SERIES: VLS / VLH / VLC 604-1204
TYPE: Air cooled water chiller, heat pump and condensing unit TECHNOLOGY: multi-scroll compressors, R410A refrigerant CAPACITY RANGE: Cool ing 153-307 [kW] Heating 170-337 [kW]
-
1 General description
VLS / VLH / VLC units have been designed and optimized to operate with R410A refrigerant and scroll compressors Thanks to multi-scroll technology and asymmetric design in tandem combination, it is possible to reach very high level of seasonal performances (ESEER up to 4,1), in line with Ecodesign…
-
fan deck sound emission, the chillers are supplied with compressors box
to reduce the noise emissions • Extra Low Noise (ELN): the units are equipped with star connected fans, fitted with a speed controller which allows the units to operate with a very low rotation speed. Besides very low fan deck sound emission, the chillers are supplied with compressors box and…
-
Several hydraulic options are available in order to cover a wide range of
requirements in terms of pump available static pressure, redundancy and inertia water side The general operation status of the unit is steadily managed by a microprocessor implementing a dedicated developed software, ensuring a total protection of compressor inside its operating envelope and…
-
2 Key points
• High seasonal performances ESEER up to 4.1 • Common configuration for the different versions Easy upgrade of the units in stock or on field • Electronic expansion device Excellent control of superheating for the best performance at full and partial load and for a safe operation •…
-
3 Cabinet
The cabinet is made of heavy gauge galvanized steel. All galvanized steel components are individually painted by a special painting process before the assembly of the unit. This painting system performs a homogeneous protection to the corrosion. The painting is a polyester powder based type, colored…
-
protection against freezing at low ambient temperature when the unit is
switched off. Maximum working pressure is 10 [bar] water side and 45 [bar] refrigerant side 6 Condenser In Heat pump version (VLH), Condensing unit (VLC) and Total heat recovery unit (VLR), condenser coils are made of seamless copper tubes, arranged in staggered rows, mechanically expanded into…
-
8 Refrigerant circuit
All the units are equipped with two independent and separate refrigerant circuits. Each refrigerant circuit is equipped with liquid line and discharge line shut-off valves, filter-drier with solid core, sight glass and electronic expansion valve. Heat pump units (VLH) are additionally provided with…
-
Evaporator antifreeze protection
Defrost management High and low pressure operating conditions management External interlocks management Remote control management o Unit power on / off o Unit cool / heat operation o Summary alarm signal • Remote signaling, by dry contacts: o Voltage presence o Compressors in operation o General…
-
• Refrigerant coil temperature
• Heat recovery temperature Unit controller can display various alarms and operation status: • Low / High pressure • Evaporator antifreeze • Lack of water flow • Compressor operation / operating hours and start-up numbers • Pump operation / operating hours • Compressor thermal protection • Fan…
-
• Crankcase oil electric heater
• Water differential pressure switch • Safety valve on discharge lines Control • • • • • • • • • High pressure transducers Low pressure transducers Discharge gas temperature probes Return water temperature sensor Leaving water temperature sensor (with an antifreeze function) Suction temperature…
-
components
• Single or double pump with low available static pressure (100 [kPa]) or high available static pressure (200 [kPa]) • Expansion tank (25 [l] for all models) • Check valves (in case of 2 pumps) • Safety valve • Automatic air vent valve • Thermal insulation for pipes and water pump(s) On board hydro…
-
12 Factory installed options
• • • • • • • • • • • • • • • • • ModBus protocol kit for BMS Lonwork protocol kit for BMS Bacnet protocol kit for BMS Compressors soft-starter Fan speed control for low ambient operation in cooling mode Double set point Power factor correction capacitors Compressor overload protection Automatic…
-
• • • • • • • Remote keyboard panel Sequencer, up to max four units Master and slave control, up to max four units Anti-vibration spring Water flow switch Water pressure switch Water filter Remote hydro kits with buffer tank, 1 or 2 low or high pressure pump(s), relevant accessories, with or without…