Installation and maintenance manual
Manuel d’installation et de maintenance Installations- und Wartungshandbuch Manuale di installazione e di manutenzione Manual de instalación y de mantenimiento SyScroll 240-660 Air CO/RE/HP/TR English 238 654 kW 256 679 kW Français Deutsch Italiano Español Air Cooled Water Chillers and Heat Pumps…
-
11--Introdução
Foreword 1.1 Introduction 1.3 Emergency stop / Normal stop Units, manufactured to state-of-the-art design and implementation standards, ensure top performance, reliability and fitness to any type of air-conditioning systems. The emergency stop of the unit can be enabled using the master switch on…
-
2 - Safety
2.1 Foreword These units must be installed in conformity with the provisions of Machinery Directive 2006/42/EC, Pressure Equipment Directive 2014/68/EU, Electromagnetic Compability Directive 2014/30/EU, as well as with other regulations applicable in the country of installation. If these provisions…
-
disassemble connections, filters, joints or other line items
2.2 Definitions OWNER: means the legal representative of the company, body or individual who owns the plant where unit has been installed; he/she has the responsibility of making sure that all the safety regulations specified in this manual are complied with, along with the national laws in force.…
-
n
periodically check the board’s internal wiring n n do not use cables having an inadequate section or flying connections, even for limited periods of time or in an emergency place a warning sign “do not turn on - maintenance in progress” on the external disconnecting switch n make sure that on-off…
-
2.7 Safety labels
Identification of the refrigerant - External door Instruction for the lifting Identification of the unit Outside, on the right-hand front column CODICE PRODOTTO NEUTRO PRODUCT CODE MODELLO MODEL 0425 MO.NO MATRICOLA SERIAL NO. ANNO DI COSTRUZIONE Sequence phase control on the electrical board Manuf.…
-
Electrical warning
Adjacent to the master switch Grounding connection on the electrical board, adjacent to the connection ATTENZIONE ! ATTENTION ! ACHTUNG ! Prima di Enlever aprire togliere l’alimentation tensione electrique avant d’ouvrir CAUTION ! ATENCION ! Vor Öffnen des Disconnect Cortar la corrente antes…
-
2.8 Safety regulations
REFRIGERANT DATA Toxicity SAFETY DATA: R410A Low If sprayed, the refrigerant is likely to cause frost burns. If absorbed by the skin, the danger is very limited; it may cause a slight irritation, and the liquid is degreasing. Unfreeze the affected skin with water. Remove Contact with skin the…
-
2.8 Safety regulations (continued)
REFRIGERANT DATA General precautions Respiratory system protection SAFETY DATA: R410A Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the professional threshold. Being more weighty than the air, the…
-
2.8 Safety regulations (continued)
LUBRICANT OIL DATA SAFETY DATA: POE/PVE OIL Classification Not harmful. Contact with skin May cause slight irritation. Does not require first aid measures. It is recommended to follow usual personal hygiene measures, including washing the exposed skin with soap and water several times a day. It is…
-
Refrigerators are supplied assembled (apart from standard
antivibrating rubber supports, that will be installed on site). The equipment are full of refrigerant and oil, in the quantity required for a proper operation. It is recommended to use a spacer to prevent cables from damaging the unit (see the figure). 3.1 Inspection When the unit is delivered, it…
-
3 - Transport, Lifting and Positioning (continued)
The eyebolts must be mounted on the unit whenever it shall be displaced and then lifted again. During the lifting and handling of the unit, be careful not to damage the finned pack of the coils positioned on the sides of the unit. WARNING WARNING WARNING 3.3 Anchoring The sides of the unit must be…
-
4.1 Positioning of the unit
DANGER 4.2 Spring Isolator Installation Before installing the unit, make sure that the structure of the building and/or the supporting surface can withstand the weight of the appliance. The weights of the units are listed in Chapter 8 of this manual. n Prepare the base, that must be flat and plane.…
-
4.3 External Water Circuit
