ENGINEERING GUIDE Revision 6 PC155-100 (GB 0510) WATER COOLED LIQUID CHILLER AND REMOTE AIR COOLED CHILLER R134a
-
Features
York YLCS Water Cooled Screw Chillers are a compact design suitable for water or water-glycol cooling. Models are available in three versions: • Standard units (SA), • Units for applications requiring high condensing temperatures (HA) • Units for applications where remote condensers are necessary…
-
Specification
General YLCS models shall be completely assembled with all interconnecting refrigerant piping and internal wiring, ready for field installation. SA and HA units shall be pressure tested, evacuated, and fully factory charged with refrigerant and oil in each of the independent refrigerant circuits.…
-
Refrigerant Circuits
An independent refrigerant circuit shall be provided per compressor. Liquid line components shall include: manual shut-off valve with charging port, high absorption removable core filter-drier, solenoid valve, sight glass with moisture indicator, and thermostatic expansion valve. Suction lines…
-
Accessories and Options
ENTRY – Enter set point changes, cancel inputs, advance day, and change AM/PM. SET POINTS – Chilled liquid temperature, chilled liquid range, remote reset temperature range. CLOCK – Time, daily or holiday start/stop schedule, manual override for servicing. PRINT – Operating data or system fault…
-
Power Factor Correction
Factory mounted passive (static) correction capacitors to correct unit compressor power factors to 0.95 (depending on operating conditions). Flow Switch Switch with 1 inch BSP thread suitable for 10 barg DWP and having gold contacts for low voltage/current, to protect unit from loss of water flow.…
-
Operating Limitations
0350 Min. Max. YLCS Models SA - HA - AA Liquid outlet temperature (water) Liquid outlet temperature (glycol) (3) Chilled Liquid outlet temperature range Liquid Flow rate Pressure drop Maximum working pressure Liquid outlet temperature Liquid outlet temperature range Cooling Total flow rate (2)…
-
Refrigeration Flow Diagram (YLCS 0350 to 0620 Models)
Evaporator PRV (2) EVAPORATOR TEV LLV S SV T Condenser PRV (2) Not fitted to YLCS AA models CONDENSER Discharge PRV (1) (2) Compressor PRV (2) PT SV s NOTES: 1 - See Discharge Pressure Relief Valve Table 2 - See Pressure Relief Valve Options Table COMPRESSOR Liquid Injection Option Start Bypass…
-
Model
SA System 2 No Valve No Valve Valve Valve Valve Valve Valve Valve Valve Valve Valve HA & AA System 1 System 2 No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve No Valve Valve No Valve Valve Valve…
-
Selection Guide - Water
Data Required To select a YORK YLCS chiller the following information is required: 1. Design cooling capacity. 2. Chilled water entering and leaving temperatures. 3. Condenser water entering and leaving temperature. 4. Chilled water flow (l/s) if one of the temperatures in (2) is unknown. 5.…
-
Condenser Pressure Drop (figure 4)
-1 Flow Rate [l/s] Pressure Drop Calculations (Table 3) Pressure drop calculated as following: 10 with Δp = a . qv ^ b 8 10 0350 0415 0480 0530 0575 0620 0670 0750 0860 0980 1120 0 -0 -0 -0 Flow Rate [l/s] Δp : pressure drop [kPa] qv : flow rate [l/s] a, b: factors (see table here below) Evaporator…
-
Selection Guide - Glycol (HA Models Only)
Data Required To select a YORK YLCS-HA chiller the following information is required: 1. Design cooling capacity. 2. Chilled glycol entering and leaving temperatures. 3. Condenser water entering and leaving temperature. 4. Chilled glycol flow (l/s) if one of the temperatures in (2) is unknown. 5.…
-
Glycol Factors (Table 5)
