TECHNICAL DATA
-
Important
Please Read Before Starting When Installing This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. …In a Room Properly insulate any…
-
Check of Density Limit
Do not install the indoor unit to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air. NOTE (1) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a…
-
Page
Please Read Before Starting Important i Check of Density Limit Important ii Section 1 : Outline of W-ECO MULTI SYSTEM I - 1 1. Line Up I - 2 2. Features of W-ECO MULTI SYSTEM I - 4 3. Outline of Indoor Unit I - 9 4. Example of W-ECO MULTI SYSTEM I - 15 Section 2 : Design of W-ECO MULTI SYSTEM II - 1…
-
Page
Section 6 : Processes and Functions VI - 1 1. Compressor Control VI - 2 2. Protection Controls VI - 3 3. Fan Control VI - 5 4. Outdoor Electronic Expansion Valve VI - 5 5. Solenoid Valve Control VI - 6 6. Hot Gas Defrosting Control VI - 7 7. Self-Separator Oil Recovery Control VI - 8 8.…
-
1. Outline of W-ECO MULTI SYSTEM
1. Line Up I - 2 2. Features of W-ECO MULTI SYSTEM I - 4 2-1. Outline of system I - 4 2-2. Installation I - 7 2-3. Control characteristics I - 7 2-4. Delicate control with large crystal display I - 8 3. Outline of Indoor Unit I - 9 3-1. 4-Way air discharge semi-concealed type I - 9 3-2. 2-Way air…
-
2-1. Outline of system
W-ECO MULTI is capable of controlling the capacity by 1 H.P. up to 30 H.P. without inverter control. 7 W-ECO multi system Up to 30 H.P. (84 kW) Limitation of system Allowable no. outdoor unit connected 2 units ● SANYO makes it possible to link Allowable max. capacity of outdoor unit 30 H.P. (84 kW)…
-
7 Capacity control
With a triple compressor organization (consisting of one PC compressor and two AC compressors), capacity control can be implemented by adding an external save valve. To Indoor Unit Narrow tube (H.P.) 30 Wide tube 1 25 Balance tube Service Value 20 External save valve Discharge Suction Discharge…
-
7 Control system diagram
Outdoor unit 1 AMY adaptor Weekly timer • The main bus is twin-core and non-polar for easier wiring. • Indoor unit settings are automated for easy installation. Note A “bus” is a pathway for transmitting control signals. ¶ Remote controller ¶ System controller ¶ Weekly timer ¶ AMY adaptor System…
-
2-2. Installation
2-3. Control characteristics 7 Compact size and Light weight outdoor unit 7 New control wiring system (S-net link system) 150 Type 190 Type 70 Type 90 Type Dimensions: H × W × D mm ¶ It allows connection of as many as total of 94 units (64 > Indoor unit + 30 > Outdoor unit) in a network with a…
-
2-4. Delicate control with large crystal
display 7 Remote controller (RCS-SH80TG) 7 “Personal” comfortable air flow : Option ¶ Comfortable auto flap control • The flap is automatically positioned moving it 1 AIR FLOW UNIT FLAP upward / downward, at the time of switching over between cooling, and heating. • The flap can be set at desired…
-
7 Whisper-quiet operation
3-1. 4-Way air discharge semiconcealed type The noise level of Type 12, 18, 25 has reduced to 37 dB (A) in the “Hi” mode and 31 dB (A) in the “Lo” mode. Thanks to the newly developed turbo fan and decreased air path resistance, one of the trade’s lowest levels of noise has been realized. XR123GH…
-
7 Ideal air stream realized for both heating
and cooling. 3-2. 2-Way air discharge semiconcealed type Comes with auto flap feature as standard. When the fan speed becomes Lo at the time of 3m heating, the auto flap adjusts the area of blow port and retains the fan speed at the same level as at the time of 783_8132 Hi, keeping the whole room…
-
¶ Sophisticated Color and Round Surface Design
3-4. Wall-mounted type ¶ Simple installation work ¶ 3-way tubing possible KR93GH, KR123GH, KR183GH K93GH, K123GH, K183GH Left tubing Right-rear tubing (recommended) Left-rear tubing 1273_K_I 582_8132 ¶ Air sweep function The air sweep function moves the flap up and down in the air outlet, directing…
-
¶ Built-in drain pump
3-6. Concealed-duct type New One of the major features of the new concealed-duct type air-conditioner is that air flow outlets can be arranged individually using circular flexible ducts. This more efficient air flow creates a more balanced air conditioning. Moreover, since the indoor unit is…
-
3-8. Floor-standing type (F Type)
FR93GH, FR123GH FR183GH, FR253GH F93GH, F123GH F183GH, F253GH Flat appearance and easy to maintain. ¶ Front panel opens fully for easier maintainance. ¶ Removable air discharge grille allows changing air flow direction. ¶ Pipes installable from either side of the indoor unit (left or right). 1…
-
3-10. 1-Way air discharge semi-concealed slim type
SLR93GH, SLR123GH SLR183GH, SLR253GH Super-slim 19.8 cm design ¶ With an embedded area of just 19.8 cm, it is ideal for installation in areas with limited space. Plus, the ceiling panel is just 1.5 cm deep, so it doesn’t impose on the interior design of the room. Auto-flap system and long-life…
-
4-1. List of controllers
Name Features 1 Group (collective) control of maximum up to 8 indoor units with a remote controller is possible. Remote Controller RCS-SH80TG AIR FLOW UNIT FLAP MODE AIM °C SET TEMP. FAN SPEED III-6~ 2 Control with multiple remote controls (main / sub) is possible. (Max. 2) 3 Operating state appears…
-
Name
Features Simplified Remote Controller RCS-KR1T 1 CENTRAL CTRL A STANDBY °C SET TEMP. TEST SETTING A CHECK SENSOR FAN SPEED SET TEMP. MODE ON - / OFF - FLAP TEST 1494_T_I Remote Sensor ART-K41T Ref. page III-62~ 1 This easy-to-operate, multifunction remote controller is ideal for use in hotels and…
-
4-2. Example of control system
Controller Contents of control Remote (1) Standard control ¶ The cooling / heating mode of controller outdoor unit is determined by RCS-SH80TG the first-press priority of remote controller. Control method (1) Standard control (2) Multiple remote control Control with remote controller (3) Group…
-
2. Design of W-ECO MULTI SYSTEM
1. Model Selecting and Capacity Calculation II - 2 1-1. Operating range II - 2 1-2. Procedure for selecting models and calculating capacity II - 3 1-3. Calculation of actual capacity II - 4 ¶ Corrected capacity of indoor unit when Indoor / Outdoor unit capacity ratio is in the range of 100 to 130 %…
-
1-1. Opertating range
Heating Cooling Outdoor air intake temp. °C (WB) 15.5 2 Outdoor air intake temp. °C (DB) 30 25 Operating range Operating range 0 –5 –10 5 –15 Indoor air intake temp. °C (DB) 606_8132 –5 –10 : Rated conditions Indoor air intake temp. °C (WB) 1750_M_I Cooling operating range NOTE When combined with…
-
1-2. Procedure for selecting models and calculating capacity
Select the model and calculate the capacity by using the procedure below. Calculation of the indoor air-conditioning load Selection of air-conditioning system Design of control system Selection of indoor unit model Preliminary selection of indoor unit and outdoor unit combination Calculation of…
-
1-3. Calculation of actual capacity
Since the capacity of multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference, etc. select the right model taking into account various correction values. 7 The actual capacity of multi air-conditioner according to its installation conditions is…
-
7 Outdoor unit capacity when the indoor / outdoor capacity ratio is in the range of 100 % to 130 %
Ex: Increasing ratio of outdoor unit capacity (%) The outdoor unit capacity, in case the indoor / outdoor capacity ratio is 100 % - 130 %, can be found out from the table of corrected capacities given the graph shown on the right. 108 107 Cooling 106 105 When both the indoor / outdoor capacity…
-
¶ Corrected capacity of indoor unit when Indoor / Outdoor unit capacity ratio is in the range of 100
to 130 % Unit: kW Indoor Unit 9 type 12 type 18 (K) type 18 type (except K) 25 type 36 type 48 type Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating 100 % 2.8 3.2 3.6 4.2 5.0 6.0 5.6 6.3 7.3 8.0 10.6 11.4 14.0 16.0 Unit type 2.78 2.76…
-
¶ Corrected capacity of outdoor unit when Indoor / Outdoor unit capacity ratio is in the range of 100 to 130 % PC units 150 type 190 type Capacity kW Capacity kW Indoor / Outdoor unit capacity ratio Cooling Heating Cooling Heating 100 % 45.0 50.0 56.0 63.0 105 % 45.6 50.3 56.7 63.3 110 % 46.1 50.6…
-
1-4. Capacity correction graph according to temperature condition (For R407C)
-
1-5. Capacity correction graph according to refrigerant tubing length and elevation
difference (For R407C) Cooling capacity coefficient Elevation Difference (m) % 0 -10 -20 -30 a 60 70 bd e c Total equivalent tubing length (m) 120 125 1529_M_I To minimize the reduction in cooling capacity to be caused when an excessively long tubing is used, we recommended increasing the diameter…
-
1-6. Capacity correction graph according to temperature condition (For R22)
-
1-7. Capacity correction graph according to refrigerant tubing length and elevation
difference (For R22) Cooling capacity coefficient Elevation Difference (m) % 0 -10 -20 -30 a bd e c Total equivalent tubing length (m) 726_8132 Heating capacity coefficient Elevation Difference (m) % 0 -10 -20 -30 a bd e c Total equivalent tubing length (m) 607_8132 NOTE 1) Plus side of the…
-
1-8. Design of tubing length
L5 1. Main tube LM = LA + LB... < = 50 m. 2. Size of main tube after distribution joint LC ...is depend on the capacity after distribution. 3. Size of distribution branch l1~l32 is depend on the tubing size of indoor unit. H3 L2 LM lA L1 lB T-joint tubing (Header Joint System) LB LC LD LE L3 LA l4 2…
-
Tubing size
Unit: mm (in.) Main tubing size (LA, LB, LC...) Combination Capacity of Outdoor Unit 52.4 kW or more 70.0 kW or more less than 70.0 kW less than 106.0 kW Main tube size Gas tube ø38.10 (1 1/2) ø41.28 (1 5/8) ø44.45 (1 3/4) LA Liquid tube ø15.88 (5/8) ø19.05 (3/4) ø22.22 (7/8) 70 kW or more, less…
-
7 Straight equivalent length of joints
Design the tubing system by referring to the following table for the straight equivalent length of joints. Straight Equivalent Lenght of Joints 2 Unit: m Wide tube size (mm) 12.7 15.88 19.05 22.22 25.4 28.58 31.8 38.1 41.28 44.45 90° Elbow 0.30 0.35 0.42 0.48 0.52 0.57 0.70 0.79 0.85 0.92 45° Elbow…