The expansion tank shall be dimensioned in such a way that it can absorb a 2% expansion of the total volume of the water in the plant (exchanger, pipelines, uses and storage tank, if available). The flow switch and the filter water, although not included in the supply, must always be fitted such as…
-
Hydraulic Circuit Diagram - Basic Unit
A D 12 5 C G FS B COMPONENTS 1 Plate heat exchanger 2 Pump 3 Draining valve 4 Water buffer tank 5 Water filter 6 Non-return valve 7 Pressure expansion tank 8 Pressure point/drainage 9 Water outlet 10 Water inlet 11 Globe valve 12 Flexible pipes 13 By pass valve SAFETY/CONTROL DEVICES A Inlet water…
-
Hydraulic Circuit Diagram - 1P Unit
C E D A G FS B COMPONENTS 1 Plate heat exchanger 2 Pump 3 Draining valve 4 Water buffer tank 5 Water filter 6 Non-return valve 7 Pressure expansion tank 8 Pressure point/drainage 9 Water outlet 10 Water inlet 11 Globe valve 12 Flexible pipes 13 By pass valve SAFETY/CONTROL DEVICES A Inlet water…
-
Hydraulic Circuit Diagram - 2P Unit
6 2 E D A C 1 G FS B COMPONENTS 1 Plate heat exchanger 2 Pump 3 Draining valve 4 Water buffer tank 5 Water filter 6 Non-return valve 7 Pressure expansion tank 8 Pressure point/drainage 9 Water outlet 10 Water inlet 11 Globe valve 12 Flexible pipes 13 By pass valve SAFETY/CONTROL DEVICES A Inlet…
-
Hydraulic Circuit Diagram - 1P+T Unit
D A 2 C 1 E G B FS D 3 Y COMPONENTS 1 Plate heat exchanger 2 Pump 3 Draining valve 4 Water buffer tank 5 Water filter 6 Non-return valve 7 Pressure expansion tank 8 Pressure point/drainage 9 Water outlet 10 Water inlet 11 Globe valve 12 Flexible pipes 13 By pass valve SAFETY/CONTROL DEVICES A Inlet…
-
Hydraulic Circuit Diagram - 2P+T Unit
D A 6 2 E C 1 G B 4 FS D 3 Y COMPONENTS 1 Plate heat exchanger 2 Pump 3 Draining valve 4 Water buffer tank 5 Water filter 6 Non-return valve 7 Pressure expansion tank 8 Pressure point/drainage 9 Water outlet 10 Water inlet 11 Globe valve 12 Flexible pipes 13 By pass valve SAFETY/CONTROL DEVICES A…
-
4.4 Water connections
WARNING It is important that the appliance is grounded. The attachments at the water inlet and outlet shall be connected in compliance with the instructions which can be found on the labels in the proximity of the attachments. DANGER Connect the water lines of the plants with the attachments of the…
-
4.7 Electrical connections
The maximum % value of these differences (unbalance) must not exceed 2% of the mean voltage. The unit must be installed on site according to the Machinery Directive 2006/42/EC, Electromagnetic Compatibility Directive 2014/30/EU and the usual procedures and standards applicable in the place of…
-
Electrical Connections
Note: For the other version refer to documentation attached to machine. 22
-
WARNING
The unit must be started for the first time by personnel suitably trained by one Authorised Service Centre. Failure to meet this requirement will immediately void the warranty. n Start the pump and check that the water flow is correct. n Set the desired fluid temperature on the control board. n…
-
6 - Control
6 General information The control system consists of: Keyboard & Display Terminal Introduction General information This document contains the information and the operating instructions for units equipped with 3/4/5/6 compressors. The figure shows the terminal with the front door open. This…
-
6.2 Display
Esc key: allows you to move from one mask to another. Alarm key: used to display the alarms, to reset them in manual. Press it one to display the mask of the activated alarm, press it again to reset the alarm signal. + Prg+Esc keys: Pressing these keys at the same time,allows you to turn the unit…
-
Alarms
Alarm code Description Main board - EPROM Failure Main board - Clock card Failure Main board - External air temperature sensor fault Main board - Return Water temperature sensor fault Main board - Leaving Water temperature sys 1 sensor fault Main board - Leaving Water temperature sys 2 sensor fault…
-
Alarm code
Description EPROM Error Driver 1 EPROM Error Driver 2 Driver 1 S1 Sensor fault Driver 1 S3 Sensor fault Driver 1 S2 Sensor fault Driver 1 S4 Sensor fault Driver 2 S1 Sensor fault Driver 2 S3 Sensor fault EEV motor Error (Check viring) Sys 1 EEV motor Error (Check viring) Sys 2 Driver 1 Battery alarm…
-
6.4 Protection and Safety Equipment
