Технический каталог Sinclair 2022 - Коммерческие системы – Кондиционеры SDV, Чиллеры, Фанкойлы
Технический каталог Sinclair 2022 - Коммерческие системы – Кондиционеры SDV, Чиллеры, Фанкойлы, Автоматика, Вентиляторы
Загружаем документ…
Текст каталога
-
V022-EN-01
TECHNICAL CATALOGUE COMMERCIAL SYSTEMS 2022 · OUTDOOR UNITS SDV4 · OUTDOOR UNITS SDV5 · OUTDOOR UNITS SDV5-3P · SDB SDV5-3P · INDOOR UNITS SDV5 · AHU KIT · CONTROLLERS · BMS SYSTEMS · MINI CHILLERS · MODULAR CHILLERS · FAN COIL UNITS AIR CONDITIONING
-
CONTAIN OUTDOOR UNITS SDV4/SDV5 SIDE AIR DISCHARGE 2 OUTDOOR UNITS SDV5 9 OUTDOOR UNITS SDV5-3P 18 SDB SDV5-3P 22 INDOOR UNITS SDV5 24 AHU KIT 48 CONTROLLERS 52 BMS SYSTEMS 53 REFNETS 54 ERROR CODES SDV 55 MINI CHILLERS 57 MODULAR CHILLERS 61 COMPACT FOUR-WAY CASSETTE FAN COIL UNITS, 2PIPES 66…
-
SDV5-100EAS
SDV4-140EAA SDV4-160EAA - 3,5 5 6 6,5 phase / Hz / V 1 ~ / 50 / 220-240 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 9,0 (2-10) 14 15,5 17,5 Cooling input power kW 2,64 3,95 4,52 5,30 EER - 3,41 3,54 3,43 3,30 Heating capacity kW 9,0 (2,1 - 12) 15,4 17 19 Heating…
-
SDV5-200EAS
SDV5-224EAS SDV5-260EAS - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 MODEL Horse power (HP) Power SDV5-280EAS Cooling capacity kW 20 22,4 26 28,5 Cooling input power kW 4,90 6,83 9,63 12,28 EER - 4,08 3,28 2,70 2,32 Heating capacity kW 20 22,4 26 28,5…
-
SDV5-335EAS
SDV4-400EAA - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 MODEL Horse power (HP) Power SDV4-450EAA Cooling capacity kW 33,5 40,0 45,0 Cooling input power kW 14,38 11,9 13,6 EER - 2,33 3,35 3,32 Heating capacity kW 33,5 45,0 50,0 Heating input power kW 8,1 11,1 12,7 COP…
-
SDV4-140EAA/160EAA
-
2 Installation
space (Unit:mm) SDV5-200EAS/224EAS/260EAS/280EAS/335EAS SDV4-400EAA/450EAA 1558 1650 4.4 Dimension(Unit: mm) C 668 206 Fig.4-8 528 494 Table 4-1 1120 Fig.4-7 505 B 500 A Model Model 40 kW A Size 175 4533.5kW/40kW kW 225 Fig.3-1 45kW B A B C C 505 1360 175555 505 1360 1460 225 555 1460 ALLOWED LENGHT…
-
SDV5-100EAS
SDV4-140EAA/160EAA/180EA 7
-
SDV5-200/224/260/280/335EAS, SDV4-400/450EAA
Outdoor power supply Switch Fuse Outdoor unit Power supply for the outdoor unit monitor Outdoor unit monitor (Optional) L N A B C N K1 K2 E O A E X Y E P Q E K1 K2 E Power supply for the central indoor unit controller central indoor unit controller(Optional) L N Digital ammeter power supply X Y E…
-
MODEL
SDV5-280EAI SDV5-335EAI SDV5-400EAI - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 28,0 33,5 40,0 45,0 Cooling input power kW 6,7 8,9 11,0 12,9 EER - 4,2 3,8 3,7 3,5 Heating capacity kW 28,0 33,5 40,0 45,0 Heating input power kW 5,5…
-
MODEL
SDV5-500EAI SDV5-560EAI SDV5-615EAI - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 50,0 56,0 61,5 67,0 Cooling input power kW 14,7 16,0 20,2 21,6 EER - 3,4 3,5 3,1 3,1 Heating capacity kW 50,0 56 61,5 67,0 Heating input power kW 12,2…
-
MODEL