-
7 Recommended location of ball valves
¶ Recommend that install a ball valve kit at each outdoor unit ¶ Select the position to perform the service easily each unit or each refrigerant system (1) In case of adding the indoor unit 1 LOCATION: Install the ball valve at distribution tube (not main tube). Outdoor unit Main tube Distribution…
-
Always check the gas density
for the room in which the unit is installed. 7 Check of limit density Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the sary to ensure that even if the refrigerant gas accidentally following table. leaks outside, its density does not exceed the limit…
-
2. Example of System Design
-
2. Example of System Design
After extending indoor and outdoor unit ×2 Total cooling capacity after distribution joint 1 Tubing 2 Additional 1× Wide tube Narrow tube / Outdoor unit type / Indoor unit type length (m) refrigerant (g/m) (g) LE2 10.6 + 7.3 + 7.3 = 25.2 kW 28.58 (1 1/8) 12.70 (1/2) LF 7.3 + 7.3 = 14.6 kW 19.05…
-
3-1. General precautions on wiring
(7) Regulations on wire diameters differ from locality to (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring locality. For field wiring rules, please refer to your closely following the wiring diagram. LOCAL ELECTRICAL CODES before…
-
3-3. Wiring system diagrams
-
CAUTION
(1) When linking outdoor units in a network (S-net link system), remove the short plug (CN031, 2P Black, location: right bottom on the outdoor control PCB) from all outdoor units except any one of the outdoor units. Otherwise the communication of S-net link system does not perform. For a system…
-
(5) Use shielded wires for inter-unit control wiring (c)
and ground the shield on both sides, otherwise misoperation from noise may occur. All wiring except inter-unit control wiring (c) has polarity. Connect wiring as shown in Section 5-3 “Wiring System Diagrams”. Shielded wire ground ground 0797_M_I Loose wiring may cause the terminal to overheat or…
-
3-4. Maximum power input
¶ The maximum power input of the outdoor unit is a electric power input consumed when the outdoor unit is operated under the condition of the JIS cooling overload at the indoor / outdoor unit capacity ratio of 130 %. ¶ The maximum power input at the indoor / outdoor unit capacity ratio of less than…
-
4-1. Selecting the installation site
Ceiling-Mounted Type Indoor Unit Ceiling AVOID: ● areas where leakage of flammable gas may be expected. Wall ● places where large amounts of oil mist exist. min. 25 cm ● direct sunlight. NOTE ● locations near heat sources which may affect the performance of the unit. The rear of the indoor unit can…
-
4-2. Transporting
When transporting the unit, have it delivered as close to Rope or strap , , the installation site as possible without unpacking. Use hook for suspending a unit type 190 and 150. Rope or strap must be settled CAUTION properly down at the bottom of the hook, not at the edge of the hook. Protective…
-
(2) The types 70 and 90 must be bolted down through
PC unit vibration insulators tightly to the blocks or platform with (132) AD unit 4 anchor bolts. 830 The unit must sit on the vibra- CAUTION tion insulator and platform at least 10 mm wide at both ends. 2092 (3) The types 190 and 150 must be bolted down through 925 90 vibration insulators tightly…
-
4-4. Outdoor Unit
AVOID: ● heat sources, exhaust fans, etc. ● damp, humid or uneven locations. ● Indoor (no ventilation place) Exhaust fan Hot air DO: Heat source Outdoor unit ● choose a place as cool as possible. ● choose a place that is well ventilated. ● allow enough room around the unit for air intake/ exhaust…
-
4-5. Shield for horizontal exhaust discharge
It is necessary for you to install an air-discharge chamber (field supply) to direct exhaust from the fan horizontally if it is difficult to provide a minimum space of 2 m between the airdischarge outlet and a nearby obstacle. In regions with heavy snowfall, CAUTION the outdoor unit should be…
-
4-8. Dimensions of snow / wind ducting
● Reference diagram for air-discharge chamber (field supply) 844 2 1081 1776_C_I TD831077 II - 29
-
● Reference diagram for snow-proof vents (field supply) (For 150, 190 type) - ø6 hole 200 2 1094 - 7 × 12 hole 632 480 1777_C_I ● Reference diagram for snow-proof vents (field supply) (For 150, 190, 70, 90 type) 5 - 7 × 10 hole - ø6 hole 829 480 1094 1778_C_I II - 30 TD831077
-
4-9. Dimensions of wind ducting
-
4-10. Dimensions of snow ducting
● Reference diagram for snow-proof vents (field supply) PC (power control) unit 1100 2 20 2050 1198 2087 2050 1751_C_I AD (additional) unit 1100 1198 2087 889 19 1752_C_I II - 32 TD831077
-
4-11. Optional distribution joint kits
-
4. APR-HV84MB
-
7. APR-DV148MB
-
4-12. Optional ball valve kits
-
3. Control of W-ECO MULTI SYSTEM
1. Main Operating Functions III - 2 1-1. Room temperature control III - 2 1-2. Fan speed control III - 2 1-3. Auto flap control III - 3 1-4. Functions for group control & multiple remote control III - 4 2. Optional Controller III - 5 List of optional controller functions III - 5 2-1. Remote…
-
1-1. Room temperature control
The thermostat turns ON / OFF with the following ∆T. (2) Fan operation : Set fan speed (3) Dry operation : L (4) When thermo. OFF ∆T = Room temp - Set temp With body thermostat Room temp = (Body sensor) - (Shift temp*) * Shift temp (valid while heating, only) is set when shipped from factory as…
-
¶ Heating operation control
1-3. Auto flap control 1 During heating operation, the “Set fan speed” is set as follows after the thermostat turns ON. [Applicable indoor units] 4-Way, 2-Way, & ceiling mounted E2 Temp ¶ The airflow direction can be set at 5 stages with FLAP setting button. Flap position according to the operating…
-
1-4. Functions for group control & multiple remote control
Group control and multiple remote control become possible by using remote controllers; however part of the functions of the main and sub remote controller cannot be controlled. So, confirm them referring to the following table. Individual remote control (standard) Diagram of system outline Outdoor…
-
2. Optional Controller
7 List of optional controller functions ¶ Remote controller functions In multi system, the following optional remote controllers can be selected, but there are some functions which cannot be controlled. So, confirm the usable functions from the following table at the time of selecting them. j…
-
2-1. Remote controller / RCS-SH80TG
7 How to use the remote controller K: UNIT button H: FLAP button AIR FLOW UNIT FLAP C: MODE button A CENTRAL CTRL UNIT No. R.C. MODE No. AIM MODE FIXED CODE No. °C I: TIMER SET button TIMER SET SET TEMP. E: FAN SPEED button SWEEP SET TEMP. A FAN SPEED SETTING J: Timer setting buttons M: SET button…
-
E
FAN SPEED button F: button (Filter) G: TEST RUN / CHECK H: The air conditioner automatically decides the fan speed. High fan speed Medium fan speed Low fan speed Use this button to reset the filter sign (timer). The air conditioner has the timer for filter and informs you the time of cleaning the…
-
Display (Remote controller)
A H AIR FLOW UNIT A CENTRAL CTRL UNIT No. MODE F FLAP R.C. AIM TIMER SET MODE FIXED CODE No. °C SET TEMP. SET TEMP. FAN SPEED SWEEP G A SET CL ON OFF MONITOR C SETTING CHECK SET DATA I B STANDBY No. D SERVICE TEST E ON • OFF • TEST / CHK 3 0180_M_I Description A : When the unit is in the heating…
-
Setting the Timer OFF Use this mode to turn off the appliance automatically after the length of time set. OFF OFF timer ON Set time 755_8132 OFF ON ON timer Set time 756_8132 OFF OFF OFF cycle timer NOTE Use this mode to start the appliance automatically after the length of time set. ON OFF ON ON…
-
How to set the OFF timer ( OFF
) (Example) To stop the air conditioner after 3:30. Operation SETTING SETTING Indication 1. Press the ON / OFF button to start the air conditioner. 2. Press the TIMER SET button to select OFF mode. The SETTING and time indications flash. \ 3. button until 3.5 is ¶ Press the displayed. ¶ Press the…
-
7 How to install the remote controller
Remote controller wiring can be extended to a maximum of 1,000 m. ¶ Do not twist the control wiring with the power wiring or run it in the same metal conduit, because this may cause malfunction. ¶ Install the remote controller away from sources of electrical noise. ¶ Install a noise filter or take…
-
7 Basic wiring diagram
CAUTION ¶ Use shielded wires for inter-unit control wiring and ground the shield on both sides. Otherwise misoperation because of noise may occur. Install wiring correctly (incorrect wiring will damage the equipment). Shielded wire ground ground Group control Connection wiring for group control…
-
7 Wiring system diagram for group control
This diagram shows when several units (maximum of 8) are controlled by a remote controller (master unit). In this case, a remote controller can be connected at any indoor unit. Remote controller Terminal 3P Wiring procedure Connection wiring for group control Wire according to the left diagram: ¶…
-
7 Wiring system diagram for multiple remote
control ¶ When Installing Multiple Remote Controllers This multiple remote controller system is used for operating the unit(s) at different positions. (A maximum of 2 remote controllers can be installed.) ¶ Setting method Remote Controller Address switch OFF To execute this control, make the setting…
-
7 Service functions of remote controller
From the remote controller you can control both the operation and settings of the unit as well as perform several useful service checks. This section explains how to use the remote controller to: (A) Set service check switches. (B) Use the test run procedure. (C) Check the sensor temperature…
-
(B)
❏ The purpose of the test run function is to let you control the operation of the unit directly without the thermostat turning the unit on or off. As indicated in the following procedure, be sure to switch out of TEST RUN when you are finished, or the air conditioner can be damaged because it won’t…
