Chilled Water Cassettes
K-OG 30 & 45 Engineering Data Manual EDM KOG2-A.2GB Date : June 2007 Supersedes : None
-
Design Features
Introduction Ventilation Chilled Water units of the "Cassette" type offer comfortable air conditioning at a low cost of installation. They fit harmoniously into standard modules of a false ceiling thanks to their design and small space requirements. - Centrifugal turbine with direct drive. They are…
-
Technical Data
MODELS 30 2 pipes 45 2 pipes 45 4 pipes Nominal cooling capacity (1) - Nominal supply voltage 230V/50Hz W 6440 10190 10100 Nominal heating capacity (2) - Nominal supply voltage 230V/50Hz W 8050 11600 6670 High speed m3/h 1550 1630 1725 Medium speed m3/h 1350 1250 1360 AIR FLOW (AVERAGE VALUES)…
-
Electrical Data
MODELS 30 45 Power supply ~230 V - 50 Hz * * VENTILATION Nominal current A 0.9 0.96 Maximum current A 1.27 1.35 Fuse rating aM* A 2 2 Fuse rating ASE/VDE* 2 2 mm2 3G 1.5 3G 1.5 Nominal current A 19.0 Maximum current A 22.6 Fuse rating aM* A 25 Cable section A VENTILATION + ELECTRIC HEATING Fuse…
-
Cooling Capacities
-
Heating Capacities
-
Pressure Drops
∆Pwo Pressure drop 50 Size 45 - 4 pipes 40 Size 45 - 2 pipes Size Water flow m3/h ∆Pwo : Pressure drops of pure water. ∆Pw : Pressure drops of brinewater. ∆Pw : K x ∆Pwo. K : Glycol coefficient % Glycol % Glycol Twm (°C) Tse (°C) 1.135 1.234 1.385 1.53 1.85 5 1.13 1.23 1.38 1.51 1.77 10 1.12 1.22…
-
Field of Operation
Using chilled water Indoor temperature °C Cooling water °C Indoor temperature °C Cooling water °C Thi 13 Tsi 17 Twe 3 Thi 22 Tsi 32 Tse 18 Thi 22 Tsi 32 Twe 60 MINIMUM TEMPERATURE MAXIMUM TEMPERATURE Using hot water (electric heating forbidden) Maximum indoor temperature °C Maximum entering water…
-
Fresh Air Intake
Fresh air flow should not exceed 12% of nominal air flow (See table hereunder). NOTE : An anti-frost thermostat preset at +5 °C, installed on site on fresh air intake is mandatory for winter application. A filter, fan and insulated air duct (not supplied) are to be installed on site. Models Treated…
-
Dimensions
2-pipe units DESCRIPTION 1 False ceiling 2 T-shaped rod (false ceiling) 3 Heat exchanger 4 Fan 5 Suction grille 6 Electric box (removable) Page Draining of condensates (Ø1/2") Coupling of water inlet (G1") Coupling of water outlet (G1") Port to distribute air through a duct into a neighbouring room…
-
Dimensions (continued)
4-pipe units DESCRIPTION 1 False ceiling 2 T-shaped rod (false ceiling) 3 Heat exchanger 4 Fan 5 Suction grille 6 Electric box (removable) 7 Draining of condensates (Ø1/2") 8 8a 9 9a 10 11 Coupling of hot water outlet (G1/2") Coupling of hot water inlet (G1/2") Coupling of chilled water outlet (G1")…
-
3-Way Valve with By-pass
The kit three-way valve with by-pass allows to control "all or nothing" of a cassette when operating chilled water mode or hot water mode. This kit includes a three-way valve with by-pass controlled by an electric servomotor. Motorized 3-way valve with by-pass Electric servomotor Valve body…
-
Electrical Wiring Diagrams - Standard Wiring for 2-pipe Cassettes
�� �� The electrical wiring diagram can be modified without advance notice. Always refer to the diagram supplied with the unit. Page 13
-
Electrical Wiring Diagrams - Standard Wiring for 4-pipe Cassettes
The electrical wiring diagram can be modified without advance notice. Always refer to the diagram supplied with the unit. Page 14
-
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Your distributor : CAC Export Department 42 cours Jean-Jaurès 17800 Pons - France Tel. : +33 (0)5 - Fax : +33 (0)5
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Модели K 9/12/18 OG. Кассетные фанкойлы Airwell. Руководство по установке и эксплуатации.PDF · 4.15 Mb
- Модели (2-трубные) K 30/45 OG 2T, (4-трубные) K 45 OG 4T. Кассетные фанкойлы Airwell. Руководство по монтажу и эксплуатации.PDF · 3.87 Mb
- Модели (2-трубные) K 9/12/18 OG 2T, (4-трубные) K 9/12/18 OG 4T. Кассетные фанкойлы Airwell. Инструкция по монтажу.PDF · 1.08 Mb
- KOG 9-18. Кассетные фанкойлы Airwell K OG. Техническое руководство.PDF · 377.93 Kb