Compressor protection Defrosting System (only for HP models) Compressors are equipped with a heating element to prevent oil dilution, which may result in remarkable risks of failure of compressors. The HP units are provided with an automatic defrosting system, which prevents the formation of…
-
6.5 HPF version configuration
possible to modify high static pressure. The table below shows the correspondance between chiller model, fan RPM, high static pressure. Units equipped with High pressure fan (HPF) can be set-up on the field to give the unit a specific static pressure. By entering parameter in service level - Max…
-
7 - Product Description
7.1 General Information 7.5 Condensing/evaporating coils Units are one-block type with double refrigerant circuit. They are intended to cool down the water required for any air-conditioning application as well as any other fluid, such as for example glycol water. These units are completely assembled…
-
Refrigerant flow diagram - SyScroll Air CO
* M A S A AT S 6 G 2 B BT S EXV CONTROL 5 UNIT CONTROL D C S E F COMPONENTS 1 Scroll type compressor 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Heat exchanger 7 Desuperheater (optional) 8 Sight glass SAFETY / CONTROL DEVICES A High pressure switch AT High…
-
Refrigerant flow diagram - SyScroll Air HP
* S A A AT M 12 ON 8 11 S 9 S S B N H BT EXV CONTROL C D 5 UNIT CONTROL 6 G F 2 G 5 E NOT FOR SIZE: 240-270 S 3 6 COMPONENTS 1 Scroll type compressor 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Check valve 7 Liquid receiver 8 Four-way valve 9 Suction…
-
Refrigerant flow diagram - SyScroll Air RE
-
Refrigerant flow diagram - SyScroll Air TR
* E F M A S A AT ON B S 6 G 5 13 BT S S D 5 EXV CONTROL UNIT CONTROL C S G 12 12 E F COMPONENTS 1 Scroll type compressor 2 Air cooled condenser 3 Filter drier 4 Electronic expansion valve 5 Globe valve 6 Heat exchange 7 Desuperheathers (optional) 8 Sight glass 9 Four-way valve 10 Heat recover 11…
-
8 - Technical Data
8.1 Pressure drops EVAPORATOR PRESSURE DROP - SYSCROLL Air CO Minimum flow rate l/s 8.2 9.2 9.9 10.8 12.4 14.2 16.1 18.3 20.2 22.4 Nominal flow rate l/s 11.4 12.8 13.8 15.1 17.4 19.9 22.5 25.6 28.3 31.4 Maximum flow rate l/s 19.0 21.4 23.0 25.2 28.9 33.1 37.5 42.7 47.1 52.3 Minimum pressure drop kPa…
-
8.2 Technical data
SyScroll Air CO _ Power supply V/ph/Hz 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 kg 9,5 10 10,5 22,5 tCO2eq 19,84 20,88 21,92 22,97 33,41 41,76 46,98 45,94 54,29 60,55 Total capacity steps 23-4669-100 25-5075-100…
-
Power supply V/ph/Hz 360 420 English 8 - Technical Data (continued) 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 kg 9,5 10 10,5 22,5 tCO2eq 19,84 20,88 21,92 22,97 33,41 41,76 46,98 45,94 54,29 60,55 Total capacity steps…
-
Power supply V/ph/Hz 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400V/3/50Hz % 31-62100 33-67100 30-60100 27-64100 kg 9,5 10 10,5 22,5 tCO2eq 19,84 20,88 21,92 22,97 33,41 41,76 46,98 45,94 54,29 60,55 Total capacity steps 23-4669-100 25-5075-100 REFRIGERANT Type / GWP Charge…
-
SyScroll Air HP
Power supply V/ph/Hz 360 420 English 8 - Technical Data (continued) 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 kg tCO2eq 56,38 58,46 83,52 62,64 87,70 104,40 108,58 104,40 133,63 154,51 Total capacity steps 23-4669-100…
-
Power supply V/ph/Hz 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 kg tCO2eq 56,38 58,46 83,52 62,64 87,70 104,40 108,58 104,40 133,63 154,51 Total capacity steps 23-4669-100 25-5075-100 REFRIGERANT Type / GWP Charge Circuit…
-
Power supply V/ph/Hz 360 420 English 8 - Technical Data (continued) 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 kg tCO2eq 56,38 58,46 83,52 62,64 87,70 104,40 108,58 104,40 133,63 154,51 Total capacity steps 23-4669-100…
-
SyScroll Air TR
Power supply Total capacity steps V/ph/Hz 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 23-4669-100 25-5075-100 kg tCO2eq 56,38 58,46 83,52 62,64 87,70 104,40 108,58 104,40 133,63 154,51 REFRIGERANT Type / GWP Charge Circuit…
-
SyScroll Air RE_
Power supply V/ph/Hz 360 420 English 8 - Technical Data (continued) 24-4765-82100 20-4060-800100 14-2943-6281-100 17-3350-6783-100 400 (± 10%) / 3 / 50 % 31-62100 33-67100 30-60100 27-64100 kg 9,5 10 10,5 22,5 tCO2eq 19,84 20,88 21,92 22,97 33,41 41,76 46,98 45,94 54,29 60,55 Total capacity steps…