SDV5-785EAI SDV5-850EAI - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 78,5 85,0 90,0 Cooling input power kW 24,9 28,3 32,1 EER - 3,2 3,0 2,8 Heating capacity kW 78,5 85,0 90,0 Heating input power kW 21,8 24,3 36,5 COP - 3,6 3,5 3,4 Combination of…
-
6.4 Wiring
-
MODEL
SDV5-280EAM SDV5-335EAM SDV5-400EAM - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 28,0 33,5 40,0 45,0 Cooling input power kW 6,3 8,7 9,9 12,0 EER - 4,5 3,9 4,1 3,8 Heating capacity kW 28,0 33,5 40,0 45,0 Heating input power kW 5,2…
-
MODEL
SDV5-500EAM SDV5-560EAM SDV5-615EAM - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 50,0 56,0 61,5 67,0 Cooling input power kW 12,5 15,1 18,4 18,1 EER - 4,0 3,7 3,7 3,7 Heating capacity kW 50,0 56 61,5 67,0 Heating input power kW 10,6…
-
MODEL
SDV5-785EAM SDV5-850EAM - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 78,5 85,0 90,0 Cooling input power kW 24,2 27,4 31,0 EER - 3,3 3,1 2,9 Heating capacity kW 78,5 85,0 90,0 Heating input power kW 20,7 23,0 25,7 COP - 3,8 3,7 3,5 Combination of…
-
ALLOWED LENGHT AND DROP HEIGHT OF CONNECTION
-
refrigerant and vacuumize)
Liquid pipe connection port (ΦA) Liquid pipe connection port (ΦA) Gas pipe connection port (ΦB) DETAIL OF PIPE CONNECTIONS Gas pipe connection port (ΦB) SDV5 MODULAR 63 DETAIL R1, R2 63 ,R3 Fig.4-9 Fig.4-9 DETAIL R4 Detail R1, R2 ,R3 Check port (used to measure system pressure, charge refrigerant…
-
MODEL
SDV5-252EA3P SDV5-280EA3P SDV5-335EA3P SDV5-400EA3P - phase / Hz / V 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 3 ~ / 50 / 380-415 Cooling capacity kW 22,4 28,0 33,5 40,0 45,0 Cooling input power kW 5,3 7,2 8,6 9,8 12,0 EER - 4,3 3,9 3,9 4,1 3,8 Heating capacity kW…
-
MODEL
SDV5-500EA3P Horse power (HP) - 18 phase / Hz / V 3 ~ / 50 / 380-415 Cooling capacity kW 50,0 Cooling input power kW 13,8 Power APPEARANCE AND DIMENSIONS OF OUTDOOR UNIT 8, 10, 12 HP EER - 3,6 Heating capacity kW 50,0 Heating input power kW 11,9 COP - 4,2 Combination of indoor units - 50-200% of OD…
-
APPEARANCE AND DIMENSIONS OF OUTDOOR UNITExpansion bolt
-
Example for power wire connection Power(380-415V 3Na50/60Hz) L1 L2 L3 N $ % & 1 Branch Box Outdoor unit(master unit) Outdoor unit(slave unit) Outdoor unit(slave unit) $ $ $ % & 1 Branch Box ( % & 1 + + ( 3 4 ( % & 1 + + ( 3 4 ( Signal wire between outdoor units SDB / + + ( 3 4 ( 3 4 ( Signal wire…
-
DISTRIBUTION BOXES
-
ELECTRICAL WIRING AND PIPING LINES
-
SDV5 COMPACT FOUR WAY CASSETTE
MODEL Capacity cooling/heating Power supply SDV5-17CA SDV5-22CA SDV5-28CA SDV5-36CA kW 1,7/2,2 2,2/2,4 2,8/3,2 3,6/4,0 SDV5-45CA 4,5/5,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W Air flow of ID m³/h…
-
SDV5 FOUR WAY CASSETTE
MODEL Capacity cooling/heating Power supply SDV5-56CA SDV5-71CA SDV5-80CA SDV5-90CA kW 5,6/6,3 7,1/8,0 8,0/9,0 9,0/10,0 SDV5-100CA 10,0/11,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W Air flow of ID m³/h…
-
SDV5 FOUR WAY CASSETTE
