Чиллеры AQCL с воздушным конденсатором и центробежными вентиляторами
AQCL 25-130. Чиллеры с центробежными вентиляторами. Технический каталог 2006г.
Смотрите также: Основной документ →
Загружаем документ…
Текст каталога
-
Air Cooled Water Chillers
-
Aqu@Logic Centrifugal Fan Air Cooled Water Chillers
The new range of AQCL air cooled water chillers with centrifugal fans is composed of 11 models covering a nominal cooling capacity range from 25 to 125 kW. As standard equipment, each unit has two compressors, fitted in AQCL represents a new generation of innovative air cooled water chillers…
-
General Specifications (continued)
Evaporator Electrical panel - Direct expansion type, made of brazed stainless steel plates. - The evaporator is surrounded by an electrical heating resistance and insulated with cellular polyurethane foam to provide antifreeze protection. Access to the electrical panel is possible after having taken…
-
ILTC Control System
- Water pump control with 2 possible operating modes: Continuous operation in ON / OFF mode or operating only in ON mode. - As standard, the ILTC control system offers the possibility of selecting a "Night-time running mode" function. When the "Night-time Running" mode is activated, four operating…
-
Refrigerant Flow Diagrams
AQCL 20 to 80 HPP FPC CPT AIR LPT PHE DL EWTS HR EPT SL FPE MI DF CPE LWTS TEV C2 C1 AQCL 100 to 130 FPC HPP CPT AIR LPT SI PHE DL HR EPT SL FPE MI DF CPE C1 EWTS LWTS TEV C2 COMPONENTS C1 Compressor 1 FPC C2 Compressor 2 FPE CPT Condensing pressure tap HPP DF Filter drier HR DL Discharge line LPT…
-
Operating Limits
Ambient air temperature (°C) Operating temperature ranges Standard unit operating range Outlet water temperature (°C) Operating limit data (*) TEMPERATURE Inlet water at start-up Inlet water during running Outlet water during running (without glycol) Water temperature difference Working pressure Air…
-
Hydraulic Circuit Diagrams
Basic version PHE AP CV WPG EWTS EWC DP FC SF PT DU HR FS FC CV WPG LWTS PT LWC DU DU Pack version PHE AP ET PU EWTS CV WPG EWC SV DP FC SF PT DU HR FS CV EAV WPG LWTS FC LWC DU COMPONENTS AP Automatic air purge valve CV Isolating valve DP Differential pressure switch (only on models 25/30/35) DU…
-
Physical Data
AQCL SIZES Power supply (V / Ph / Hz) 124.8 400/3+N/50 Cooling capacity (1) kW 24.9 28.8 33.7 39.6 46.2 56.3 67.5 76.5 99.1 113.7 Total power consumption with pump kW 12.3 13.7 15.0 16.8 22.7 26.6 29.6 33.1 42.8 46.1 49.8 Total power consumption kW 11.5 12.9 14.2 16.1 22.0 25.5 28.5 32.0 40.95 44.25…
-
Electrical Data
Unit with standard fan motors AQCL sizes Fuse aM type - (A) Full load current (max.) 400V - (A) 68.8 71 Starting current (max.) - (A) Unit with high static fan motors (optional) AQCL sizes Fuse aM type - (A) Full load current (max.) 400V - (A) 71.8 Starting current (max.) - (A) Compressors AQCL…
-
Sound Data
In-duct sound power levels at discharge side Units with standard fan motors and completely closed pulley Sizes 57.8 57.8 57.8 56.3 61.5 61.5 58.7 58.7 74.5 74.5 74.5 125 65.6 65.6 65.6 65.8 71.0 71.0 68.5 68.5 76.5 76.5 76.5 250 67.6 67.6 67.6 66.7 71.9 71.9 69.1 69.1 79.7 79.7 79.7 Frequencies (Hz)…
-
Performance Data
AQCL SIZES OUTDOOR AIR TEMPERATURE (°C) LWT (°C) Cool. Cap. (kW) Input Power (kW) Cool. Cap. (kW) Input Power (kW) Cool. Cap. (kW) Input Power (kW) Cool. Cap. (kW) Input Power (kW) Cool. Cap. (kW) Input Power (kW) Cool. Cap. (kW) Input Power (kW) Cool. Cap. (kW) Input Power (kW) 25.0 25.7 26.6 27.4…
-
Hydraulic Pump External Static Pressure
Models 25 & 30 ��� ��� ��� ��� �� �� �� � ���� ���� ���� ���� ���� WATER FLOW (l/s) Nominal (1) Minimum (2) Maximum (3) ���� MODEL 25 1.04 0.7 1.73 ���� ���� ���� ���� ���� MODEL 30 1.29 0.86 2.15 (1) Eurovent conditions, Water : 12/7 °C, Air : 35 °C. (2) With water ∆T : 7.5 K at nominal capacity.…
-
Hydraulic Pump External Static Pressure (continued)
Models 100, 1200 & kPa l/s WATER FLOW (l/s) Nominal (1) Minimum (2) Maximum (3) MODEL 100 4.74 3.16 7.90 MODEL 120 5.44 3.63 9.07 MODEL 130 5.97 3.98 9.95 (1) Eurovent conditions, Water : 12/7 °C, Air : 35 °C. (2) With water ∆T : 7.5 K at nominal capacity. (3) With water ∆T : 3 K at nominal…
-
Heat Exchanger Water Pressure Drop
-
Heat Exchanger Water Pressure Drop (continued)
Models 100, 120 & 130 1000 kPa l/s Page 15
-
Dimensions (mm)
-
таблицы и схемы — в просмотре
-
Water Connection Side and Electrical Access
Standard blowing Electrical access Water connections Vertical blowing Electrical access Water connections Opposite blowing Electrical access Water connections Page 18
-
Water Connections
AQCL 25-30-35 ����� ��� ��� ����� Water in Water out Note : Water connections are inside the unit. AQCL 100-120-130 AQCL 40-50-60-70-80 B 318 Water in 300 318 Water in 50 A 366 Water out Note : Water connections exceed about 50 mm to exterior. Water out AQCL A sizes (mm) B (mm) 202.5 202.5 202.5 306…
-
Minimum Clearance Around the Unit
AIR 500 1000 AIR 500 1000 1000 Electrical access Water connections Dimensions in mm. As par Your distributor : CAC Export Department 42 cours Jean-Jaurès 17800 Pons - France Tel. : +33 (0)5 - Fax : +33 (0)5