Инструкция на Система управления чиллером Trane UCM-CLD для холодильных машин RTAD
Система управления UCM-CLD для чиллеров Trane RTAD: работа контроллера, индикация, настройки, аварийные сигналы. Руководство владельца RLC-SVU02C-E4. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
Owner
Manual UCM-CLD Chiller Control System RLC-SVU02C-E4
-
General information
Foreword Reception Maintenance contract These instructions are given as a guide to the operation of the controller(s) mounted on Trane RTAD chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician…
-
Contents
General Information 2 Principles of operation of the UCM-CLD module 4 General Information 4 Operator’s Interface 5 Operational Features 9 Hot Water Mode Control Module (model RTWB units only) 14 Diagnostics 17 Diagnostics 17 Default Description 18 Additional controller for Free Cooling / Heat…
-
General Information
Figure 1 : Operator’s interface This UCM-CLD chiller control is composed of eight electronic modules, which each have their own 115V or 24V power supply and communicate with each other via a serial link. The names of the modules are linked to their functions. Alarm Select Report Group Custom Report…
-
Figure 2 : Control panel mounted on a model RTWA unit
Operator's Interface Digital Display The display of control regulation and operating parameters, diagnostics, and error messages is a 2-line, 40-character, liquid-crystal display. The display has a LED backlight to read in low-light conditions and to warm up the display under low ambient…
-
Control Key Functions
[+] key If the information displayed is read-only, pressing this key will add it to the operator's menu. If the information can be modified, pressing this key will increase the value without exceeding the maximum possible value. [-] key If the information displayed is read-only, pressing this key…
-
Parameters and setpoints within each menu
Menu Parameters/setpoints Chiller Report Menu Active Chilled Water Setpoint Evaporator Entering/ Leaving Chilled Water Temperature Condenser Entering / Leaving Chilled Water Temperature Active Ice-Storing Setpoint Active Hot Water Setpoint Entering/Leaving Hot Water Temperature Current Active…
-
Service Settings Menu**
Service Tests Menu Diagnostics Menu LEVEL ONE-Information adjusted by customer Unit Line Voltage Over/Undervoltage Protection Restart Inhibit Time Balanced Compressor Starts and Hours Display Language and Units Programmable Relay Set-up External Circuit Lockout LEVEL TWO- Information adjusted by…
-
Operational features
Entering evaporator water temperature When one or both compressors are running, the UCM continually monitors and compares the entering and leaving evaporator-water temperatures. If the temperature of the entering water drops more than 1°C below the leaving water temperature for more than…
-
Chilled-Water Reset (CWR)
As an option, the UCM will reset the chilled-water temperature setpoint, based on either the return water temperature or the outdoor air temperature. The CSR module is necessary to perform CWR. If the leaving-water temperature cutout is set upward, the Clear Language Display will maintain the 2.7°C…
-
Low refrigerant temperature cutout
Both circuits are protected from a saturated-evaporator refrigerant temperature that goes below this setting. The cutout Setpoint must be at a minimum of 8°C lower than the front panel or active chilled-water setpoints. See Table 2 for proper settings. There must be a minimum of 8°C between the…
-
Balanced compressor starts and hours
This feature is enabled/disabled in balanced starts and hours (service setting menu). When enabled, the UCM will start the compressor with the fewest starts and stop the compressor with the greatest number of operating hours, as determined by the “compressor starts“ accumulator and the “compressor…