-
(C)
Check the sensor temperature readings The air conditioner has temperature sensors placed in areas where temperature levels control the heating or cooling process. ❏ Each sensor has an address which is made up of the indoor unit address, and the sensor address. The indoor unit address is used only…
-
Refer to the table below for the relationship between the sensor address and the location of the sensor. Relationship between the sensor address and the location of sensor 3 Sensor Address (CODE No.) Indoor Unit Outdoor Unit 0A 0B 0C 0D 0E 0F ( Location of Sensor (Themistor) — TH1 TH2 TH3 TH4 TH5…
-
The panel now shows this display as shown below
UNIT No. UNIT No. 1–1 R.C. No. Refrigerant Circuit No. No. CODE No. CODE No. CHECK Alarm message SERVICE 778 _8132 c. A maximum of 4 alarm messages can be accessed by pressing either SET TEMP button j or l as follows. MODE NOTE Pressing CL (Clear) button will clear all the service history. Past SET…
-
Important
Never press CL button unless you want to erase the accessed data in memory. Follow the procedure below only when erasing is necessary. ❏ To erase accessed data, press the CL button. ❏ When erasing is finished, shows on the controller’s display. CAUTION After checking the alarm messages be sure to…
-
(F)
Execute the auto. address operation ❏ Auto. address operation is executed by pressing the A. ADD button of outdoor unit’s PCB usually (See “Test Run” V-2 ~). For your convenient it can be executed by remote controller also. a Press the TEST / CHK and b Set CODE No. A1 with ( , ) buttons at the same…
-
(G) Confirm and change the indoor unit address
❏ a The purpose of the above function is to let you confirming the indoor unit address after the auto. address operation, and changing the indoor unit address if it is needed. Press the TEST / CHK and ( AIR FLOW UNIT FLAP ) buttons at the same time for more than 4 seconds. MODE R.C. CODE No. SET…
-
e
Set the required new indoor No. by pressing the AIR FLOW UNIT FLAP , ( ) button. MODE R.C. Ex: UNIT No. 3-6: current registed the indoor unit address No. CODE No. SET TEMP. TIMER SET FAN SPEED SETTING SET DATA SET Required new indoor No.8: SET DATA CL * In this case, UNIT No. 3 ↓– 6 (current) ON •…
-
(H) Change the shift temperature in heating mode
a ❏ If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off early in heating mode because of the hot air temperature of ceiling level. In order to resolve the problem, the shift temp. (valid while heating only) is set when shipped from factory (refer to…
-
(I)
Set the indoor unit address ❏ This function is usable if the auto. address operation is not possible. Indoor unit address can be set one by one by remote controller in such case. NOTE 1) In case of group control, branch wiring for group control should be removed temporarily. 2) In case of remote…
-
d
Set the No. of R. C. which you want to set with AIR FLOW UNIT FLAP , ( ) button. Ex. No. of R. C. will be set 2. MODE UNIT No. R.C. No. CODE No. SET TEMP. TIMER SET FAN SPEED SETTING SET DATA SET CL ON • OFF • TEST / CHK 842_8132 e Press the SET button. UNIT No., CODE No. 12, SETTING and SET DATA…
-
i
Select the code No. 14 to set group setting with the j Set the No. of group setting as shown below with the AIR FLOW UNIT FLAP , (SET TEMP) button. , ( ) button. 0 : Standard system (except group control) MODE UNIT No. R.C. 1 : Main indoor unit in case of group control No. CODE No. SET TEMP. 2 : Sub…
-
(J)
Change the period of the filter timer ❏ a If the period of filter timer is not suitable (for example in case of dirty environment), the period can be half done as follows: Press the TEST / CHK button for more than 4 seconds. AIR FLOW UNIT FLAP MODE UNIT No. R.C. No. SET TEMP. CODE No. TIMER SET FAN…
-
Explanation of alarm messages Alarm message Possible cause of malfunction Serial communication errors Mis-setting Activation of protective device Error in receiving serial communication signal. (Signal from main indoor unit in case of group control) R.C. address on CCU (CR-DYPTG), indoor unit…
-
Possible cause of malfunction
Thermistor fault Indoor thermistor is either open or damaged. Outdoor thermistor is either open or damaged. Comp. CT detection current fault 3 EEP ROM on indoor P.C.B. failure Protective device for PC comp. Protective is activated. device for comp. is activated Protective device for AC comp. is…
-
2-2. System controller / SHA-KC64TG
ALL / ZONE / GR SELECT ALL MODE ZONE ZONE GROUP CENTRAL CTRL SET CL SET TEMP. °C SET TEMP. FAN SPEED CENTRAL CTRL FLAP 1 ON • OFF • TEST / CHK 668 _8132 ¶ Example of central control with system controller (individually controlled) Control wiring system System Remote controller controller (main)…
-
7 How to use the system controller
A: ALL / ZONE / GROUP SELECT button ALL / ZONE / GR SELECT B: ZONE select button ZONE C: GROUP select button GROUP K: CENTRAL CONTROL button CENTRAL CTRL L: SET button SET ALL ZONE GROUP A ZONE MODE FIXED A 7 15 SWEEP AIM MODE F: MODE button SET TEMP. G: Temperature setting buttons SET TEMP. °C 3…
-
7 Function of buttons (Continued)
D: ON/OFF operation button This button is for turning the selected air conditioner(s) on and off. E: Operation lamp This lamp lights when the appliance is turned on. F: MODE button Use this button to select one of the following four operations: (AUTO) A : Used to automatically set cooling or heating…
-
K: CENTRAL CONTROL button
Use this button to inhibit individual operation by remote controller for central control as follows: CENTRAL CTRL 1 : Inhibiting individual ON / OFF operation 2 : Inhibiting individual ON / OFF, MODE and SET TEMP operation. 3 : Inhibiting individual MODE and SET TEMP operation. No indication…
-
Display
A F ALL / ZONE / GR SELECT ZONE GROUP CENTRAL CTRL SET CL ALL ZONE GROUP A ZONE MODE FIXED STANDBY SET TEMP. CHECK E FAN SPEED SWEEP AIM B SET TEMP. °C A CENTRAL CTRL MODE C TEST CENTRAL CONTROL FLAP D ON • OFF • I TEST / CHK G H 3 0199_M_I Description A : When the unit is in the heating standby…
-
How to start individual operation
Press the SELECT button and select GROUP. 1 Select the ZONE No. including the group to be operated by pressing ZONE button. 2 To start individual operation Keep the power supply Power switch turned on more than 5 hours before starting operation. ALL / ZONE / GR SELECT ZONE Select the GROUP No. to be…
-
7 How to install the system controller
Installation site selection Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is completed. ● Install the system controller at a height of between 1 and 1.5 meters above the floor. ● Do not install the system controller in a place where it will be…
-
● Diagram of outer dimensions
Control unit 160 148 (6) 24 Unit: mm (6) Z 122 Mounting plate (for flush mounting) 4-ø 5 diameter holes (for mounting) 0215_M_I Hole for electrical wiring Hole for electrical wiring 6 Electrical component box Rear plate 4-ø 5.5 diameter holes (for mounting) 0216_M_I Z-view (black side) * In order to…
-
● Installation procedure
Mounting plate Electrical component box Hole for electrical wiring a): Normal mounting Rear plate b): Flush mounting 0217_M_I 1. Decide how the system controller will be mounted: in the normal manner or flush with the wall. a) To mount the system controller in the normal manner, remove the mounting…
-
7 Layout of electrical terminals
Clamp for electrical wiring Connector (CN02) for weekly timer (TM-WBGN: optional) CN02 Ground for power wiring P.C board C1 C2 L (L1) N (L2) B3 B2 B1 A3 A2 A1 C3 C4 1789_M_I How to connect electrical wiring 1) Basic wiring L (L1): Power supply ( 3 50 Hz / 60 Hz, 220 - 240 V) N (L2): C1: Inter-unit…
-
7 Basic wiring diagram
Make correct wiring without any mistakes (incorrect wiring will damage the equipment). CAUTION Outdoor unit–1 Outdoor unit–2 Outdoor unit–3 Outdoor unit–m m > System controller C1 C2 C3 C4 Power supply 220-240V 50Hz L N Ground Ground for control wiring In.–1 In.–2 In.–3 In.–4 Remote controller…
-
7 Control with multi (main / sub)
system controllers Address switch This controll is used for operating the unit(s) with multiple system controllers (up to two). CN2 CN1 1 OFF ON ON Bit No. BIT NO. OFF ON P.C. board of the control unit OFF System controller operates as System controller operates as sub-controller main controller 2…
-
7 How to set zone registration
To operate system controller properly, zone registration is required after finishing test run (after setting all indoor unit addresses) as following methods. (1) Zone registration by remote controller (RCS-SH80TG) (2) Zone registration by system controller (SHA-KC64TG) (3) Auto. zone registration by…
-
ZONE registration table
ZONE GROUP Indoor unit Central address address (UNIT No.) Unit location ZONE GROUP Indoor unit Central address address (UNIT No.) NOTE 3 4 Unit location 1. You should assign each indoor unit address to the desired position (Central address) manually. 2. In case of group control, only main indoor…
-
(1) Zone registration by remote controller (RCS-SH80TG)
❏ In this case confirming the indoor unit connected with the remote controller, you set the central address one by one. ❏ In case of remote controller–less system, connect remote controller to the system temporarily then follow this procedure. NOTE Indoor unit address must have been already set…
-
d
Set the central address which you want to set to this indoor unit address with the zone registration table , ( ) button according to For example, in case of left Indoor unit address : 1–8 AIR FLOW UNIT FLAP Central address MODE UNIT No. R.C. : 17 (ZONE 2, GROUP 1) No. CODE No. SET TEMP. TIMER SET…
-
Zone registration by system controller
❏ In this case you set all central addresses by system controller at once manually. a Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds. SETTING and CODE No. C1 will flush. b After confirming code No. C1, press the SET button. Once in this mode, a change takes place as…
-
c
