SysAqua 20 / 25 / 30 / 35 / 40 / 45 / 50 / 65 / 75 / 90 / 105 / 125 140 / 150 / 170 / 190 / 210 Air Cooled Water Chillers and Heat Pumps 19.5 â 217.6kW 19.3 â 208.8kW
-
REGULATION MANUAL
English MANUEL DE REGULATION Français REGELUNGSHANDBUCH Deutsch MANUALE DI REGOLAZIONE Italiano MANUAL DE REGULACIÓN Español
-
SYSAQUA 5
English 1. DESCRIPTION 1.1. ABBREVIATIONS Abb. Unit Description BP bar Evaporation pressure BMS - Building Management System CDT °C Compressor backflow temperature CST °C Compressor aspiration temperature EEV - Electronic pressure reducing valve EWT °C Entering water temperature HMI - