YMC2 - ALL MODELS
ENGINEERING GUIDE Revision 0 Form 160.78-EG1.EN.CE/PED (1010) MAGNETIC BEARING CENTRIFUGAL LIQUID CHILLERS STYLE A (735 - 1350 KW) R134a
-
INTRODUCTION
Real-World Energy Performance SUSTAINABILITY Johnson Controls pioneered the term “Real-World Energy” to illustrate the energy-saving potential of focusing on chiller performance during off-design conditions. Offdesign conditions are not only seen at part load, but at full load operation as well, by…
-
SUSTAINABILITY
Quiet Operating Range with Magnetic Bearing Technology Lower Direct and Indirect Environmental Impact. 98% of the Global Warming Potential (GWP) of a centrifugal chiller is from the indirect effect – the greenhouse gases produced to produce the electricity to run the chiller. 2% of the GWP is from…
-
RATINGS
COMPUTERIZED PERFORMANCE RATINGS COLDER COOLING TOWER WATER TEMPERATURES Each chiller is custom-matched to meet the individual building load and energy requirements. A variety of standard heat exchangers and pass arrangements are available to provide the best possible match. The YORK YMC2 chillers…
-
OPTIVIEW CONTROL CENTRE
The YORK OptiView Control Centre, furnished as standard on each chiller, provides the ultimate in efficiency, monitoring, data recording, chiller protection and operating ease. The OptiView Control Centre is a factory-mounted, wired and tested state-of-the-art microprocessor based control system for…
-
for greater efficiency and less chiller cycling. The chiller
cycles off when the leaving chilled water temperature is below setpoint and is adjustable from 0.55°C below to a minimum of 2.2°C. Restart is adjustable from setpoint up to a max of 44.4°C. The panel will check for flow to avoid freeze up of the tubes. If flow is interrupted shutdown will occur…
-
The TREND COMMON SLOTS screen displays the
Master Slot Numbers List of the monitored parameters. DISPLAY MESSAGES The OptiView Control Centre continually monitors the operating system displaying and recording the cause of any shutdowns (Safety, Cycling or Normal). The condition of the chiller is displayed at the System Status line that…
-
UNIT COMPONENTS
OPTISPEED OPTIVIEW OPTISPEED OPTIVIEW 9
-
MECHANICAL SPECIFICATIONS
GENERAL YORK YMC2 Centrifugal Liquid Chillers are completely factory-packaged including the evaporator, condenser, compressor, motor, Variable Speed Drive (VSD), control centre, and all interconnecting unit piping and wiring. The initial charge of refrigerant is supplied for each chiller. When the…
-
• 3-phase output current
• Input kVA • Input Power (kW) • Kilowatt-Hours (kWH) • Input Voltage Total harmonic Distortion (THD) • Input Current Total Demand Distortion (TDD) • Self diagnostic service parameters HEAT EXCHANGERS Shells Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion…
-
water temperature. The sophisticated program and sensor
monitors the chiller water temperature to prevent freezeup. When needed, Hot Gas Bypass control is available as an option. The panel displays countdown timer messages so the operator knows when functions are starting and stopping. Every programmable point has a pop-up screen with the allowable…
-
CODES AND STANDARDS
Chillers conform Directives: with the FACTORY INSULATION OF EVAPORATOR following European • Machinery directive (2006/42/EC) • EMC Directive (2004/108/EC) • Pressure Equipment Directive (97/23/EC) • Safety Code for Mechanical Refrigeration (EN378-2 (2008)) ISOLATION MOUNTING The unit is provided…
-
WATER CIRCUITS
Flow Rate – For normal water chilling duty, evaporator and condenser flow rates are permitted at water velocity levels in the heat exchangers tubes of between 0.91 m/s (1.0 m/s for condensers) and 3.66 m/s. Two pass units are also limited to 134 kPA water pressure drop. Three pass limit is 201 kPA.…
-
WATER FLOW RATE LIMITS (l/s) — BASED UPON
STANDARD TUBES @ DESIGN FULL LOAD CONDITIONS EVAPORATOR MODEL 1 PASS MIN MAX 2 PASS MIN MAX CONDENSER 3 PASS MIN MODEL MAX 1 PASS 2 PASS 3 PASS MIN MAX MIN MAX MIN MAX CA2110-BS CA2110-CS CA2110-DS CA2110-ES CA2110-2S CA2110-3S EA2510-BS CA2510-BS EA2510-CS CA2510-CS EA2510-2S CA2510-DS EA2510-3S…
-
MULTIPLE UNITS