Select the zone and group No. which you want to set with ZONE and d Set the UNIT No. (Indoor unit address) with FAN SPEED and FLAP buttons according to the zone registration table. e R.C. No. FAN SPEED button Indoor unit No. FLAP button , (GROUP) buttons. Press the SET button. GROUP No. turns ON and…
-
Auto. zone registration by system controller a Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds. SETTING and CODE No. C1 will flush. b , (SET TEMP) button and press the SET button. Select CODE No. C2 by pressing C2 changes from flashing to ON state and auto. zone…
-
How to check overlapping of central address No. a Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds. SETTING and CODE No. C1 will flash. b Select CODE No. C3 by pressing , (SET TEMP) button and press the SET button. C3 changes from flashing to ON state and SETTING will…
-
2-3. Weekly timer / TM-WBGN
Su Mo Tu We Th Fr Sa PROGRAM CHECK PROGRAM ON ERROR OFF DAY PROGRAM 1 CANCEL HH PROGRAM 2 MM PROGRAM 3 CLEAR CLOCK SET 682 _8132 ¶ The weekly timer is used, connected to remote controller (RCS-SH80TG), and system controller (SHA-KC64TG). ¶ ON / OFF can be easily set 3 times a day, in units of 1…
-
7 How to use the weekly timer
PROGRAM button Used to set the program operation CHECK button Used to check the operation reservation. DAY button Su Mo Tu We Th Fr Sa PROGRAM CHECK PROGRAM ON CANCEL button Used to cancel the temporary program operation and cancel this function. ERROR OFF DAY PROGRAM 1 CANCEL HH PROGRAM 2 MM…
-
(A) Setting the current time
(B) Setting the day ¶ Set the current time. (Ex: When the current time is 11 hrs. 45 min.) 1 Holding the SET button pressed, press the HH. button and adjust the current time. ¶ Set today’s day. (Ex: On Wednesday) 1 Holding the SET button pressed, press the DAY button and adjust the today’s day. ¶…
-
1 At first, press the program button
❚ ¶ The operation reservation display “ ” starts flashing as soon as the program button is pressed. 4 Set the OFF time by pressing the HH. and MM. buttons, and press SET button. Su Mo Tu We Th Fr Sa PROGRAM CHECK PROGRAM ERROR ON OFF DAY PROGRAM 1 CANCEL HH PROGRAM 2 Su Mo Tu We Th Fr Sa PROGRAM…
-
6 Finally, press the PROGRAM button
After setting, press the PROGRAM button within the next 30 seconds. (D) Set error If the “ERROR” starts flashing at the time of setting program operation, correct the time in the following way. 1 When the “ERROR” starts flashing, the ON time of error generated program also starts flashing. Su Mo Tu…
-
NOTE
¶ “ERROR” is displayed, if the ON / OFF times are set as follows. (1) If the operating times overlap Ex: ON OFF 0:00 23:59 ON OFF ON 1050_1143 OFF (2) If the OFF time is earlier than the ON time Ex: ON OFF 0:00 23:59 1051_1143 OFF ON (3) If the ON and OFF times are the same Ex: ON OFF 0:00 23:59 ON…
-
2 Press DAY button, and bring the operation reservation indicator “ ” at the day to be checked
❚ (E) Copying the program operating time At the time of setting program operation, if the operating time to be set is the same as that an already set another day, it can be copied here. ¶ Every time the DAY button is pressed, the operation reservation indicator “ ” starts flashing, and the operation…
-
¶ Description of operation
The operation is temporarily cancelled on the day which is set as a cancel day, but on the following day the cancel set indicator “I I” disappears automatically and operation reservation indicator “ ” is restored. (H) Clearing a program operation ¶ Clearing the program of the day Su Mo Tu We Th Fr…
-
(J) Others
Some information on this weekly timer 1. Power Failure If a power failure occurs during operation, and the power supply is later recovered, the display appears as shown on the right. (The colon “ : ” of current time flash). Su Mo Tu We Th Fr Sa PROGRAM CHECK PROGRAM ON ERROR OFF DAY PROGRAM 1 CANCEL…
-
7 How to install the weekly timer
Switch box for 1 (no cover) or switch box for 2 (no cover) Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is completed. Spacer M4 × 25 Screws (2) 7 Accessories Accompanying parts Weekly timer 1 Q’ty No. 1 5 Accompanying parts Spacer 2 654_8132…
-
7 Wiring diagram
(for wiring, always use the supplied wires) Timer terminal Weekly timer Test run setting ¶ After installation, check the output state of the weekly timer with the “FORCED OPR.” switch (OFF to ON) located on the rear side of its PCB. After confirming normal operation, turn the “FORCED OPR.” switch…
-
2-4. Simplified remote controller / RCS-KR1TG
7 How to use the simplified remote controller CENTRAL CTRL A STANDBY °C SET TEMP. TEST SETTING A CHECK SENSOR FAN SPEED SET TEMP. D: FAN SPEED selector button C: Temperature setting buttons ON - / OFF - MODE B: MODE button A: ON/OFF operation button FLAP TEST E: FLAP button G: TEST button 3 F…
-
D
FAN SPEED selector button (AUTO) (HI.) (MED.) (LO.) E: FLAP button A : : : : The air conditioner automatically decides the fan speed. High fan speed Medium fan speed Low fan speed 1. Use this button to set the airflow direction to a specific angle. ¶ In the cool mode and dry mode, if the flaps are…
-
Display (Remote controller)
A I CENTRAL CTRL A STANDBY H G B °C SET TEMP. C TEST SETTING A CHECK D SENSOR E FAN SPEED SET TEMP. F MODE ON - / OFF - FLAP TEST 3 1505_T_I Description A : This is displayed to indicate that the system controller is being used for control. When CENTRAL CTRL is flashing on the display, the operation…
-
7 How to install the simplified remote controller
When connecting the locally supplied three core lead wires to the terminal block, check the terminal numbers in the indoor unit to make sure that the wires are correctly connected. (The simplified remote controller is damaged if 220 / 240 V AC is applied.) Fit the simplified remote controller to the…
-
7 Basic wiring diagram
CAUTION Make correct wiring without any mistakes (incorrect wiring will damage the equipment). ¶ Following is a wiring diagram for controlling one indoor unit by two simplified remote controllers. Simplified remote controller (main) Simplified remote controller (sub) Option Option 3-pin terminal…
-
2. Optional
2-5. Indoor-use Relay Board / ACC-DC24SB Used for centralized control over various air conditioner operations from a remote location. Can be connected to all ECO indoor units. Input Indoor Board ¶ Three-way On/Off selection • Individual On/Off pulse signals (DC24V pulse signal) • On/Off pulse signal…
-
2. Optional Controller (remote sensor)
7 How to install the remote sensor Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is completed. 7 Accessories No. Accompanying parts (4) Q’ty No. 1 4 Remote sensor 1 Accompanying parts Q’ty Spacers 2 (comes with 200 mm wire) Under case (back…
-
2. Optional Controller (remote sensor)
7 How to wire the remote sensor ¶ Connection diagram Approximately 200 mm Terminal block for wiring the remote controller of the indoor unit 3P-1 3P-2 3P-3 RED WHT BLK ∗1 Remote sensor Power supply from remote sensor body Connector Remote sensor wiring (supplied locally) ∗1: 0.5 mm2 to 1.6 mm2 of…
-
Hook the AMY adapter to the fixture 7 Accessories Accompanying parts Q’ty No. Fixture Q’ty TYPE 3 TYPE 4 RS-232C cable Screws (4 × L12) For fixture 2 4 Screws for Nylon clamper 3 (3 × L8) Wall ¶ Dimension 260 Accompanying parts Nylon clamper 1 each No. ¶ Electrical specs. 65 3 Rated voltage…
-
7 Wiring diagram
(2) Connecting control wires. 2 2 Use two-core, 0.5 mm to 1.6 mm lead wire for AMY control wire. The limited length of control wire is 1,000 m in total. The control wire has no polarity. ¶ Do not thread the AMY control wire through a metallic pipe with power cord. ¶ Do not wire the power cord and…
-
¶ RS-232C cable
(2) Branch wiring If branching the inter-adapter control wiring, the number of branches should be 16 or less. (Branch length less than 1 m is not included in the total branch number.) RS-232C cable is used to connect between the terminals CN4 of the large P.C.B. in S-DDC and Host Computer. The cable…
-
NOTE
Main P.C.B. for S-DDC F1 7 Connection to the outside equipments Fuse 1 2 (1) Signal input for turn-off the all units. (Potential free normal open contact) <Inputting photo coupler> B A CN3 TB1 * ln case of Host Computer (Program) has CD (Carrier Detect) function, RS switch is always ON AMY control…
-
7 How to install the AMY adapter (SHA-KC3500G)
Hook the AMY adapter to the fixture 7 Accessories No. Accompanying parts Q’ty No. 1 Screws for Nylon clamper 3 (3 × L8) Fixture 1 Screws (4 × L12) For fixture ¶ Dimension 260 Q’ty Nylon clamper 2 200 Accompanying parts 1 ¶ Electrical specs. 65 Wall 3 Rated voltage : 220/230/ 240 V AMY adapter…
-
7 Wiring diagram
(2) Connecting control wires. 2 2 Use two-core, 0.5 mm to 1.6 mm lead wires for both AMY control and inter-unit control wires. The limited length of control wire is 1,000 m in total. The control wire has no polarity. ¶ Do not thread the AMY control and inter-unit control wires through a metallic…
-
7 Wiring procedure
Main P.C.B. for AMY adapter 1 2 AMY control wire connecting terminals 1 2 A B AMY control wire short plug for emergency A B 1 (Connect the short plug 2 from A side to B side.) 1861_M_I (When shipped (Emergency) from factory) To another AMY adapter To the terminal plate for inter-unit control wire in…
-
7 Switch setting
ON 7 Connection to the outside equipments SW1 SW2 (1) Signal input for turn-off the all units. (Potential free normal open contact) <Inputting photo coupler> 0 OFF TB2 5 D1 6 OFF Not defined. Test Mode: Use this switch Keep these switches always OFF always OFF Address setting (1-9) Pulse counter…
-
4. W-ECO MULTI SYSTEM Unit Specifications
1. Outdoor Unit IV - 3 1-1. Specifications IV 1-2. Major component specifications IV 1-3. Dimensional data IV 1-4. Refrigerant flow diagram IV 1-5. Noise criterion curves IV - 2. 4-Way Air Discharge Semi-concealed Type (X Type) IV - 25 2-1. Specifications IV 2-2. Major component specifications IV…
-
9. Floor-Standing Type (F Type) ...................................................... IV - 115
9-1. Specifications IV - 115 9-2. Major component specifications IV - 119 9-3. Dimensional data IV - 123 9-4. Noise criterion curves IV - 124 9-5. Air throw distance chart IV - 125 10. Concealed Floor-Standing Type (FM Type) IV - 126 10-1. Specifications IV - 126 10-2. Major component specifications…
