Инструкции на Настенные газовые конденсационные котлы Unical серии X
Модели: X R 24, X C 24, X R 32, X C 32. Руководство по монтажу и сервисному обслуживанию настенных газовых конденсационных котлов: общая информация и меры безопасности, технические характеристики и размеры, монтаж, гидравлические и электрические подключения, ввод в эксплуатацию, техобслуживание, коды неисправностей. Документ на английском языке.
Смотрите также: Коды ошибок: 3 кода →
Схемы в документе: стр. 45
Загружаем документ…
Текст инструкции
-
MIN
® bar Reset MAX MIN MAX service X R 24 - C 24 R 32 - C 32 INSTALLATION AND SERVICING MANUAL
-
https://www.unicalag.it/prodotti/domestico-50/condensazione-gas/2846/x
Provisions for proper disposal of the product. At the end of its life cycle the product must not be disposed of as urban waste. It can be taken to a special recycling centre managed by the local authorities, or to a dealer who offers this service. Separate disposal of a domestic appliance avoids…
-
GENERAL INFORMATION 1.1 - GENERAL WARNINGS The instruction booklet is an integral and essential part of the product and must be kept by the user. Read the warnings contained in this instruction booklet carefully as they provide important guidelines regarding installation, use and maintenance safety.…
-
1.2 - SYMBOLS USED IN THE MANUAL
Pay special attention when reading this manual to the parts marked by the symbols: DANGER! Serious danger to safety and health ATTENTION! Possible dangerous situation for the product and the environment NOTE! Tips for the user DANGER! Danger of burns! OBLIGATION! wear gloves protective NOTE! For…
-
1.5 - SAFETY WARNINGS
ATTENTION! The boiler cannot be used by children. The boiler can be used by adults and only after having carefully read the user’s manual. Children should be supervised to ensure that they do not play or tamper with the device. ATTENTION! The appliance must be installed, adjusted and maintained by…
-
The CE marking is affixed to each piece of equipment with an appropriate label
The CE declaration of conformity issued in accordance with international standards by the manufacturer, is placed in documentation envelope supplied with the product. The technical data plate is located inside the boiler on the back at the bottom / KEY: 1 = CE monitoring body 2 = Type of boiler 3 =…
-
1.7 - WATER TREATMENT
The treatment of the supply water allows to prevent inconveniences and maintain the functionality and efficiency of the generator over time. The ideal water pH in heating systems must be within: VALUE PH Hardness [°fr] MIN 6.5 9 MAX 8 15 To minimise corrosion, it is crucial to use a corrosion…
-
The Antifreeze protection is always active
Even by disabling the heating and domestic hot water services. MIN Do not use car engine antifreeze products as they could damage the water gaskets. MAX P O S 1 Power supplies Electric Gas MIN 11 - SR (*) ON ON < 6 °C < 2 °C ON OFF OFF ON OFF OFF (*) Sensor 11 par. 2.2 < 7 °C 2 ON ON The heating…
-
AND DIMENSIONS NOTE!
2 2.1 - TECHNICAL FEATURES For further details refer to the Technical Information from the website (link at page 2) 2.2 - VIEW WITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS KEY Burner Expansion vessel N° C.E. S.E. Description 8 1 db SS Domestic hot water temperature sensor 10 HL TL…
-
18 Plate heat exchanger FL FH VM 20 R Heating system return Rc Filling valve Sc Boiler drain Svs Safety valve drain Scond Condensation drain G¾ Fan Safety valve 22 rb SRR Return temperature sensor 23 tf TLC Flue gas collector safety thermostat 24 Aluminium Heat Exchanger/Capacitor (*) Condensate…
-
MIN ® X bar MAX MIN MAX service 420 345 View from above View from below F G R Rc Scond Svs C Sc M 247 Reset
-
Technical Features ENGLISH Avaible Head (m.c.a.) metres of water 2.3 - DIAGRAM OF FLOW RATE/PRESSURE AVAILABLE FOR INSTALLATION 13
-
2.4 - OPERATING DATA
For the adjustment data: NOZZLES - PRESSURES - DIAPHRAGMS - FLOW RATES refer to the paragraph ADAPTATION FOR USE WITH OTHER GASES Our appliances are built to work with natural gas (G20), G.P.L. and mixtures of methane and hydrogen up to 20% by volume (20% H2NG). The supply pipe must be equal to or…
-
2.6 - DATA ACCORDING TO ErP DIRECTIVE
Description Symbol Unit Model: X Nominal Heat Output Pnominal kW 23 31 Seasonal space heating energy efficiency ƞs % 93 93 A A Seasonal efficiency class in heating mode C24 R32 C32 ENGLISH R24 Useful Heat Output in high-temperature regime (Tr 60 °C / Tm 80 °C) P4 kW 23,4 31,2 Useful efficiency at…
-
INSTALLATION INSTRUCTIONS 3.1 - GENERAL WARNINGS ATTENTION! This boiler is intended solely for the use for which it was expressly designed. Any other use is to be considered improper and therefore dangerous. This boiler heats water at a temperature lower than the atmospheric pressure boiling…
-
3.4 - PACKAGING
After having removed the appliance from the packaging, make sure that the supply is complete and undamaged. The packaging elements (cardboard box, straps, plastic bags, etc.) must be kept out of the reach of children as they are potential sources of danger. Unical AG S.p.A. will not be held liable…
-
3.5 - POSITIONING THE BOILER
When choosing the place of the installation of the appliance, follow the safety instructions below: - Place the appliance in rooms protected from frost. - Avoid installation in rooms with a corrosive or very dusty atmosphere. - The appliance must only be installed on a vertical and solid wall which…
-
3.5.1 - REFERENCES FOR BOILER POSITIONING
-
WARNING!