MODEL SDV5-112CA Capacity cooling/heating Power supply SDV5-140CA kW 11,2/12,5 14,0/16,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W 75 94 Air flow of ID m³/h 1596/1477/1365/1239/ 1154/1087/1034 1727/1622/1517/1426/ 1351/1289/1224 dB(A) 47/45/43/41/39/37/36…
-
SDV5 ONE WAY CASSETTE
MODEL Capacity cooling/heating Power supply SDV5-18C1A SDV5-22C1A SDV5-28C1A SDV5-36C1A kW 1,8/2,2 2,2/2,6 2,8/3,2 3,6/4,0 SDV5-45C1A 4,5/5,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W Air flow of ID m³/h…
-
SDV5 ONE WAY CASSETTE
Unit mm SDV5-56C1A Capacity cooling/heating kW Power supply phase / Hz / V Power input 7,1/8,0 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 A W 48 60 m³/h SH/MH/H/M/L/ ML/SL 792/763/728/688/643/ 589/549 933/873/815/749/689/ 637/592 dB(A) 42/41/40/39/38/37/36 44/43/42/41/39/38/37 dB(A) 56/55/54/53/52/51/50…
-
MODEL
SDV5-17HA SDV5-22HA kW 1,7/2,2 2,2/2,4 2,8/3,2 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-28HA Power input W Air flow of ID m³/h 411/402/393/385/378/ 368/356 422/411/402/393/380/ 368/356 417/402/386/370/353/ 338/316 dB(A)…
-
MODEL
SDV5-36HA SDV5-45HA kW 3,6/4,0 4,5/5,0 5,6/6,3 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-56HA Power input W Air flow of ID m³/h 656/628/591/573/544/ 515/488 594/563/535/507/478/ 450/424 747/713/685/648/613/ 578/547 dB(A)…
-
MODEL
SDV5-71HA SDV5-80HA kW 7,1/8,0 8,0/9,0 9,0/10,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-90HA Power input W Air flow of ID m³/h 1195/1130/1065/1005/ 940/875/809 1195/1130/1065/1005/ 940/875/809 1421/1300/1125/1067/…
-
MODEL
SDV5-17DA/17DAP SDV5-22DA/22DAP SDV5-28DA/28DAP kW 1,7/2,2 2,2/2,6 2,8/3,2 3,6/4,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-36DA/36DAP Power input W Air flow of ID m³/h 490/480/440/400/360/ 330/300…
-
MODEL
SDV5-45DA/45DAP SDV5-56DA/56DAP SDV5-71DA/71DAP kW 4,5/5,0 5,6/6,3 7,1/8,0 8,0/9,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-80DA Power input W Air flow of ID m³/h 800/740/680/620/ 540/480/400…
-
MODEL
Capacity cooling/heating Power supply SDV5-90DA SDV5-112DA kW 9,0/10,0 11,2/12,5 SDV5-140DA 14,0/15,5 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W Air flow of ID m³/h 1260/1180/1100/1020/ 940/860/780 1500/1430/1360/1290/ 1210/1140/1080 1960/1860/1760/1660/…
-
MODEL
Capacity cooling/heating Power supply SDV5-71DHA SDV5-80DHA SDV5-90DHA SDV5-112DHA kW 7,1/8,0 8,0/9,0 9,0/10,0 11,2/12,5 SDV5-140DHA 14,0/16,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W Air flow of ID m³/h…
-
MODEL
Capacity cooling/heating Power supply SDV5-160DHA SDV5-200DHA SDV5-250DHA SDV5-280DHA kW 16,0/17,0 20,0/22,5 25,0/26,0 28,0/31,5 SDV5-400DHA 40,0/45,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W 1200 1800 Air flow of ID…
-
MODEL
SDV5-450DHA Capacity cooling/heating Power supply SDV5-560DHA kW 45,0/50,0 56,0/63,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W 1800 2272 Air flow of ID m³/h 6500/6150/5800/5450/ 5100/4750/4400 7400/7000/6600/6200/ 5800/5400/5000 dB(A) 60/59/58/57/55/54/52…
-