-
1-1. Specifications
Unit specifications (A) MODEL No. Outdoor Unit SPW-CR1503GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity kW BTU / h Cooling Heating 45.0 50.0 154,000 171,000 3 Air circulation (Hi) m /min(cu. ft3/min) 310 (10,950) ELECTRICAL RATINGS Voltage rating VAC Available voltage range…
-
Unit specifications (B)
MODEL No. Outdoor Unit SPW-CR1903GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity kW BTU / h Cooling Heating 56.0 63.0 191,000 215,000 3 Air circulation (Hi) m /min(cu. ft3/min) 310 (10,950) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC - 456 Running amperes…
-
Unit specifications (C)
MODEL No. Outdoor Unit SPW-CR703GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity Cooling Heating kW 22.4 25.0 BTU / h 76,400 85,300 3 Air circulation (Hi) m /min(cu. ft3/min) 155 (5,470) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC Running amperes Running…
-
Unit specifications (D)
MODEL No. Outdoor Unit SPW-CR903GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity Cooling Heating kW 28.0 31.5 BTU / h 95,500 107,500 3 Air circulation (Hi) m /min(cu. ft3/min) 155 (5,470) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC - 456 Running amperes A…
-
Unit specifications (E)
MODEL No. Outdoor Unit SPW-C1503GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity kW BTU / h Cooling Heating 45.0 50.0 154,000 171,000 3 Air circulation (Hi) m /min(cu. ft3/min) 310 (10,950) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC Running amperes…
-
Unit specifications (F)
MODEL No. Outdoor Unit SPW-C1903GDYH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity kW BTU / h Cooling Heating 56.0 63.0 191,000 215,000 3 Air circulation (Hi) m /min(cu. ft3/min) 310 (10,950) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC - 456 Running amperes…
-
Unit specifications (G)
MODEL No. Outdoor Unit SPW-C703GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity Cooling Heating kW 22.4 25.0 BTU / h 76,400 85,300 3 Air circulation (Hi) m /min(cu. ft3/min) 155 (5,470) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC Running amperes Running…
-
Unit specifications (H)
MODEL No. Outdoor Unit SPW-C903GDCH8 POWER SOURCE 380 - 400 - 415 V / 3 N / 50Hz PERFORMANCE Capacity Cooling Heating kW 28.0 31.5 BTU / h 95,500 107,500 3 Air circulation (Hi) m /min(cu. ft3/min) 155 (5,470) ELECTRICAL RATINGS Voltage rating VAC Available voltage range VAC - 456 Running amperes A…
-
1-2. Major component specifications
-
Outdoor Unit (B)
-
Outdoor Unit (C)
MODEL No. SPW-CR703GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model … Code No. C-SCN753H8B 80976188 Nominal output kW 7.5 Compressor oil (ETHER FV68S) cc 2,700 Coil resistance Ω V - U: 1.308 (Ambient…
-
Outdoor Unit (D)
MODEL No. SPW-CR903GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model … Code No. C-SCN753H8C 80976288 Nominal output kW 7.5 Compressor oil (ETHER FV68S) cc 2,100 Coil resistance Ω V - U: 1.308 (Ambient…
-
Outdoor Unit (E)
-
Outdoor Unit (F)
-
Outdoor Unit (G)
MODEL No. SPW-C703GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model … Code No. C-SC753H8B 80975188 Nominal output kW 7.5 Compressor oil (ETHER FV68S) cc 2,700 Coil resistance Ω V - U: 1.308 (Ambient…
-
Outdoor Unit (H)
MODEL No. SPW-C903GDCH8 Source 380 - 440 - 415 V / 3 N / 50Hz Controller P.C.B. Ass’y CR - CR703GDH8 Control circuit fuse 250 VAC , 15 A Compressor SC (Scroll) Model … Code No. C-SC753H8C 80975288 Nominal output kW 7.5 Compressor oil (ETHER FV68S) cc 2,700 Coil resistance Ω V - U: 1.308 (Ambient…
-
1-3. Dimensional data
Detail of installation hole Installation hole (15 × 20 hole) SPW-CR703GDCH8 / C703GDCH8 SPW-CR903GDCH8 / C903GDCH8 1318 1198 Balance tube (ø9.52 flare connection) Drilling center for hole saw Max. diameter ø80 available Installation hole (4 - 15 × 20 hole) Refrigerant liquid line ø12.7 (narrow tube)…
-
2092 1198 1318 836 (Electrical component box) Electrical component box 2092 Installation hole (15 × 20 hole) 35 Detail of installation hole SPW-CR1503GDYH8 / C1503GDYH8 SPW-CR1903GDYH8 / C1903GDYH8 2050 57 2092 2132 2050 90 63 1100 CL ø60 knock out hole for power supply 2 Installation hole (4 - 15 ×…
-
Combinational dimension
-
1-4. Refrigerant flow diagram
SPW-CR1503GDYH8, SPW-CR1903GDYH8, SPW-C1503GDYH8, SPW-C1903GDYH8 HPV LPV valve valve PC compressor TH1 CM HP Accumulator High pressure switch ( ) ∗ TH2 CM HP ∗ High pressure switch Accumulator AC compressor Low pressure switch LP ∗ CM HP High pressure switch Oil separator Wide tube 150 type: ø38.1…
-
SPW-CR703GDCH8, SPW-CR903GDCH8, SPW-C703GDCH8, SPW-C903GDCH8
Accumulator High pressure switch Wide tube 90 type: ø28.58 70 type: ø25.4 Low pressure switch LP CM HP Fusible plug TH1 Oil separator LIV valve S S ( ) ( ) Narrow tube ø12.7 ( ) BALV valve High pressure port S Balance tube ø9.52 Low pressure port ( ) S BPV valve ( ) 4-way valve DFV valve TH4 S TH3…
-
1-5. Noise criterion curves
-
2-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-XR123GH56 / SPW-X123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase – 50Hz PERFORMANCE Cooling Heating 3.6 12,000 4.2 14,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 900 / 780 / 660 0.9 — ELECTRICAL…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-XR183GH56 / SPW-X183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 5.6 19,000 6.3 21,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 900 / 780 / 660 2.6 — ELECTRICAL RATINGS Voltage rating VAC…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-XR253GH56 / SPW-X253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 7.3 25,000 8.0 27,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 1,140 / 1,020 / 840 3.6 — ELECTRICAL RATINGS Voltage rating…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-XR363GH56 / SPW-X363GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 10.6 36,000 11.4 39,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 1,920 / 1,680 / 1,320 4.6 — ELECTRICAL RATINGS Voltage…
-
Unit specifications (E)
MODEL No. Indoor Unit SPW-XR483GH56 / SPW-X483GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 14.0 47,800 16.0 54,600 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 1,920 / 1,680 / 1,320 7.4 — ELECTRICAL RATINGS Voltage…
-
2-2. Major component specifications
Indoor unit (A) MODEL No. SPW-XR123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-X123GH56 CR-X253GH (Microprocessor) mm Turbo (1 … ø 490) W SFG6X-41A5P … 40 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance…
-
Indoor unit (B)
MODEL No. SPW-XR183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-X183GH56 CR-X253GH (Microprocessor) mm Turbo (1 … ø 490) W SFG6X-41A5P … 40 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
Indoor unit (C)
MODEL No. SPW-XR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-X253GH56 CR-X253GH (Microprocessor) mm Turbo (1 … ø 490) W SFG6X-41A5P … 40 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
Indoor unit (D)
MODEL No. SPW-XR363GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-X363GH56 CR-X253GH (Microprocessor) mm Turbo (1 … ø 490) W SFG6X-61A3P…60 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature…
-
Indoor unit (E)
MODEL No. SPW-XR483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-X483GH56 CR-X253GH (Microprocessor) mm Turbo (1 … ø 490) W SFG6X-61A3P…60 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature…
-
2-3. Dimensional data
Indoor unit : 12, 18, 25 Type 207 205 X-view (Ceiling opening) 590 (Suspention bolt pitch) (Suspention bolt pitch) 820 (Ceiling opening) 9 Panel center Air intake grille Air outlet Refrigerant liquid line [ø 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line ø 12.7: 12 type, ø…
-
Indoor unit : 36, 48 Type
X-view (Ceiling opening) (Suspention bolt pitch) 15 1150 790 12 1050 Panel center Air intake grille Air outlet Refrigerant liquid line (ø9.52) Refrigerant gas line (ø19.05) Drain connection Power supply entry For discharge duct Humidifier (option) mounting hole 9 Suspension bolt mounting 1020…
-
2-4. Noise criterion curves
MODEL : SPW-XR123GH56 , XR183GH56 MODEL : SPW-XR253GH56 SPW-X123GH56 , X183GH56 SOUND LEVEL : HIGH 37 dB(A), NC 30 LOW 30 dB(A), NC 22 CONDITION : Center, SOURCE : 220 - 230 - 240 V, SPW-X253GH56 SOUND LEVEL : HIGH 37 dB(A), NC 30 LOW Under the unit 1.5 m 1 Phase, 50 Hz NC 22 : Center, Under the…
-
2-5. Air throw distance chart
Model: 12, 18, 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0 AXIS AIR VELOCITY 0276_X_I Model: 36, 48 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0 AXIS AIR VELOCITY 0277_X_I : LOUVER ANGLE 20˚ in Cooling mode : LOUVER ANGLE 60˚ in…
-
3-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-SR93GH56 / SPW-S93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 2.8 9,600 3.2 11,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 540 / 485 / 410 1.0 — ELECTRICAL RATINGS…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-SR123GH56 / SPW-S123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 3.6 12,000 4.2 14,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 570 / 510 / 430 1.6 — ELECTRICAL RATINGS Voltage rating VAC…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-SR183GH56 / SPW-S183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 5.6 19,000 6.3 21,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 960 / 860 / 720 2.4 — ELECTRICAL RATINGS Voltage rating VAC…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-SR253GH56 / SPW-S253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 7.3 25,000 8.0 27,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 1,140 / 1,030 / 860 3.5 — ELECTRICAL RATINGS Voltage rating…
-
3-2. Major component specifications
Indoor unit (A) MODEL No. SPW-SR93GH56 Source SPW-S93GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 190) W UF4X-31B3P 30 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of…
-
Indoor unit (B)
