. start-up current (LRA) A External fuses (A) Wire cross area (1) mm2…
-
Pagina 44 Technical data Electrical data - Standard Unit SLS STD-LN / STD-ELN Nominal voltage 1402 1602 1802 V(%)-ph-Hz 1902 2002 2202 2502 2702 ±10% / 3 / 50 Nominal power input kW 151 168 Max power input kW Nominal current A Max. current (FLA) A Max. start-up current (LRA) A External fuses (A)…
-
Pagina 45 Electrical data - High Efficiency Unit SLS HE-BLN Nominal voltage 1402 1602 1802 V(%)-ph-Hz 1902 2002 2402 2602 2802 ±10% / 3 / 50 Nominal power input kW 158 174 Max power input kW Nominal current A Max. current (FLA) A Max. start-up current (LRA) A External fuses (A) Wire cross area (1)…
-
Pagina 49 English Technical data Electrical data - Fans Fans SLS STD BLN Power supply 1402 1602 1802 1902 V-ph-Hz 2002 2202 2502 2702 3002 3202 3402 3602 400 ± 10% / 3/ 50 Number n° Rated power per fan kW Max. absorbed current per fan A 4202 4602 4802 5004 5404 5704 6004 6404 6804 7204 8404 Fans SLS…
-
Pagina 50 Technical data 8.4 Position of antivibration mounting springs and weight distribution on supports SLS, SLS-R 1402-2702 STD-BLN / STD-LN / STD-ELN SLS, SLS-R 1402-1902 HE-BLN / HE-LN / HE ELN SLS, SLS-R 3002-4202 STD-BLN / STD-LN / STD-ELN SLS, SLS-R 2002-13002 HE-BLN / HE-LN / HE ELN…
-
Pagina 51 English Technical data SLS 5704 STD-BLN / STD-LN / STD-ELN SLS 6004-8404 STD-BLN / STD-LN / STD-ELN SLS 4804-8404 HE-BLN / HE-LN / HE ELN ELECTRICAL BOARD ELECTRICAL BOARD COMPRESSORS SIDE COMPRESSORS SIDE P1-P14 - Unit supporting points P1-P16 - Unit supporting points Page 51
-
POSITION
-
Page 58
-
Pagina 63 English Technical data SLS-R R134a Versions STD 1402-1802 - SLS-R R134a Versions 1402-1802 UNIT A 1402 1602 1802 1250 UNIT A 1402 1602 1802 1250 B SLS-R R134a STD Version Evaporator Condenser Inlet Outlet Inlet Outlet C D water water water water N° FAN 410 2250 80 DN125 450 2200 160 DN150…
-
Pagina 64 Technical data SLS-R R134a Versions STD 1902-2702 - SLS-R R134a Version HE 1902 UNIT 1902 2002 2202 2502 2702 A B SLS-R R134a STD Version Evaporator Condenser Inlet Outlet Inlet Outlet C D water water water water N° FAN 7 1250 450 2200 160 DN150 G3 8 UNIT A B SLS-R R134a HE Version…
-
Pagina 65 English Technical data SLS-R R134a Versions HE 2002-3002 UNIT 2002 2402 2602 2802 3002 A B SLS-R R134a HE Version Evaporator Condenser Inlet Outlet Inlet Outlet C D water water water water N° FAN 8 2200 1250 450 160 DN150 245 DN200 2700 465 2630 G3 10 12 OUTLET WATER INLET WATER INLET…
-
Pagina 66 Technical data SLS-R R134a Versions STD 3002-4202 UNIT 3002 3202 3402 3602 4202 A B 450 1250 467 SLS-R R134a STDVersion Evaporator Condenser Inlet Outlet Inlet Outlet C D water water water water N° FAN DN150 2700 160 3200 195 500 OUTLET WATER INLET WATER INLET WATER OUTLET WATER Page 66…
-
Pagina 69 MAINTENANCE Scheduled Maintenance Do not throw away the waste oil of the compressor, because it contains refrigerant in solution. The waste oil must be returned to the manufacturer. Check the temperature of the leaving fluid • Check for electric absorption • Check suction pressure tand…
-
Pagina 70 Maintenance 9.3 Refrigerant charge Do not inject refrigerant liquid into the LP side of the circuit. Be ver y careful, and charge the circuit properly. If the charge is insufficient, the efficiency of the unit will be lower than expected. In the worst of cases the LP pressure switch may be…
-
Pagina 71 9.6 Fans The fans of the condenser, of axial type, are complete with impeller with aerodynamic profile blades and a cylindrical nozzle. The motor’s bearings are lubricated forever. Before starting the appliance, after any maintenance operations involving the disconnection of 3-phase…
-
Pagina 72 Troubleshooting 10 TROUBLESHOOTING The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or not listed, contact one of Itelco-Industry’s Service Centre for technical assistance. Anomaly Cause Operation…
-
Pagina 73 Anomaly Cause Operation One or both compressors are not working. Breaking of the electric circuit. Check the electric circuit and detect any ground dispersions and short circuits. Check fuses. Intervention of the HP pressure switch. Reset the pressure switch and the control panel and…
-
Pagina 74 Spare parts 11 SPARE PARTS 11.1 Spare part list The table below shows the list of spare parts recommended during the first two years of operation. Component HP pressure switch Gas filter Thermostatic valve Auxiliary relays Fan’s fuses Compressor’s fuses Auxiliary fuses Set of compressor…
-
Pagina 75 12 DISMANTLING, DEMOLITION AND SCRAPPING During the draining of the refrigeration circuits, do not let the refrigerant overflow in the surrounding atmosphere. The circuit must be drained using suitable recovery equipment. Do not disperse the waste oil of the compressors in the environment…
-
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Your distributor : ITELCO-INDUSTRY Via XXV Aprile, 29 20030 BARLASSINA (MI) - ITALY : +39 0362 6801 : +39 0362 680281