Fit gasket 1, secure with screws 4 and 5. 4 * references for twin output Ø 80. * references for twin outputs Ø 80 (kit b) Fasten the collar 3 to the spacer before screwing the screws 4. A1 S A2 references for coaxial outputs, (kit a) distance from safety relief valve wall / condensate drain Scond…
-
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
FOR BOILERS WITH FORCED DRAUGHT) CAUTION LT** total length is a reference value for the dimensioning of the ducts of A (intake) and S (Exhaust). ENGLISH To connect the flue gas exhaust pipe, local and national standards must be observed In the event the boiler is replaced, ALWAYS replace the flue…
-
C(43) 3 x
C(43) 3 Collective chimney flue system, consisting of two pipes, one for combustion air intake and the other one for combustion products evacuation, coaxial or double. C(53) 3 x C(53) 3 C(53) 3 NOT ALLOWED C(53) 3 LT** (LUNGHEZZA TOTALE o LAspirazione + LScarico) DOUBLE Ø80 DOUBLE Ø60 FROM [m] 1+1…
-
ATTENTION
The flue must comply with standards in force. C(83) 3 B(23) 3 P ENGLISH C(83) 3 x C(93) 3 x C(93) x TOTAL LENGTH (LS) DOUBLE Ø80 FROM [m] 1 TO [m] DOUBLE Ø60 30 FROM [m] TO [m] 1 15 FROM [m] DOUBLE Ø50 TO [m] 1 10 Connection to a combustion products evacuation pipe outside the room; the combustion…
-
3.6.1 - Installation on collective flues
in positive pressure The collective flue is a smoke exhaust system suitable for collecting and expelling the combustion products of multiple appliances installed on multiple floors of a building. Positive pressure collective flues can only be used for type C condensing appliances. Consequently, the…
-
FOLLOWS: Installation on collective flues in positive pressure
- The assembly of the ducts must be carried out in such a way as to avoid condensation which would prevent the correct evacuation of the combustion products. - A data plate must be present at the connection point with the collective smoke duct. Data plate must contained the following information…
-
GENERAL INFORMATION ON THE FLUE GAS EXHAUST SYSTEM
For coaxial systems, mount always the suction adapter / exhaust 2 supplied with the boiler and collar 3 (contained in coaxial fumes kit) as indicated. T Attention: The air closure cap T must always be mounted on the air inlet hole Ø 80 A1 or A2. A1 (*) 3 2 S A2 3 2 T A1 S A2 KIT A coax. Ø 100/60 =…
-
Attention: The air closure cap
T d must always be mounted on the air inlet hole Ø 80 A1 or A2. (the unused one) (*) T ENGLISH For split systems DO NOT USE THE INTAKE EXHAUST ADAPTER 2 supplied with the boiler. Use split system adapters (*) as indicated. A1 S A2 (*) 1 T A1 S KIT B double Ø 80 = 00364891 00364817 (*) Installation…
-
For split systems DO NOT USE
THE INTAKE EXHAUST ADAPTER 2 supplied with the boiler. Use split system adapters (*) as indicated. Attention: The air closure cap T d must always be mounted on the air inlet hole Ø 80 A1 or A2. (the unused one) It is recommended to only use original Unical exhaust pipes. The supplier will have no…
-
GAS
3/4’’ Danger! The gas connection must be carried out only by a qualified installer who must respect and apply that foreseen by relevant laws in force in the local prescriptions of the supply company. Incorrect installation can cause damage to persons, animals and objects for which the manufacturer…
-
3.8 - FILLING THE SYSTEM
ENGLISH Attention! Do not mix the heating water with incorrect concentrations of antifreeze or anti-corrosion substances! This could damage the gaskets and cause noise during operation. Unical will not be held liable for damage to persons, animals or objects due to failure to comply with the above…
-
3.9 - ELECTRICAL CONNECTIONS
Danger! Only a qualified technician may perform the electrical installation. Before performing connections or any type of operation on electrical parts, always disconnect electrical power and make sure that it cannot be reconnected accidentally. Attention, before rotate or removing panel. Disconnect…
-
Electric power supply connection
ENGLISH External probe connection (*) - Predisposed on the terminal board, terminals SE The boiler is equipped with a power cable, boiler installation requires electric al connection to the mains power supply. This connection must be made up to standard, as required the regulations in force.…
-
3.10 - COMMISSIONING