MODEL No. SPW-SR123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-S123GH56 CR-X253GH (Microprocessor) mm Centrifugal (1…ø 190) W UF4X-31B3P 30 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
Indoor unit (C)
MODEL No. SPW-SR183GH56 Source SPW-S183GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (2 ø190) W KFG4X-51E3P 50 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V…
-
Indoor unit (D)
MODEL No. SPW-SR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-S253GH56 CR-X253GH (Microprocessor) mm Centrifugal (2 … ø 190) W KFG4X-51E3P 50 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
3-3. Dimensional data
Indoor unit : 9, 12 Type FOR DISCHARGE DUCT (1–ø150 SLIT HOLE) 1110 1110 1070 PANEL CENTER 510 330 INSPECTION PANEL FOR DRAIN PUMP 616 CEILING OPENING (1070 × 640) 640 SUSPENSION HOLES 680 FOR FRESH AIR INTAKE (ø125 HOLE) 140 INSPECTION PANEL FOR ECV, DRAIN PAN Refrigerant liquid line (ø 9.52)…
-
Indoor unit : 18, 25 Type
680 1390 32 4 INSPECTION PANEL FOR DRAIN PUMP 1390 1350 590 1176 PANEL CENTER 650 330 FOR DISCHARGE DUCT (2–ø150 SLIT HOLES) 616 CEILING OPENING (1350 × 640) 640 SUSPENSION HOLES 680 FOR FRESH AIR INTAKE (ø125 HOLE) Refrigerant gas line (ø 15.88) Drain connection (25 A. O.D.32 mm) Power supply entry…
-
3-4. Noise criterion curves
MODEL : SPW-SR93GH56 MODEL SPW-S93GH56 SOUND LEVEL : HIGH LOW 32 dB(A), SPW-S123GH56 NC 29 SOUND LEVEL : HIGH 33 dB(A), NC 29 25 dB(A), NC 21 LOW 26 dB(A), NC 22 : Center, SOURCE : 220 - 230 - 240 V, 1 Phase, Under the unit 1.5 m 50 Hz CONDITION : Center, SOURCE : 220 - 230 - 240 V, NC-70 60 NC-60…
-
MODEL
: SPW-SR183GH56 MODEL SPW-S183GH56 SOUND LEVEL : HIGH 34 dB(A), LOW SPW-S253GH56 NC 29 SOUND LEVEL : HIGH NC 24 LOW CONDITION : Center, SOURCE : 220 - 230 - 240 V, 1 Phase, Under the unit 1.5 m 50 Hz : 220 - 230 - 240 V, 1 Phase, NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF 20 NC-20…
-
3-5. Air throw distance chart
Model: 9, 12 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0 6 AXIS AIR VELOCITY 0282_S_I Model: 18 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0 6 AXIS AIR VELOCITY 0283_S_I Model: 25 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s)…
-
4-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-ASR93GH56 / SPW-AS93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Heating 2.8 9,600 3.2 11,000 m3 / h Air circulation (Hi / Me / Lo) Moisture removal (High) 480 / 420 / 360 Liters / h 1.1 — ELECTRICAL…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-ASR123GH56 / SPW-AS123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 3.6 12,000 4.2 14,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h 580 / 520 / 450 1.7 — ELECTRICAL RATINGS Voltage rating…
-
4-2. Major component specifications
Indoor unit (A) MODEL No. SPW-ASR93GH56 Source SPW-AS93GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 190) W UE6Q-21B3P … 20 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of…
-
Indoor unit (B)
MODEL No. SPW-ASR123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-AS123GH56 CR-X253GH (Microprocessor) mm Centrifugal (1 … ø 190) W UE6Q-21B3P … 20 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
4-3. Dimensional data
Indoor unit : 9, 12 Type Z * : Suspension bolt pitch : For ceiling opening 590** 620 4 - 12 × 652* 780** 60 287 483* Z View Refrigerant liquid line (ø 9.52) Refrigerant gas line (ø 12.7) Drain connection (25 A, O.D.32 mm) Power supply entry Suspension holes (4-15 × 30) For discharge duct (2-ø150)…
-
4-4. Noise criterion curves
MODEL : SPW-ASR93GH56 MODEL : SPW-ASR123GH56 SPW-AS93GH56 SPW-AS123GH56 SOUND LEVEL : HIGH 34 dB(A), NC 25 LOW 30 dB(A), NC 22 CONDITION : Center, SOURCE : 220 - 230 - 240 V, SOUND LEVEL : HIGH 38 dB(A), LOW Under the unit 1.5 m 1 Phase, 50 Hz NC 25 CONDITION : Center, SOURCE : 220 - 230 - 240 V, 1…
-
4-5. Air throw distance chart
Model: 9 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) AXIS AIR VELOCITY 0287_AS_I Model: 12 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) AXIS AIR VELOCITY 0288_AS_I 1: LOUVER ANGLE 10˚ in cooling mode 2: LOUVER ANGLE 20˚ in cooling mode 3…
-
5-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-KR93GH56 / SPW-K93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h Heating 2.8 9,600 3.2 11,000 450 / 390 / 340 1.3 — ELECTRICAL…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-KR123GH56 / SPW-K123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Heating 3.6 12,000 4.2 14,000 m3 / h Air circulation (Hi / Me / Lo) Moisture removal (High) 630 / 490 / 430 Liters / h 1.6 — ELECTRICAL RATINGS Voltage rating…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-KR183GH56 / SPW-K183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 5.0 17,000 6.0 20,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h 800 / 660 / 520 2.5 — ELECTRICAL RATINGS Voltage rating…
-
5-2. Major component specifications
-
Indoor unit (B)
-
Indoor unit (C)
-
5-3. Dimensional data
Indoor unit : 9, 12, 18 Type 205 A 360 1000 VIEW A 4 50 0289_K_I TYPE OF COPPER TUBE TUBE OUTER DIAMETER NARROW 9.52 mm (3 / 8 inch) 9, 12, 18 type WIDE NOTES 12.7 mm (1 / 2 inch) 9, 12 type 15.88 mm (5 / 8 inch) 18 type TD831077 IV - 65
-
5-4. Noise criterion curves
: SPW-KR93GH56 SPW-K93GH56 SOUND LEVEL : HIGH 38 dB(A), NC 33 LOW 30 dB(A), NC 25 CONDITION : Distance 1 m, Under the unit 1 m SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz MODEL : SPW-KR123GH56 SPW-K123GH56 SOUND LEVEL : HIGH 40 dB(A), NC 35 LOW 34 dB(A), NC 29 CONDITION : Distance 1 m, Under the unit…
-
5-5. Air throw distance chart
Model: 9 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0 AXIS AIR VELOCITY 0293_K_I Model: 12 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0294_K_I Model: 18 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0295_K_I…
-
6-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-TR183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h Heating 5.6 19,000 6.3 21,000 780 / 660 / 540 2.8 — ELECTRICAL RATINGS Voltage…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-TR253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h Heating 7.3 25,000 8.0 27,000 1,080 / 960 / 840 3.5 — ELECTRICAL RATINGS Voltage rating VAC 220 - 230…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-TR363GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h Heating 10.6 36,000 11.4 39,000 1,680 / 1,410 / 1,200 4.7 — ELECTRICAL RATINGS Voltage rating VAC 220…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-TR483GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3 / h Moisture removal (High) Liters / h Heating 14.0 47,800 16.0 54,600 1,920 / 1,680 / 1,320 7.0 — ELECTRICAL RATINGS Voltage rating VAC 220…
-
6-2. Major component specifications
Indoor unit (A) MODEL No. SPW-TR183GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (3 … ø 130) W SR4X-31A3P … 30 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
Indoor unit (B)
MODEL No. SPW-TR253GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (4 … ø 130) W SR4X-51A6P … 50 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature 20…
-
Indoor unit (C)
MODEL No. SPW-TR363GH56 Source 220 - 230 - 240 V / 1 phase / 50 Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (4 … ø 150) W KFG4X-101C6P…100 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature 20…
-
Indoor unit (D)
MODEL No. SPW-TR483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (4…ø150) W KFG4X-101C6P…100 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm. Ω…
-
6-3. Dimensional data
Indoor unit : 18, 25, 36, 48 Type I Hole for wall-through piping (View from front) C (Suspension bolt hole pitch) 35 500 or more 251 Air intake 4 250 Air outlet or more (Service space) A 250 or more Front (Service space) 89 N 670 L B M (Suspension bolt hole pitch) 141 J Holes in the rear unit (View…
-
6-4. Noise criterion curves
-
6-5. Air throw distance chart
Model: 18 Type HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 1224_T_I HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY 1225_T_I Model: 18 Type HORIZONTAL DISTANCE (m) 0 AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 5 AXIS AIR VELOCITY…
-
7-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-UR93GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 2.8 3.2 BTU / h 9,600 11,000 Capacity for Multi system (R22 and R407C) 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-UR123GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity for Multi system (R22 and R407C) Heating kW 3.6 4.2 BTU / h 12,000 14,000 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) 600 /…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-UR183GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity for Multi system (R22 and R407C) Heating kW 5.6 6.3 BTU / h 19,000 21,000 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) Pa…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-UR253GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity for Multi system (R22 and R407C) kW 7.3 8.0 BTU / h 25,000 27,000 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) Heating Pa…
-
Unit specifications (E)
MODEL No. Indoor Unit SPW-UR363GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 10.6 11.4 BTU / h 36,000 39,000 Capacity for Multi system (R22 and R407C) 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) Pa…
-
Unit specifications (F)
MODEL No. Indoor Unit SPW-UR483GHN56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 14.0 16.0 BTU / h 47,800 54,600 Capacity for Multi system (R22 and R407C) 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) Pa…
-
7-2. Major component specifications
Indoor unit (A) MODEL No. SPW-UR93GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 190) W KFG4X-51C3P … 50 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230…
-
Indoor unit (B)
MODEL No. SPW-UR123GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (1 … ø 190) W KFG4X-51C3P … 50 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature…
-
Indoor unit (C)
MODEL No. SPW-UR183GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 190) W KFG4X-51C3P … 50 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm.…