Selection – Many applications require multiple units to meet the total capacity requirements as well as to provide flexibility and some degree of protection against equipment shutdown. There are several common unit arrangements for this type of application. The YORK YMC2 chiller has been designed to…
-
on request. Control of sound and vibration transmission
must be taken into account in the equipment room construction as well as in the selection and installation of the equipment. THERMAL INSULATION No appreciable operating economy can be achieved by thermally insulating the chiller. However, the chiller’s cold surfaces should be insulated with a vapour…
-
NOMENCLATURE
Unit Nomenclature Position: 1,2,3,4 Compressor Nomenclature - 5 6,7,8,9 10 11 YMC2 Position: 1,2 M1 Chi ller Model Single Stage Compressor Capacity in KW S # # ## A 3 - Motor Motor Revision Level Impeller A # # # Refrigerant HFC R-134a A Mod Level Forward Rotation F A Impeller Design Revision Level…
-
DIMENSIONS - UNIT
VSD VSD COMPRESSOR CONTROL PANEL CONTROL PANEL MOTOR J H B C M 3-3/8” D F (EVAP.) A E G (EVAP.) ADDITIONAL OPERATING HEIGHT CLEARANCE TO FLOOR TYPE OF CHILLER MOUNTING M NEOPRENE PAD ISOLATORS 45 SPRING ISOLATORS 1" DEFLECTION 25 DIRECT MOUNT 19 DIMENSIONS (MM) EVAPORATOR CODE CONDENSER CODE A B C D…
-
DIMENSIONS - EVAPORATOR NOZZLE ARRANGEMENTS
(COMPACT WATER BOXES) EVAPORATORS – COMPACT WATER BOXES FRONT OF UNIT 1-PASS 1-PASS NOZZLE ARRANGEMENTS NO. OF PASSES AA EVAPORATOR IN OUT LEFT END RIGHT END RIGHT END LEFT END AA FLOOR LINE M 1 C RIGHT END C LEFT END M FRONT OF UNIT 2-PASS 2-PASS NOZZLE ARRANGEMENTS BB BB AA FLOOR LINE 2 EE M C EE…
-
EVAPORATORS – COMPACT WATER BOXES
F F ONE PASS G F TWO PASS F F THREE PASS DIMENSION (MM) EVAPORATOR SHELL CODE F G EA25 359 160 NOTES: 1. Standard water nozzles are furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or use of ANSI/AWWA C-606 couplings. Factory-installed, class 150…
-
DIMENSIONS - CONDENSER NOZZLE
ARRANGEMENTS (COMPACT WATER BOXES) CONDENSERS – COMPACT WATER BOXES FRONT OF UNIT 1-PASS 1-PASS NOZZLE ARRANGEMENTS AA FLOOR LINE 1 C M CONDENSER NO. OF PASSES AA C RIGHT END LEFT END IN OUT LEFT END RIGHT END RIGHT END LEFT END M FRONT OF UNIT 2-PASS 2-PASS NOZZLE ARRANGEMENTS BB BB AA CONDENSER…
-
CONDENSERS – COMPACT WATER BOXES
F F ONE PASS G F TWO PASS F F THREE PASS DIMENSION (MM) CONDENSER SHELL CODE H J CA21 349 148 CA25 349 160 NOTES: 1. Standard water nozzles are furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or use of ANSI/AWWA C-606 couplings.…
-
DIMENSIONS - EVAPORATOR NOZZLE ARRANGEMENTS
(MARINE WATER BOXES) EVAPORATORS – MARINE WATER BOXES FRONT OF UNIT 1-PASS 1-PASS NOZZLE ARRANGEMENTS NO. OF PASSES AA AA FLOOR LINE M 1 C RIGHT END C LEFT END EVAPORATOR IN OUT LEFT END RIGHT END RIGHT END LEFT END M FRONT OF UNIT 2-PASS 2-PASS BB BB NOZZLE ARRANGEMENTS AA EVAPORATOR NO. OF PASSES…
-
EVAPORATORS – MARINE WATER BOXES
F 1-PASS 2-PASS 3-PASS EVAPORATOR SHELL CODE F I F I G F I EA25 NOTES: 1. 2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of furnished. 3. One-, two-, and three-pass nozzle arrangements are available only in pairs…
-
DIMENSIONS - CONDENSER NOZZLE ARRANGEMENTS
(MARINE WATER BOXES) CONDENSERS – MARINE WATER BOXES FRONT OF UNIT 1-PASS 1-PASS NOZZLE ARRANGEMENTS AA AA CONDENSER NO. OF PASSES FLOOR LINE 1 C RIGHT END C M LEFT END M IN OUT LEFT END RIGHT END RIGHT END LEFT END FRONT OF UNIT 2-PASS 2-PASS BB BB NOZZLE ARRANGEMENTS 2 C M EE CONDENSER NO. OF…
-
CONDENSERS – MARINE WATER BOXES
F 1-PASS 2-PASS 3-PASS CONDENSER SHELL CODE F I F I G F I CA21 CA25 NOTES: 1. 2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option are not furnished. 3. One-, two-, and three-pass nozzle arrangements are available only…
-
WEIGHTS
APPROXIMATE UNIT WEIGHT*(MAX TUBE COUNT USING COMPACT WATERBOXES) COMPRESSOR EVAPORATOR M1-197FAA M2-205FAA SHIPPING WEIGHT (KG) CONDENSSER OPERATING WEIGHT (KG) EST. REFRIGERANT CHARGE (KG) 1 EA2510 CA2110 6315 6970 260 EA2510 CA2510 6755 7605 285 EA2514 CA2514 7855 8990 390 EA2510 CA2110 6435 7130…
-
NOTES
-
www.johnsoncontrols.com
Form No. 160.78-EG1.EN.CE/PED (1010) Revision 0 Subject to change without notice. ALL RIGHTS RESERVED