The positioning of the ceiling hole, indoor unit and hanging screw bolts
Routine method of installation: The size of the installation for the indoor unit. 7,1-11,2 KW 14-16 KW 38
-
The positioning of the ceiling hole, indoor unit and hanging screw bolts
Routine method of installation: The size of the installation for the indoor unit. 20 KW, 25 KW, 28 KW APPEARANCE AND DIMENSIONS OF INDOOR UNIT 1937 The positioning of the ceiling hole, indoor unit and hanging screw bolts. Routine method of installation: The size of the installation for the indoor…
-
SDV5 FRESH AIR DUCT
MODEL SDV5-125DFA Capacity cooling 1)/heating 2) Power supply SDV5-140DFA kW 12,5/10,5 14,0/12,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W 480 480 Air flow of ID m³/h 2000/1917/1833/1750/ 1667/1583/1500 2000/1917/1833/1750/ 1667/1583/1500 dB(A) 48/47/46/45/44/43/42…
-
Size of
Return Air Inlet Position of lifting bolt Connect to water piping Return Air Inlet Flange (L) Return Air Inlet Flange Connection hole Return Air Inlet Air Outlet Electric control box assembly 12.5~14.0KW 3.3.1 Installation dimensions of lifting bolts and location size of connecting piping (unit: mm)…
-
SDV5 FLOOR/CEILING
MODEL SDV5-36FA SDV5-45FA SDV5-56FA SDV5-71FA kW 3,6/4,0 4,5/5,0 5,6/6,3 7,1/8,0 8,0/9,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-80FA Power input W Air flow of ID m³/h…
-
SDV5 FLOOR/CEILING
MODEL SDV5-90FA SDV5-112FA kW 9,0/10,0 11,2/12,5 14,0/15,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-140FA Power input W Air flow of ID m³/h 1280/1245/1210/1170/ 1130/1085/1050 1890/1830/1765/1700/ 1660/1620/1580…
-
SDV5 FLOOR CONCEALED
MODEL SDV5-22FCA SDV5-28FCA SDV5-36FCA kW 2,2/2,4 2,8/3,2 3,6/4,0 4,5/5,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply SDV5-45FCA Power input W Air flow of ID m³/h 530/504/478/456/439/ 418/400 569/540/515/485/462/…
-
SDV5 FLOOR CONCEALED
MODEL Capacity cooling/heating Power supply SDV5-56FCA SDV5-71FCA kW 5,6/6,3 7,1/8,0 SDV5-80FCA 8,0/9,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Power input W Air flow of ID m³/h 1150/1094/1028/970/ 925/886/830 1380/1290/1205/1100/ 1033/955/870 1380/1290/1205/1100/…
-
SDV5 CONSOLE
MODEL SDV5-22PA SDV5-28PA SDV5-36PA kW 2,2/2,4 2,8/3,2 3,6/4,0 4,5/5,0 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity cooling/heating Power supply Power input Air flow of ID SH/MH/H/M/L/ ML/SL Sound pressure level at 1 m SDV5-45PA W m³/h…
-
ALL INDOOR UNITS SDV5
ELECTRICAL CONNECTION COMMUNICATION WIRING BETWEEN THE INDOOR UNIT AND OUTDOOR UNIT PQE COMMUNICATION WIRING BETWEEN THE INDOOR UNIT AND WIRED CONTROLLER The wired controller and the indoor unit can be connected in different manners, depending on the forms of communication. For a bidirectional…
-
AHU KIT
COMPATIBLE WITH OD SDV4, SDV4F, SDV5 AND SDV5-3P MODEL AHUKZ-00D AHUKZ-01D AHUKZ-02D kW 2,2-8 9-20 21-36 37-56 phase / Hz / V 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 1 ~ / 50 / 220-240 Capacity Power supply AHUKZ-03D Net dimensions wxdxh mm 393x341x125 393x341x125 393x341x125…