-
Chilled-Water Setpoint (CWS) or Current limit Setpoint (CLS) When either external CWS or external CLS is used on the optional module A9, DIP switch SW1 positions 1 and/or 2 must be set to accommodate the type of of signal source the customer has chosen, either 2-10 V (dc) or 4-20 mA. Position SW1-1…
-
Hot-Water Mode Control
Module - Option Model RTWB Scope of Supply The following parts will be installed in the control panel of the unit: • One Additional Board A70 with display • One CDS LWT sensor + immersion well to be installed by the customer The sensor will be connected to terminals 5 and 6 on terminal block TB2 of…
-
The operation in Cooling or Heating
mode is selected either from the operator interface or from a remote place using a binary input. + - - Cooling Setpoint : from -12.0°C to 18.0°C Default Setting : 06.0 DEG + - - Differential to start/stop : from 1.0°C to 2.5 °C Default Setting : 1.0 DEG - Temperature Deadband : from 0.2°C to 2.0°C…
-
External Controls
If the unit is controlled from external signals (parameter “External Control”), the following wiring will be done: - External Start/Stop: Binary Input (close = start; open = stop). Terminals 1 and 2 on terminal block TB4. - External Cooling setpoint: Analog Input from -17.8 to 18.3°C (4 - 20mA or 2…
-
If there are no diagnostic messages,
the selected menu item will be displayed continuously. If the diagnostics key is pressed and there are no active diagnostics, the readout on the display will be: NO ACTIVE DIAGNOSTICS PRESENT When a system malfunction occurs, one of the following appropriate diagnostic messages will be displayed: A…
-
Displayed Code
Fault 87 Check External Chilled Water Setpt : Fault 89 Check External Current Limit Setpt : Fault 8A Chilled Water Flow (Ent Wtr Temp) : Fault 8E Evaporator Entering Water Temp Sensor : Fault 8F Condenser Rfgt Temp Sensor - Ckt 1 : Fault 90 Condenser Rfgt Temp Senspr - Ckt 2 : Fault 93 Evaporator…
-
Displayed Code
Fault 180 Starter Transition - Cprsr A : Type Description CMR 1) Transition proof signal not received 2) Proof input shunted Fault 181 Starter Transition - Cprsr B : CMR 1) Transition proof signal not received 2) Proof input shunted Fault 182 Starter Transition - Cprsr C : CMR 1) Transition proof…
-
Displayed Code
Fault 1AA EXV Elec Drtive Ckt - Rfgt Ckt 2 : Fault 1Ad Memory Error Type I : Fault 1AE Low Differential Pressure - Ckt 1 : Fault 1AF Low Differential pressure - Ckt 2 : Fault 1b2 Severe Phase Unbalance - Cprsr A : Fault 1b3 Severe Phase Unbalance - Cprsr B : Fault 1b4 Severe Phase Unbalance - Cprsr…
-
Displayed Code
Fault 1E0 High Oil Temp - Cprsr D : Fault 1E1 Oil System Fault - Cprsr A : Fault 1E2 Oil System Fault - Cprsr B : Fault 1E3 Oil System Fault - Cprsr C : Fault 1E4 Oil System Fault - Cprsr D : Fault 1E5 Entering Oil Temp Sensor - Cprsr A : Fault 1E6 Entering Oil Temp Sensor - Cprsr B : Fault 1E7…
-
Communication Failures
Displayed Code Fault 410 Fault 412 Fault 413 Fault 414 Fault 415 Fault 416 Fault 417 Fault 418 Fault 431 Fault 434 Fault 435 Fault 436 Fault 437 Fault 441 Fault 443 Fault 445 Fault 451 Fault 453 Fault 454 Fault 461 Fault 463 Fault 467 Fault 471 Fault 473 Fault 476 Fault 481 Fault 483 Fault 484 Fault…
-
Controller for Free Cooling/
Heat Recovery Application The aim of this section is to list available screens on the additional controller used to control Free Cooling /Heat Recovery application (version 1.0). The built-in control terminal features: • An LCD display (1), 4 lines x 20 characters with back lighting • 6 buttons (2)…
-
Permanent display