-
8.3 Unit electrical data
SyScroll Air Rated voltage V/ph/Hz (± 10%) / 3 / 50 Max. absorbed power kW Rated Current A Max. current FLA A Max. start-up current LRA A External fuses A mm2 2x185 2x185 2x185 2x185 Max. cable section (*) Exchanger resistance Rated voltage Exchanger resistance Max. absorbed power V/ph/Hz W SyScroll…
-
Compressors electrical data
Syscroll Air 240 Number Rated power kW 270 kW A A Oil pan resistor 26.7 26.7 26.7 26.7 32.7 32.5 32.5 25.6 32.5 21.1 26.7 26.7 32.7 26.7 32.7 32.5 32.50 25.6 32.5 21.1 26.7 32.7 32.7 26.7 32.7 25.6 32.5 25.6 32.5 32.7 32.7 39.0 39.0 39.0 39.0 49.0 25.6 32.5 32.5 32.5 25.6 32.5 32.5 32.5 32.5 32.5…
-
8.4 Hydraulic features
Evaporator Water Pressure Drop Curves - SyScroll Air CO 470-540 240-270-290 [kPa] 100 590-660 320-360-420 10 5,00 50,00 [l/s] Evaporator Water Pressure Drop Curves - SyScroll Air HP 240-270-290 470-540 [kPa] 100 590-660 320-360-420 10 4,00 40,00 [l/s] Condenser Water Pressure Drop Curves - SyScroll…
-
Condenser Water Pressure Drop Curves - SyScroll Air TR
-
Available pressure head - SyScroll 240-270 Air CO 2P+T
Available static pressure [kPa] A B Water Flow [m3/h] Available pressure head - SyScroll 290 Air CO 2P+T Available static pressure [kPa] A 150 B Water Flow [m3/h] Available pressure head - SyScroll 320 Air CO 2P+T Available static pressure [kPa] A 200 150 B Curve A: High pressure. Curve B: Low…
-
Available pressure head - SyScroll 360-420 Air CO 2P+T
Available static pressure [kPa] A 150 B Water Flow [m /h] 3 Available pressure head - SyScroll 470 Air CO 2P+T Available static pressure [kPa] 350 300 A 250 200 B Water Flow [m3/h] Available pressure head - SyScroll 540 Air CO 2P+T Available static pressure [kPa] 400 350 A 300 250 B Curve A: High…
-
Available pressure head - SyScroll 590-660 Air CO 2P+T
Available static pressure [kPa] 300 250 A 200 150 B Water Flow [m3/h] Curve A: High pressure. Curve B: Low pressure.
-
8.5 Position of shock adsorbers and weight distribution on supports
-
SYS HP
-
Operating Shipping
-
8.6 Dimensions SyScroll Air 240-270-290-320
-
P2
-
Dimensions SyScroll Air 470-540
-
Dimensions SyScroll Air 590-660
-
8.7 Space requirements
-
DANGER
When the recovered refrigerant cannot be reused, return it to the manufacturer. Do not throw away the waste oil of the compressor, because it contains refrigerant in solution. DANGER The waste oil must be returned to the manufacturer. Unless otherwise specified, the operations described below may be…
-
9 - Maintenance (continued)
9.3 Refrigerant charge 9.5 Condenser Do not inject refrigerant liquid into the LP side of the circuit. Be very careful, and charge the circuit properly. If the charge is insufficient, the efficiency of the unit will be lower than expected. (In the worst of cases the LP transducer may stop the unit.)…
-
9.9 Electronic Expansion Valve
9.10 Evaporator The circuit of the unit is equipped with electronic expansion valve, with external equalizer The valve is shop-calibrated for an overheating of 5°C. Check at regular intervals that the water side of the heat exchanger is perfectly clean. To do this, measure the pressure drop, water…
-
10 - Troubleshooting
The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or not listed, contact one of authorised Service Centre for technical assistance. Anomaly Cause Operation The unit continues to work, but without cooling…
-
11 - Spare Parts
11.1 Spare part list The table below shows the list of spare parts recommended during the first two years of operation. Component Number Fan 1 Flow switch 1 High pressure transducer 1 Low pressure transducer 1 Expansion valve 1 Gas filter 1 4 way valve 1 Electronic main board 1 Auxiliary circuit…
-
12 - Dismantling, Demolition and Scrapping
After draining operations, the piping of the hydraulic networks can be disconnected and disassembled. During the draining of the refrigeration circuits, do not let the refrigerant overflow in the surrounding atmosphere. DANGER Once they have been disconnected as specified, the packaged units can be…
-
Systemair srl
Via XXV Aprile, 29 20825 Barlassina (MB) Italy Tel. +39 0362 680 1 Fax +39 0362 680 693 www.systemair.com As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Dans un souci d’amélioration constante, nos produits…