-
Indoor unit (D)
MODEL No. SPW-UR253GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (2 … ø 190) W KFC4X-71B5P … 70 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature…
-
Indoor unit (E)
MODEL No. SPW-UR363GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (3 … ø 190) W KFC4X-141A5P…160 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm.…
-
Indoor unit (F)
MODEL No. SPW-UR483GHN56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (3 … ø 190) W KFC4X-141A5P…160 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm.…
-
7-3. Dimensional data
Indoor unit : 9, 12, 18 Type (150) 780 (Suspension bolt pitch) P × 3 = 12-ø3.3 (Hole) Inspection access (450 × 450) (Field supply) (Suspension bolt pitch) (Air outlet duct flange) 11 260 (Air outlet duct flange) Refrigerant liquid line ø9.52 (narrow tube) Refrigerant gas line 9.12: ø12.7, 18: ø15.88…
-
Indoor unit: 25 Type
Inspection access (450 × 450) (Field supply) (150) 1080 (Suspension bolt pitch) (Suspension bolt pitch) 90 962 (Air outlet duct flange) 1000 16-ø3.3 (Hole) (Air outlet duct flange) Refrigerant liquid line ø9.52 (narrow tube) (Use the tube connector) Refrigerant gas line ø15.88 (wide tube) Upper…
-
Indoor unit: 36, 48 Type
(150) 75 65 1560 (Suspension bolt pitch) 335 115 1480 18-ø3.3 (Hole) Inspection access (450 × 450) (Field supply) P × 6 = 1380 (Suspension bolt pitch) 90 260 (Air outlet duct flange) 1442 (Air outlet duct flange) Refrigerant liquid line ø9.52 (narrow tube) Refrigerant gas line ø19.05 (wide tube)…
-
7-4. Noise criterion curves
-
MODEL
: SPW-UR363GHN56 MODEL : SPW-UR483GHN56 CONDITION : Under the unit 1.5 m CONDITION : Under the unit 1.5 m SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) SOUND LEVEL : HIGH 40 dB(A), NC 33 / LOW 33 dB(A)…
-
7-5. Increasing the fan speed
If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: (1) Electrical component box Booster cable Fan motor Booster cable…
-
8-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-DR253GH56 / SPW-D253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h 7.3 25,000 m3 / h Air circulation (Hi / Me / Lo) External static pressure (High) Heating 8.0 27,000 1,380 / 1,320 / 1,260 mmAq (Pa)…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-DR363GH56 / SPW-D363GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h 10.6 36,000 m3 / h Air circulation (Hi / Me / Lo) External static pressure (High) Heating 11.4 39,000 1,800 / 1,680 / 1,500 mmAq (Pa) Moisture removal (High) 18…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-DR483GH56 / SPW-D483GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Capacity kW BTU / h 14.0 47,800 m3 / h Air circulation (Hi / Me / Lo) External static pressure (High) Heating 16.0 54,600 2,160 / 2,100 / 1,980 mmAq (Pa) Moisture removal (High) 17…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-DR763GH5 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 22.4 25.0 BTU / h 76,400 85,300 Capacity 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) 3,360 / 3,190 / 2,980 11.1 — Pa (mmAq)…
-
Unit specifications (E)
MODEL No. Indoor Unit SPW-DR963GH5 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 28.0 31.5 BTU / h 95,500 107,500 Capacity 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h External static pressure (High) Pa (mmAq) 4,320 / 4,200 / 3,960 13.9…
-
8-2. Major component specifications
Indoor unit (A) MODEL No. SPW-DR253GH56 / SPW-D253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 220) W KFC4X-201B5P … 200 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of…
-
Indoor unit (B)
MODEL No. SPW-DR363GH56 / SPW-D363GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 220) W KFC4X-201B5P … 200 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m.…
-
Indoor unit (C)
MODEL No. SPW-DR483GH56 / SPW-D483GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 250) W KFC4Q-401A5P … 400 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m.…
-
Indoor unit (D)
MODEL No. SPW-DR763GH5 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (1 … ø 220) W KFC4X-201B5P … 180 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature…
-
Indoor unit (E)
MODEL No. SPW-DR963GH5 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 250) W KFC4X-401B3P … 400 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm.…
-
8-3. Dimensional data
Indoor unit : 25, 36, 48 Type A A B C 25, 36 type type Refrigerant liquid line [ø 9.52 (In case of B Drain pan × 100 = 700 22 - ø3.2 55 (Hole for full circumference) - ø3.2 (Hole for full circumference) × 100 = (Suspension bolt pitch) 4-ø20 Hole for suspension bolt) 81 1010 (Suspension bolt pitch)…
-
Indoor unit : 76, 96 Type
Refrigerant liquid line ø12.7 (narrow tube) Refrigerant gas line 76: ø25.4, 96: ø28.6 Power supply outlet Drain port (OD 32 mm) Duct connection for suction Duct connection for dicharge 4 - 37 × 12 (Hole for suspention bolt) 1170 (Suspention bolt pitch) 1100 71 364 (236) 1334 1428 364 67 1310 26-ø3.5…
-
8-4. Noise criterion curves
MODEL MODEL : SPW-DR253GH56 : SPW-DR363GH56 SPW-D253GH56 SPW-D363GH56 : HIGH 44 dB(A), NC 38 SOUND LEVEL : HIGH 45 dB(A), NC 39 CONDITION : Under the unit 1.5 m CONDITION : Under the unit 1.5 m SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz NC-70 60 NC-60 50…
-
: SPW-DR763GH56
MODEL : SPW-DR963GH56 SOUND LEVEL : HIGH 48 dB(A), NC 42 SOUND LEVEL : HIGH 51 dB(A), NC 43 CONDITION : Under the unit 1.5 m CONDITION : Under the unit 1.5 m SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE…
-
¶ Connect two units in parallel for each indoor unit. ¶ Attach the R.A.P. valve kit within 30 meters from the indoor unit. ¶ Secure the R.A.P. valve kit using hanging bolts, etc. ¶ Do not place the R.A.P. valve kit directly on the ceiling. 40 ¶ The R.A.P. valve kit is required when a multiple number…
-
8-6. Indoor fan performance
How to Read the Diagram The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR FLOW (m3/minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control. The name plate values are shown based on the “H” air flow. Therefore in the case of…
-
Increasing the Fan Speed (96 type only)
If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: (1) Electrical component box Booster cable Fan motor Booster cable…
-
9-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-FR93GH56 / SPW-F93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 2.8 3.2 BTU / h 9,600 11,000 Capacity 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h 420 / 360 / 300 1.3 – ELECTRICAL…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-FR123GH56 / SPW-F123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 3.6 4.2 12,000 14,000 Capacity kW BTU / h 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) 540 / 420 / 360 Liters / h 1.7 – ELECTRICAL RATINGS Voltage rating…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-FR183GH56 / SPW-F183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 5.6 6.3 19,000 21,000 Capacity kW BTU / h 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h 900 / 780 / 660 2.5 – ELECTRICAL RATINGS Voltage rating…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-FR253GH56 / SPW-F253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 7.1 8 24,000 27,000 Capacity kW BTU / h 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h 1,020 / 840 / 720 3.5 – ELECTRICAL RATINGS Voltage rating…
-
9-2. Major component specifications
Indoor unit (A) MODEL No. SPW-FR93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-F93GH56 CR-X253GH (Microprocessor) mm Centrifugal (1 … ø 153) W KFT6Q-11A3P … 15 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance…
-
Indoor unit (B)
MODEL No. SPW-FR123GH56 Source SPW-F123GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 153) W KFT4Q-21B3P … 20 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V…
-
Indoor unit (C)
MODEL No. SPW-FR183GH56 Source SPW-F183GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (2 … ø 153) W KFG4Q-61C3P … 60 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V…
-
Indoor unit (D)
MODEL No. SPW-FR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) SPW-F253GH56 CR-X253GH (Microprocessor) mm Centrifugal (2 … ø 153) W KFG4Q-61C3P … 60 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient…
-
9-3. Dimensional data
Indoor unit : 9, 12, 18, 25 Type Size A B C Narrow tube Wide tube 9, 12 1065 665 632 9.52 12.7 18,25 1380 980 947 9.52 15.88 Type Side panel Refrigerant tubing space for downward tubing C B A 156 67 Air outlet R Air inlet 54 Rear-tube outlet 0755_M _I 4-ø12 hole (For fastening the indoor unit to the…
-
9-4. Noise criterion curves
-
9-5. Air throw distance chart
9 Type Model: 12 Type HEATING 4.0 2.0 3.0 COOLING 3.0 2.0 4.0 1.0 5.0 0.0 0 1.0 2.0 3.0 4.0 5.0 6.0 HEATING 1.0 4.0 2.0 3.0 COOLING 3.0 2.0 4.0 1.0 5.0 0.0 FLOOR CEILING 5.0 HORIZONTAL DISTANCE (m) 0 1.0 2.0 3.0 4.0 5.0 0839_V_I Model: 18 Type Model: 25 Type CEILING 6.0 AIR OUTLET HEATING 0.0…
-
10-1.Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-FMR93GH56 / SPW-FM93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating kW 2.8 3.2 BTU / h 9,600 11,000 Capacity 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h 420 / 360 / 300 1.3 – ELECTRICAL…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-FMR123GH56 / SPW-FM123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 3.6 4.2 12,000 14,000 Capacity kW BTU / h 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) Liters / h 540 / 420 / 360 1.7 – ELECTRICAL RATINGS Voltage rating…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-FMR183GH56 / SPW-FM183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 5.6 6.3 19,000 21,000 Capacity kW BTU / h 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) 900 / 780 / 660 Liters / h 2.5 – ELECTRICAL RATINGS Voltage rating…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-FMR253GH56 / SPW-FM253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 7.1 8 24,000 27,000 Capacity kW BTU / h 3 Air circulation (Hi / Me / Lo) m /h Moisture removal (High) 1,020 / 840 / 720 Liters / h 3.5 – ELECTRICAL RATINGS Voltage rating…
-
