DVCompact
Supply/Extract Unit Installation instructions Document in original language 208383-EN_GB 2013-11-27 A001
-
1 Declaration of Conformity
Manufacturer Systemair AB Industrivägen 3 SE-739 30 Skinnskatteberg, SWEDEN Office: +46 Fax: +46 www.systemair.com hereby confirms that the following products: DVCompact Supply/Extract (The declaration applies only to product in the condition it was delivered in and installed in the facility in…
-
2 Warnings
The use of the equipment in the air handling unit can lead to serious mechanical or electrical danger as well as danger in relation to noise and vibrations. To reduce the risk of these dangers involved, it is absolutely necessary to follow all instructions concerning safety, installation, operation…
-
3 Product Introduction
3.1 General This installation manual concerns air handling unit type DVCompact Supply/Extract manufactured by Systemair AB. DVCompact Supply/Extract include the following model options: Model Description DVCompact Supply 10–100 Unit without built in control system. Sizes 10–100 DVCompact…
-
3.2 Technical Data
Fig. 1 Dimensions of Supply unit without control system Table 1: Dimensions and weights for Supply Unit without control system Model Base casing Doors Duct connection A B C Filter D E F Weight (kg) DVCompact 10 1720 DVCompact 15 1720 1120 1000 450 195 DVCompact 20 1720 1270 1150 500 230 DVCompact 25…
-
Fig. 2 Dimensions of Supply unit with control system
Table 2: Dimensions and weights for Supply Unit with control system Base casing Model Doors Duct connection Conn. A B C Filter D E F Weight (kg) box. DVCompact 10 2170 DVCompact 15 2170 1120 1000 450 225 DVCompact 20 2170 1270 1150 500 260 DVCompact 25 2320 1420 1300 600 307 DVCompact 30 2320 1570…
-
Table 3: Dimensions and weights for Extract unit
Model Base casing Doors Duct connection A B C Filter D E F Weight (kg) DVCompact 10 1120 DVCompact 15 1120 1120 1000 450 148 DVCompact 20 1120 1270 1150 500 183 DVCompact 25 1270 1420 1300 600 220 DVCompact 30 1270 1570 1450 650 283 DVCompact 40 1420 1720 1600 750 320 DVCompact 50 1570 2020 1045 300…
-
When changing components a free space corresponding to the width of the component in question is
necessary. Table 5: Power Consumption and Current Model IE2 fan (kW tot.) 400 V 3N~ Current (A) Fuse (main) DVCompact 10 1,1/2,2 2,8/4,49 10/10 DVCompact 15 1,5/3,0 3,13/5,88 10/10 DVCompact 20 2,2/4,0 4,49/7,65 10/13 DVCompact 25 3,0/5,0 6,18/10,9 10/16 DVCompact 30 3,0/5,0 6,18/10,9 10/16…
-
3.3.1 Unloading with Crane
Lifting straps must be secured in the leg brackets (figure 5). Fig. 5 Secured straps When lifting unit sections mounted on pallet or units mounted on a base frame, use metal tubes inserted through the holes in the frame and suspend the unit by soft cables (figure 6). Make sure that the upper part of…
-
4 Installation
4.1 Unpacking Verify that all ordered equipment are delivered before starting the installation. Any discrepancies from the ordered equipment must be reported to the supplier of Systemair products. 4.2 Where to Install the Unit The unit without roof is meant for indoor installation. The electronic…
-
4.3 Installing the Unit
The unit needs to be installed in the following position (figure 7). From size 40 the feet are replaced by a base frame. Fig. 7 Installation position for units with feet 4.3.1 Installation Procedure Mounting the sections 1 Prepare the surface where the unit is to be mounted. Make sure that the…
-
4.4 Supply air sensor
The supply air sensor is wired from factory to terminals in the electrical connection box. The sensor is placed in a box inside the unit on delivery. Install the sensor in the supply air duct ca. 3 m after the unit (figure 8). See below tables (table 6 and table 7) to which terminals the sensor is…
-
4.6 Connections
4.6.1 Electrical connections DVCompact Supply-10-100-w/aut are delivered with enclosed control. Internal and external wiring is connected to terminals in the enclosed electrical connection box placed on the front of the unit. DVCompact Supply 10–100 and DVCompact Extract-10–100 are delivered without…
-
Electrical connections cont'd
Terminal block Corrigo designation Description 21 C+ 22 75 DI5 External stop swich (optional) 23 76 DI6 Fire alarm (optional) 24 C+ 25 77 DI7 26 78 DI8 27 C+ 28 31 AI1 29 Agnd Analog signal gnd 30 G 24V AC 31 32 AI2 Outdoor air temp. sensor 32 35 AI4 Frost protection temp. sensor 33 Agnd Analog…
-
4.6.3 Connections to condensation drainage
Sections in which condensation from components may occur are fitted with drain pan and condensate drain. Condensate drains should always be provided with properly designed trap with sufficient height difference. Each condensate drain must be equipped with traps with same diameter as the drain pipe.…
-
4.6.4 BMS Connection
Exo-line, Modbus and optional LON connections are to be connected to the following terminals: • RS485(Modbus): 50-51-52 • RS485(Exo-line): 50-51-52-53 • LON: 57-58-59 RS-485 contact and Exo-line via TCP/IP (WEB) are included as standard (figure 12). Note: RS-485 port and TCP/IP port can not be used…
-
4.7 Installing the Control Panel
4.7.1 Dimensions Fig. 13 Control panel dimensions Position Dimensions (mm) A 115.0 B 94.0 C 26.0 D c/c 60.0 E 50.5 4.7.2 General information The control panel is delivered connected to the Corrigo control unit situated in the electrical connection box. Cable length is 10m. In case the control panel…
-
4.7.3 Installation
1 Find an appropriate place to install the control panel. Maximum length between control panel and unit is 10 m as standard. 2 If needed, drill two holes in the wall to hang the control panel (center to center: 60 mm) (pos.1 figure 14). Fig. 14 Control panel wire connections Position Description 1…
-