Access to this mask using the Esc key from any mask. The program will return automatically into it after 5 min. 1 = Application name and version number 2 = Current date and time 3 = Leaving water temperature 4 = Unit status: "Chiller Low Ambient" "FC Low Ambient" "Chiller" "Chiller, wait => FC"…
-
Data display menu
The following mask will be accessed using the Up and Down keys Analog Inputs 1 = Entering water temperature 2 = Leaving water temperature 3 = Ambient air temperature 4 = Active chilled water setpoint Setpoint Source 1 = Setpoint Source (Front Panel, External, Air Reset, Return Water Reset) 2 =…
-
Digital Inputs
1 = System (Off, On); NNSB (Off, On) 2 = UCM Pump (Not Req., Required) 3 = Flow Switch (OK, Not OK) 4 = Free Cooling (Disable, Enable) Digital Outputs 1 = Fans 1, 2 and 3 (Off, On) 2 = Fan Speed (Low, High) 3 = FC status (Off, On) 4 = UCM enabled (Off, On) 5 = System Pump (Off, On) 6 = Flow Switch…
-
3 Way Valve IO
Speed Low Relay Off 1 = 3WV Input Position (Value and Input Analog Voltage) 2 = 3WV Output Position (Value and Output Analog Voltage) Chilled Water Setpoint IO 1 = External Chilled Water Setpoint (Value and Input Analog Voltage) 2 = Adjusted Water Setpoint Output (Value and Output Analog Voltage)…
-
Chilled Water Reset CWR
1 = Reset Type (None, External, Based on OAT, Based on Ret Wat) "None" "External" "Based on OAT" "Based on Ret Wat" No reset has been requested Reset comes from external source Reset is based on outdoor air temperature Reset is based on return water temperature 2 = Ratio (-80%..120%: 25%) 3 = Start…
-
Alarm Messages - Free Cooling Application
Alarm Screen History Events Record Reset Type Unit status No Alarm No Alarm - Free Cooling ON Chiller ON See unit status on Main display Alarm LWT Sensor Faulty LWT Sensor Auto Free Cooling OFF Chiller ON Faulty sensor, out of range -38..+ 60°C during + 30s Alarm EWT Sensor Faulty EWT Sensor Auto…
-
Permanent display
Access to this mask using the Esc key from any mask. The program will return automatically into it after 5min. HR Application 00/00/00 Hot Wat Temp: Cool&HR Mode V1.0 00:00 00.0°C Running 1 = Application name and version number 2 = Current date and time 3 = Hot water temperature 4 = Unit status…
-
Access to Sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using the Up and Down keys and selected using the Enter button. 1 = Data display menu 2 = Settings menu 3 = Clock menu 4 = Unit configuration menu Data display menu The following mask will be accessed using the Up and Down keys…
-
Digital Inputs
Circuit 1: Running Circuit 2: Running HR Status: Enabled NNSB: Off 1 = Circuit 1 (Stopped, Running) 2 = Circuit 2 (Stopped, Running) 3 = Heat Recovery Status (Disabled, Enabled) 4 = Night Noise Set Back (Off, On) Digital Outputs 1 FAN1: Off FAN2: Off PRG Relay: On 2 Off Off 3 Off Off CKT On On 1 =…
-
Settings Menu
Access to each field within a mask using the Enter key. Change the field value using the Up and Down keys and confirmation by Enter. 1 = Access via password, 0000 to 9999 User Settings Hot Water SP: 50°C PRG Relay: HR ON 1 = Hot Water Temp SP (40..60°C: 50°C) 2 = Programmable Relay Function (PLC ON…
-
Alarms Messages - Heat Recovery Application
34 Alarm Screen History Events Record Reset Type Unit status Description No Alarm No Alarm - Heat Recovery ON Chiller ON See unit status on Main display Alarm HWT Sensor Faulty HWT Sensor Auto Heat Faulty sensor, out of range -38..+ Recovery OFF 85°C during + 30s Chiller ON Alarm PRS1 Sensor Faulty…
-
Literature Order Number
RLC-SVU02C-E4 Date 0106 Supersedes RLC-SVU02B-E4_0805 Literature Stocking Location Europe www.trane.com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the…