10-2. Major component specifications
Indoor unit (A) MODEL No. SPW-FMR93GH56 Source SPW-FM93GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 153) W KFT6Q-11A3P … 15 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of…
-
Indoor unit (B)
MODEL No. SPW-FMR123GH56 Source SPW-FM123GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (1 … ø 153) W KFT4Q-21B3P … 30 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230…
-
Indoor unit (C)
MODEL No. SPW-FMR183GH56 Source SPW-FM183GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (2 … ø 153) W KFG4Q-61C3P … 60 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230…
-
Indoor unit (D)
MODEL No. SPW-FMR253GH56 Source SPW-FM253GH56 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (2 … ø 153) W KFG4Q-61C3P … 60 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230…
-
10-3. Dimensional data
Indoor unit : 9, 12, 18, 25 Type Size A B C D Narrow tube 9, 9.52 12.7 18,25 1173 1007 1002 980 9.52 15.88 Type Wide tube 56 100 D A 166 Air outlet 229 B C (Internal dimension) Air inlet 0756_M_I 4-ø12 hole (For fastening the indoor unit to the floor by screws.) Air filter Refrigerant connection…
-
10-4. Noise criterion curves
-
10-5. Air throw distance chart
9 Type Model: 12 Type HEATING 4.0 2.0 3.0 COOLING 3.0 2.0 4.0 1.0 5.0 0.0 0 1.0 2.0 3.0 4.0 5.0 6.0 HEATING 1.0 4.0 2.0 3.0 COOLING 3.0 2.0 4.0 1.0 5.0 0.0 FLOOR CEILING 5.0 HORIZONTAL DISTANCE (m) 0 1.0 2.0 3.0 4.0 5.0 0839_V_I Model: 18 Type Model: 25 Type CEILING 6.0 AIR OUTLET HEATING 0.0…
-
10-6. Indoor fan performance
How to Read the Diagram The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR FLOW (m3/minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control. The name plate values are shown based on the “H” air flow. Therefore in the case of…
-
11-1. Specifications
Unit specifications (A) MODEL No. Indoor Unit SPW-SLR93GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 2.8 9,600 3.2 11,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 840 (750)* / 630 / 540 0.6 — ELECTRICAL RATINGS…
-
Unit specifications (B)
MODEL No. Indoor Unit SPW-SLR123GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 3.6 12,000 4.2 14,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 870 (780)* / 660 / 570 1.3 — ELECTRICAL RATINGS Voltage rating VAC Available…
-
Unit specifications (C)
MODEL No. Indoor Unit SPW-SLR183GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 5.6 19,000 6.3 21,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 900 (810)* / 690 / 600 2.5 — ELECTRICAL RATINGS Voltage rating VAC Available…
-
Unit specifications (D)
MODEL No. Indoor Unit SPW-SLR253GH56 POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz PERFORMANCE Cooling Heating 7.3 25,000 8.0 27,000 Capacity kW BTU / h Air circulation (Hi / Me / Lo) m3/h Moisture removal (High) Liters/h 1200 (1110)* / 990 / 780 3.3 — ELECTRICAL RATINGS Voltage rating VAC…
-
11-2. Major component specifications
Indoor unit (A) MODEL No. SPW-SLR93GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (3) W SR4X - 31A3P... 30 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V…
-
Indoor unit (B)
MODEL No. SPW-SLR123GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (3) W SR4X - 31A3P... 30 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm. Ω Coil…
-
Indoor unit (C)
MODEL No. SPW-SLR183GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y Fan (Number…diameter) CR-X253GH (Microprocessor) mm Centrifugal (3) W SR4X - 31A3P... 30 W Fan motor Model…Nominal output Source No. of pole…r.p.m. (230 V, High) Coil resistance (Ambient temperature 20 °C) 220…
-
Indoor unit (D)
MODEL No. SPW-SLR253GH56 Source 220 - 230 - 240 V / 1 phase / 50Hz Controller P.C.B. Ass’y CR-X253GH (Microprocessor) Fan (Number…diameter) mm Centrifugal (4) W SFG4X - 51B5P... 30 W Fan motor Model…Nominal output Source 220 - 230 - 240 V / 1 phase / 50 Hz No. of pole…r.p.m. (230 V, High) rpm. Ω…
-
11-3. Dimensional data
Indoor unit : 9, 12, 18, 25 Type B C D E 9, 12, 18 Type 1233 1193 1089 1003 660 25 Type 1430 1390 1286 1200 900 635 A 28 D *: Suspension bolt pitch **: For ceiling opening 5 ø12 610 88 ø137 Air intake grille Air outlet Refrigerant liquid line (ø 9.52) Refrigerant gas line (ø 12.7: 9, 12 type, ø…
-
11-4. Noise criterion curves
-
11-5. Air throw distance chart
SPW-SLR93GH56 HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 2 AXIS AIR VELOCITY 1489_K_I SPW-SLR183GH56 HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 2 4 AXIS AIR VELOCITY 1490_K_I SPW-SLR253GH56 HORIZONTAL DISTANCE (m) AXIS AIR VELOCITY (m/s) VERTICAL…
-
5. Test Run and Others
1. Test Run V - 2 1-1. Test run procedure V - 2 1-2. Monitor and self-diagnostic function V - 4 1-3. Alarm messages on CCU (CR-DYPTG) V - 6 2. Electrical Work V - 10 2-1. Electrical wiring V - 10 2-2. Noise countermeasures of control wiring V - 11 3. Installation Standards Important V - 12 3-1.…
-
1-1. Test run procedure
Start Multiple remote control? Yes Turn on RCU. ADR switch of sub-remote controller No S006 S004 & S005 S002 & S003 CN031 (open*) : For link system Setting of CCU in PC unit NOTE *One of CN031 of all linked outdoor units should be short. Check the confirmation items before the test run Press the…
-
¶ Test run procedure in detail
● The following addresses will be set in EEPROM (IC8) on indoor P.C.B. after test run. (Data is not set when shipped from factory). Item Factory Setting data code setting data 0001 (unit No. 1) ~ 0030 (unit No. 30) R.C. address 12 0099 0001 (unit No. 1) ~ Max. value of indoor Indoor unit 13 0099…
-
1-2. Monitor and self-diagnostic function
7 Monitor function for CCU (CR-DYPTG) in PC unit By selecting the Item SW (S7) and Select SW (S8), the LED will display all the necessary information to be monitored. The monitored information stored in memory can be deleted by turning off the power supply. ¶ Location and name of LED on CCU in PC…
-
ITEM
SELECT SW (S7) SW (S8) 0~F 1~4 Message displayed Item RUN / ALARM LED MESSAGE LED 1 1~4 Display of connected RUN / ALARM LED Vertical LED : Lights up starting from 1 in sequence by display does not affect indoor unit pressing the Select switch each time monitored information. Horizontal LED : Lights…
-
1-3. Alarm messages on CCU (CR-DYPTG)
-
Remote
-
Outdoor unit
-
2. Electrical Work
2-1. Electrical wiring ¶ Do not mistake the polarities of the wiring for group control and central control. ¶ Take the power supply for indoor units separately in units of each outdoor unit. 7 Cautions on electrical work ¶ Regulations on wire diameters differ from locality to locality. For field…
-
2. Electrical Work
¶ Engineering method 2-2. Noise countermeasures of control wiring 1. Ground the shield on both sides (Fig. 2-1) 2. Install the unit 3 m away from any nearby high frequency equipment. * House the remote controller into an iron box, and its wiring into a wiring pipe or iron conduit. 3. Do not bundle…
-
3-1. Method of gas leak inspection after completing the tubing
1. Procedure Connect the indoor unit, tubing, and outdoor unit, and check for gas leakage according to the following procedure (also check the service valve and the sealing of spindle). Refrigerant tubing work (tube, indoor unit side) Check for pressure drop Pressurize nitrogen gas (3 15 kg/cm2 G)…
-
3-2. Check of density limit
Do not install the indoor unit to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air. The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set…
-
3-3. Precautions for new refrigerant installation
1. Care regarding piping 1-1. There is no need to change piping and tube wall thickness. Use refrigerant pipes of the same wall thickness as R22. Unit: mm Type Copper tube 0 Outer diameter 6.35 9.52 12.7 15.88 19.05 22.2 Wall thickness 0.8 0.8 0.8 1.0 1.0 1.2 41.3 44.45 Type Copper tube 1/2 H, H…
-
3-4. New refrigerant R407C cannot be used for existing models
1. Compressor specs are different. When refilling the R22 compressor with R407C, durability will significantly decrease since some of the materials used for compressor parts are different. 2. Existing piping cannot be used. Completely cleaning out residual refrigerating machine oil is impossible…
-
6. Processes and Functions
1. Compressor Control VI - 2 1-1. Compressor capacity control VI - 2 2. 3. 4. 5. 6. Protection Controls VI Fan Control VI Outdoor Electronic Expansion Valve VI Solenoid Valve Control VI Hot Gas Defrosting Control VI - 6-1. Frost detection VI - 7 6-2. Defrosting operation conditions VI - 8 6-3.…
-
1. Compressor Control
1-1. Compressor capacity control (1) Outdoor unit operation control ¶ The compressor capacity is calculated by the C.C.U. based on the operation capacities of the indoor units and the difference between the temperature setting and room temperature. This is designated as the C.C.U. target capacity…
-
2. Protection Controls
¶ If the C.C.U. target capacity decreases, the C.C.U. target capacity does not increase for one minute. ¶ If the outdoor unit capacity decreases, the capacity does not increase for one minute. However, the case in (6) under "1-1. Compressor capacity control" is an exception. (1) Discharge…
-
2. Protection Controls
(3) Coil temperature control 1 Evaporation temperature control The lowest of the E1, E2, and E3 temperatures of all indoor units whose cooling thermostat is on is designated as the minimum evaporation temperature (Te), and control is performed as shown in the table 7. This control is performed every…
-
3. Fan Control
(1) Outdoor fan mode Table 10 Table 11 [PC unit] [AD unit] Mode Fan No. 1 Fan No. 2 Mode Fan 8 7 High High 5 – High Medium 4 – 6 Medium Medium 3 High 5 Medium Low 2 Medium 4 Low Low 1 Low 3 High Stop 0 Stop 2 Medium Stop 1 Low Stop 0 Stop Stop * When fan No. 1 is set to Low, fan No. 2 cannot be set…
-
5. Solenoid Valve Control
¶ In solenoid valve control, in addition to the conditions shown below, multiple valves may be controlled at the same time. This is performed according to the respective control items. (1) Liquid valve control (LIVP, LIVA, LIVS) To properly control the discharge temperature, control is performed on…