-
Signálový kabel (P/Q/E): Kabel mezi venkovní jednotkou a primárním AHU kitem
Signálový kabel (X/Y/E): Kabel mezi primárním AHU kitem a sekundárními AHU kity Wiring signal wires Terminal block for signal wires Ovladač od výrobce Ovladač od třetí strany CN17 CN18 CN62 CN61 nebo CN9 Vi- Vi+ Primární AHU kit Signálový kabel venkovní jednotky (X/Y/E) CN32 Signálový kabel (P/Q/E)…
-
EXTERNAL CONTROL OF AHU KIT
The definition of signal between the third party controller and AHU control box Signals from the third party controller to AHU control box Signal Signal Type Specification Port Capacity set Analog voltage 0-10VDC 0-10V ON/OFF Dry contact Close: ON Disconnect: OFF ON/OFF Cool mode Dry contact Close…
-
ANALOG VOLTAGE CONTROL
Based on outdoor unit capacity - setting 0-100% (possible to use T1 or TA) Capacity Setting requirement table (Same in Heating and Cooling) Analog input 0-10V DC Normal (V) Capacity Setting Requirement Range (V) 0 U<0.5 0% 1 0.5≤U<1.5 10% 2 1.5≤U<2.5 20% 3 2.5≤U<3.5 30% 4 3.5≤U<4.5 40% 5 4.5≤U<5.5…
-
MODEL RM05B SWC-86E SWC-86ED SWC-120G On/Off yes yes yes yes Mode selection yes yes yes yes Temperature setting yes yes yes yes Dual temp. set points no no yes yes 7-speed fan control yes yes yes yes Auto swing yes yes yes yes 5-step swing louver yes yes yes yes Adress setting yes yes yes yes Follow…
-
MODEL CCM15 CCM-180A CCM-270A SCM-30 Max. number of ID Max. number of OD - 32 192 - Max. number of ref. systems - 8 48 - - 6,2 10,1 touch pads Touch screen inch On/Off yes yes yes yes Mode selection yes yes yes yes yes (1 °C steps) yes (0,5 °C steps) yes (0,5 °C steps) yes (1 steps) Dual temp. set…
-
SDV4-HN04k
-
COMERCIAL AIR CONDITIONING
GENERAL OVERVIEW OF ERROR CODES APPLIES TO ALL SDV OUTDOOR UNITS IN THIS CATALOGUE C7 Inverter module temperature protection d0 Oil return operation dF Defrosting operation E0 Communication error between outdoor units E1 Phase sequence error E2 Communication error between indoor and master unit E4…
-
GENERAL All dimensions on pictures are in milimeters (mm) in this catalogue. CONDITIONS UNDER WHICH HAS BEEN PERFORMED MEASUREMENTS OF TECHNICAL PARAMETERS: OUTDOOR UNITS 1. Capacities are based on the following conditions: Cooling: Indoor temperature 27 °C DB / 19 °C WB; Outdoor temperature 35 °C…
-
MINI CHILLERS
MODEL SCV-50EB Power supply Heating A7W35 SCV-70EB V/Ph/Hz SCV-100EB SCV-120EB SCV-140EB 220-240/1/50 Capacity W 6500 8400 10000 12200 14100 Rated input W 1226 1663 2128 2490 3000 EER - 5,30 5,05 4,70 4,90 4,70 Capacity W 5600 7100 8200 12300 13000 Rated input W 1333 1797 2158 3417 3714 EER - 4,20…
-
MINI CHILLERS
MODEL SCV-160EB Power supply Heating A7W35 V/Ph/Hz 220-240/1/50 SCV-120EB-3 SCV-140EB-3 SCV-160EB-3 380-415/ 3/50 Capacity W 16000 12200 14100 16000 Rated input W 3556 2490 3000 3556 EER - 4,50 4,90 4,70 4,50 Capacity W 14500 12300 13000 14500 Rated input W 4462 3417 3714 4462 EER - 3,25 3,60 3,50…