Glycol Concentrations Factors (Table 7) Ethylene Glycol Propylene Glycol LCLT °C % by Weight 10 10 0.2404 0.2515 0.2577 0.2734 0.2876 10 1.045 1.020 1.070 1.025 5 0.2399 0.2510 0.2579 0.2753 0.2906 20 1.020 1.010 1.040 1.015 0 0.2397 0.2505 0.2581 0.2772 0.2916 30 1.000 1.000 1.000 1.000 -5 0.2394…
-
LCLT
-
Model Refrigerant circuits Refrigerant Circuit 1 Charge Circuit 2 Circuit 1 Oil Charge Circuit 2 Compressor Number Type (circuit 1) Type (circuit 2) Capacity Control Evaporator Number Type Water volume Victaulic connection sizes Condenser Number Type Water volume (each) BSPPint / Victaulic…
-
Electrical Data - Unit (SA)
Nominal Running Maximum Running AMPS AMPS @ 380 V 0415 0480 0530 0575 0620 0670 0750 0860 0980 1120 34 @360 V @ 380 V @ 400 V Without Power Factor Correction Model YLCS SA 0350 @ 400 V With Optional Power Factor Correction fitted GB
-
Electrical Data - System (SA)
-
Electrical Data - Unit (HA/AA)
Nominal Running Maximum Running AMPS AMPS @ 380 V @ 400 V @360 V @ 380 V Model Without Power Factor Correction YLCS SA With Optional Power Factor Correction fitted 0350 0415 0480 0530 0575 0620 0670 0750 0860 0980 1120 Notes: Nominal: Maximum: @ 400 V (1) @ 7°C leaving liquid temperature and 45°C…
-
Electrical Data - System (HA/AA)
-
YLCS 0350 SA Capacity stage number 8 Temp. °C Cycling coefficient 0.9 30 Weighting coefficients 25 % - 50 % - 75 % - 100 % 0.23 - 0.41 - 0.33 - 0 .03 ESEER 26 5.14 22 18 YLCS 0415 SA Capacity stage number 8 Temp. °C Cycling coefficient 0.9 30 Weighting coefficients 25 % - 50 % - 75 % - 100 % 0.23…
-
YLCS 0670 SA Capacity stage number 8 Temp. °C Cycling coefficient 0.9 30 Weighting coefficients 25 % - 50 % - 75 % - 100 % 0.23 - 0.41 - 0.33 - 0 .03 ESEER 26 5.58 22 18 YLCS 0750 SA Capacity stage number 8 Temp. °C Cycling coefficient 0.9 30 Weighting coefficients 25 % - 50 % - 75 % - 100 % 0.23…
-
SOUND PRESSURE (dB) Model SA/HA/AA dB A SWL 63Hz 125Hz 250Hz 500Hz 0350 0415 0480 0530 0575 0620 0670 0750 0860 0980 1120 1000Hz 2000Hz 4000Hz 8000Hz Total (dB A) EN 292-1991 SWL = Sound Power Level Notes: 1. Sound Power tolerance is + 3 dB as per Eurovent Specification. 2. Frequency band tolerances…
-
Q
-
Dimensions
-
Power Supply Connection Diagrams
3 50HZ 380/400V L1 L2 L3 PE QRESB Standard Single Point Power Supply One supply to master non-fused disconnect switch QCSISD with internal power distribution to system fuses and control supply non-fused disconnect switch QCSD/ESD CS 1 PS PE 2 PS CIS -QCSD/ESD U -APB 1-F V W 3 4 2-F -ARB -QCSISD -AMB…
-
Power Supply Connection Diagrams (Continued)
3 50HZ 380/400V L1 L2 L3 PE QRESB Single Point Power Supply (Option) One supply to master non-fused disconnect switch QCSISD with internal power distribution to system fused disconnect switches QSDF and control supply non-fused disconnect switch QCSD/ESD CS 1 PS PE 2 PS CIS -QCSD/ESD U -APB QSDF…
-
Customer Connection Diagram
1 PS 2 PS CIS APB CS AMB ARB } } } } } } PS POWER SECTION CS CONTROL SECTION CIS COMMON INPUT SECTION ARB RELAY BOARD AMB MICRO BOARD APS POWER SUPPLY BOARD Chilled Liquid Pump Start Unit Run Signal Open on Alarm Close on Alarm Open on Alarm Close on Alarm } System N° 2 } System N° 1 Note Remote…
-
Clearances
The recommended clearances below are the distances between the edge of the unit and the architectural enclosure surrounding the unit. The clearances allow for access of the control panel and for component removal. 1.0 m 1m 3m CONTROL PANEL 1.3 m Notes: Clearances around the unit are recommended for…
-
www.johnsoncontrols.com
PC155-100 Rev.6 (0510) Subject to change without notice. Supersedes: PC155-100 Rev.5 (0609) ALL RIGHTS RESERVED