Commissioning must be done by professionally qualified personnel. Unical AG S.p.A. will not be held liable for damage to persons, animals or objects due to failure to comply with the above instruction. Before commissioning the boiler, check that: does the installation meet the specific standards and…
-
The air bleed function is activated every time the
boiler is powered electrically (Power ON). The procedure has a duration of 10 minutes and for the entire time of the procedure the display shows AP flashing. 1 ’’ Reset Note. The procedure can be forced to interrupt by pressing the release button for 1 s. ENGLISH 3.10.1 - AIR BLEED FUNCTION OF…
-
3.11.2 - POSITIONING THE PROBES
To determine the combustion efficiency one must make the following measurements: - measurement of the combustion air temperature taken in the relevant hole 1. - measurement of the flue gas temperature and content of CO2 taken in the relevant hole 2. A 1 N.B.: Insert the smoke probe only afterwards…
-
3.12 - ADJUSTING THE BURNER
Attention, during these operations do not take any samples in DHW mode. All boilers leave the factory already calibrated and tested, however in the event the gas valve recalibration is required: The following instructions are intended exclusively for authorised service personnel. 1) Maximum output…
-
NOZZLES - PRESSURE - FLOW RATES TABLE
Check the levels of CO2 often, especially with low flow rates. They refer to the boiler with a closed combustion chamber. X R 24 - X C 24 (referring data to CH mode) Supply Press. Fan speed [kW] Heating Thermal Capacity [kW] [mbar] [rpm] min max Nat. gas (G20) 4,8 - 23,4 5 - 24 20 1300 Nat. gas…
-
3.12.1 - ADAPTATION OF THE POWER TO THE HEATING SYSTEM
ENGLISH ATTENTION! Function reserved for Authorised Assistance Centres only. The user is NOT authorised to activate the function described below. It is possible to adjust the maximum thermal capacity in heating mode, by decreasing the burner output value. Act on parameter HP (par. 4.2 parameters…
-
INSPECTION AND MAINTENANCE Inspections and maintenance performed professionally and according to a regular schedule, as well as the use of original spare parts, are of the utmost importance for fault-free operation of the boiler and to guarantee its long life. Yearly maintenance of the appliance is…
-
FL
(domestic hot water priority flow switch ( 2 ) Is the minimum domestic hot water flow rate 3 l/min.? VG (Gas valve) ( 3 ) Does the valve modulate properly? SR (heating sensor)( 11 ) Do the sensors maintain the SS (domestic hot water sensor) original characteristics? (1) SSR (return sensor) ( 22 )…
-
4.2 - PARAMETERS THAT CAN BE EDITED FROM THE CONTROL PANEL
1 MIN ATTENTION! Function reserved for Authorised Assistance Centres only. Some service parameters can be edited from the control panel: ACTIVATION MAX PREHEATING VALUES TO 1 x 10’’ FROM 0 Reset DEFAULT 0 service MIN By pressing the button (D) for 10 seconds, the function is activated when the key…
-
DISATTIVAZIONE To exit the parameters list wait for 20” or quickly turn the domestic hot water knob ‘‘C’’. 4.3 - ADAPTATION TO THE USE OF OTHER GAS The boilers are produced for the type of gas specifically requested upon ordering. DANGER! The conversion for the operation of the boiler with a type of…
-
- Remove fitting 3 on gas valve (flat key 30 mm)
- Access the modulation board contained in the electric panel and position the jumper in the position corresponding to the new type of gas indicated in the figure; 4.3.1 - Ending of gas transformation - Remove Diaphragm VG 4 - Close the electric panel and restore the appliance’s electric power…
-
4.5 - WIRING DIAGRAM
-
4.6 - ERROR CODES
The symbol flashes on the display monitor when the boiler detects an anomaly. service 1) In the event of an anomaly that does not stop boiler operation, press the unblock key to display the error code; in the event the boiler is in stand-by, the error code appears and remains fixed on the display.…
-
SPEED OUT OF Check fan operation (18) and CONTROL the connections. Alteration of the fan speed; the speed is not reached. SPEED OUT OF Check fan operation (18) and CONTROL the connections. Alteration of the fan speed; the speed is above that requested. HIGH TEMPERATURE Boiler temperature too high. 8…
-
CHIMNEY BLOCK Check the gas supply or that No gas or failed burner ignition the ignition/detection electrode is working properly (4) PARASITE FLAME Check the wiring of the Ign/Det. Flame detected upon ignition. electrode and remove any oxidation, check for humidity between drain wire and ceramic, if…
-