Installation and Maintenance Manual
Water Cooled Water Chillers, Water-to-Water Reverse Cycle Heat Pumps. Models CWP / CWP-HP 02 to 35 with HCFC 22 and HFC 407C F GB R IMW 910.2M/12.01 Supersedes : IMW 910.1E/01.00
-
Table of Contents
Introduction p. 3 Safety Precautions p. 3 General p. 4 Physical Data p. 4 Electrical Data p. 6 Dimensional Data p. 7 Installation p. 9 Unit Handling p. 9 Unit Placement p. 9 Service Access p. 9 Vibration Isolators p. 9 Water Piping p. 10 Flow Switch p. 10 Refrigerant Charge p. 11 Glycol Solution p.…
-
1 - Introduction
The purpose of this manual is to provide the installation, start-up, operating and maintenance rules to the users of water cooled water chillers and water-to-water reverse cycle heat pumps. It does not give a full description of all maintenance works assuring the long life and reliability of this…
-
3 - General
are carefully checked and tested, with pure water having positive temperature, in accordance with normal operating conditions. 3.1 - Description The cooling only and heat pump chillers 02 to 35 are designed for indoor installations. Each unit consists of hermetic compressor(s), insulated plate type…
-
4 - Physical Data (cont'd)
Cooling only models Nominal cooling capacity (1) - HCFC 22 Nominal power input (1) - HCFC 22 Nominal cooling capacity (1) - HFC 407C Nominal power input (1) - HFC 407C Number of refrigerant circuit Refrigerant charge HCFC 22 / HFC 407C Compressor Type / Number No of capacity reduction steps…
-
4 - Physical Data (cont'd)
Heat pump models Nominal heating capacity (1) - HCFC 22 Nominal power input (1) - HCFC 22 Nominal heating capacity (1) - HFC 407C Nominal power input (1) - HFC 407C Nominal cooling capacity (1) - HCFC 22 Nominal power input (1) - HCFC 22 Nominal cooling capacity (1) - HFC 407C Nominal power input…
-
6 - Dimensional Data
Cooling only and Heat pump 02 to 21 Side view Front view Evaporator inlet : 1"1/4 male (sizes 02 to 09) or 1"1/2 male (sizes 15 to 21) 1 Evaporator outlet : 1"1/4 male (sizes 02 to 09) or 1"1/2 male (sizes 15 to 21) 2 Condenser inlet : 1"1/4 male (sizes 02 to 09) or 1"1/2 male (sizes 15 to 21) 3…
-
6 - Dimensional Data (cont'd)
Cooling only and Heat pump 25 to 35 Front view Rear view Side view 1 Evaporator inlet : 2" male 3 Condenser inlet : 2" male 2 Evaporator outlet : 2" male 4 Condenser outlet : 2" male For heat pump models, make provision for a flow switch per water circuit and water connections must be made as…
-
7 - Installation
7.1 - Unit Handling Blocking required across full width Warning Sharp edges are a potential injury hazard. Avoid contact with them. Be careful to avoid rough handling of the unit. Do not push or pull the unit anything other than the base. Block the pushing vehicle away from the unit to prevent…
-
7 - Installation (cont'd)
7.5 - Water Piping 3 2 Local authorities can supply the installer with the proper building and safety codes required for safe and proper installation. 6 Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the following when installing water piping: 6 1. 2.…
-
7 - Installation (cont'd)
Note : The effect of glycol in the condenser is negligible. As 7.7 - Refrigerant Charge glycol increases in temperature, its characteristics have a All units are designed for use with HCFC 22 and HFC 407C. See nameplate for specific refrigerant used. Units are shipped with an operating charge.…
-
8 - Evaporator Water Pressure Drop Curves
Water flow rate calculation : q m with : = P × 860 ∆ t × 3600 q m water flow in l/s P capacity in kW D t water delta T in °C Curve 1 : Cooling only 02 and Heat pump 02 Curve 2 : Cooling only 03 & 04 and Heat pump 03 & 04 Curve 3 : Cooling only 05 & 06 and Heat pump 05 & 06 Curve 4 : Cooling only 07…
-
9 - Condenser Water Pressure Drop Curves
Water flow rate calculation : q m with : = P × 860 ∆ t × 3600 q m water flow in l/s P capacity in kW D t water delta T in °C Curve 1 : Cooling only 02 & 03 and Heat pump 02. Curve 2 : Cooling only 04 & 05 and Heat pump 03 & 04. Curve 3 : Cooling only 06 & 07 and Heat pump 05 & 06. Curve 4 : Cooling…
-
10 - Controls
10.1 - Temperature Controller 10.4 - Heat Exchanger Heater Thermostat The controller fitted on the cooling only and heat pump units 02 to 35 is factory calibrated for operation on return water temperature. For this reason, the controller sensor is located at the evaporator inlet in order to control…
-
11 - Field Wiring
Wiring must be in accordance with all applicable codes and regulations. Warranty is void if wiring does not comply with specifications. A blown fuse indicates a short, ground or overload. Before replacing a fuse or restarting a compressor, find and correct the trouble. The heat exchanger heater…
-
11 - Field Wiring (cont'd)
Example of wiring diagram for single compressor cooling only units - control circuit Legend : F1, F2 T1 TH EVAP R EVAP1 RC MC1 M/A M/A-D PME FS SAG1 TAG1 BP1 HP1 ACC1 S90 ST1 C1 ALIM TRI Page 16 Fuses Transformer Evaporator heater thermostat Evaporator heater Compressor crankcase heater On/Off…
-
11 - Field Wiring (cont'd)
Example of wiring diagram for single compressor heat pump units - control circuit Legend : F5, F6, F7 Fuses T1 Transformateur µCHILLER COMPACT : Controller ST1, ST2, ST3 : Temperature sensors HP1 High pressure switch H1 Indicator light CH1 Hour meter BP1 Low pressure switch PSE1 Safety pressure…
-
12 - Start-up
12.1 - Pre Start-up Before starting up the unit, a certain number of verifications must be performed on the installation to ensure that the unit will operate under the best possible conditions. The check list below is not exhaustive and should only be used as a minimum reference basis. 1. Inspect…
-
13 - Maintenance
Maintenance on this equipment are to be performed by qualified personnel. Causes for repeated tripping of safety controls must be investigated and corrected. The units are designed to operate for long periods of time with a minimum of maintenance. However, certain preventive maintenance operations…
-
14 - Spare Parts List
Common parts, All sizes Sensor well High pressure switch Low pressure switch Antifreeze thermostat Temperature sensor Safety pressure switch for detection of lack of water Pressostatic valve, 1/2" Pressostatic valve, 3/4" Pressostatic valve, 1" Pressostatic valve, 1" 1/4 Cooling only/Heat pump…
-
15 - In-Warranty Return Material Procedure
Material must not be returned without permission of our After Sales Department. To return the material, contact your nearest sales office and ask for a "return voucher". This return voucher shall be sent out with the returned material and shall contain all necessary information concerning the…
-
17 - Troubleshooting Chart
PROBLEM COMPRESSOR WILL NOT RUN POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS 1. Close switch. 2. Check electrical circuits and motor windings for shorts. Check for overloads and loose connections. Replace fuse or reset circuit breaker. 3. Thermal relay tripped. 3. Reset thermal relay, check unit when…
-
18 - Check List
-
With a concern for a constant improvement, our products can be modified without notice. Photos non contractual. Your distributor : R Wesper S.A. - 42 cours Jean Jaurès - 17800 Pons - Tel. : +33-5 - Fax : +33-5 - www.wesper.com