-
SCV-50/70/100/120/140/160EB/EB-3
-
KOMUNIKAČNÍ ZAPOJENÍ DO KASKÁDY
ELECTRICAL WIRING KOMUNIKAČNÍ ZAPOJENÍ DO KASKÁDY SW9 SW9 OFF Slave unit OFF Slave unit ON Master unit ON Master unit X/HAY/HB Please use the shielded wire, and the shield layer must be grounded. X/HAY/HB Please use the shielded wire, and the shield layer must be grounded. Master unit Master unit…
-
MODULAR CHILLERS
MODEL SCV-300EB Power supply Cooling1 Heating2 Water side heat exchanger Refrigerant SCV-600EBH SCV-900EB kW 27,5 27,5 Input kW 10,3 11,0 21,5 23,0 27,8 EER - 2,67 2,50 2,55 2,39 2,95 SEER - 4,62 4,25 4,00 4,03 4,50 Capacity kW Input kW 10 10,7 20 21,5 28,1 COP - 3,20 2,99 3,10 2,88 3,20 SCOP - 4,24…
-
MODULAR CHILLERS
MODEL SCV-900EBH Power supply Cooling1 Heating2 V/Ph/Hz Capacity kW 82 Input kW 28,3 EER - 2,90 SEER - 4,44 Capacity kW 90 Input kW 29,0 COP - 3,10 SCOP - 3,77 Max. running current Compressor A Type Quantity Air side heat exchanger Water side heat exchanger Refrigerant 380-415/3/50 60 DC inverter…
-
SCV-300EB/300EBH
SCV-600EB/600EBH 63
-
A D
-
EXPANSION BOLT POSITIONING
SCV-300EB/300EBH SCV-600EB/600EBH SCV-900EB/900EBH 2200 Inlet and outlet pipe side 1460 370 Electric control 1017 box side Drainage channel Anchor bolt DETAIL OF PIPE CONNECTIONS SCV-300EB/300EBH SCV-600EB/600EBH Model Pipe connection methods SCV-300EB/EBH SCV-600EB/EBH SCV-900EB/EBH…
-
FCU COMPACT FOUR-WAY CASSETTE, 2 PIPES
MODEL SF-300C2(M) SF-400C2(M) SF-500C2(M) Power supply V/Ph/Hz Air flow (H/M/L) m³/h 535/429/322 610/477/381 CFM 314/252/189 359/281/224 459/359/290 Capacity (H/M/L) kW 2,98/2,53/2 3,96/3,26/2,76 4,2/3,48/3,01 Cooling Heating 220-240/1/50 781/611/494 Water flow rate m³/h 0,53/0,45/0,35 0,7/0,58/0,51…
-
FCU FOUR-WAY CASSETTE, 2 PIPES
-
FCU COMPACT FOUR-WAY CASSETTE, 4 PIPES
MODEL SF-300C4(M) SF-400C4(M) SF-500C4(M) Power supply V/Ph/Hz Air flow (H/M/L) m³/h 493/395/295 669/523/415 CFM 290/232/173 393/307/244 395/309/250 Capacity (H/M/L) kW 2,16/1,86/1,49 2,78/2,38/2,05 2,77/2,38/2,07 Water flow rate m³/h 0,42/0,37/0,3 0,53/0,46/0,4 0,56/0,49/0,43 Water pressure drop…
-
FCU FOUR-WAY CASSETTE, 4 PIPES
-
FCU WALL-MOUNTED
MODEL SF-250HM2 SF-400HM2 SF-600HM2 Power supply V/Ph/Hz Air flow (H/M/L) m³/h 492/454/400 825/689/590 CFM 289/267/235 485/405/347 575/499/421 Capacity (H/M/L) kW 2,7/2,59/2,39 3,81/3,3/2,88 4,87/4,26/3,79 Water flow rate m³/h 0,48/0,46/0,42 0,67/0,57/0,51 0,85/0,72/0,65 Water pressure drop kPa…
-
таблицы и схемы — в просмотре
-
FCU DUCT 2 PIPES
-
FCU FLOOR CEILING 2 PIPES
-
таблицы и схемы — в просмотре
-
GENERAL - All dimensions on pictures are in mimimeters (mm) in this catalogue This catalogue is informative only and does not constitute a binding offer from the side of SINCLAIR CORPORATION LTD. The Company takes no responsibility for any damage arising out of using or interpretation of this…
-
AIR CONDITIONING
sinclair-world.com | sinclair-solutions.com
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.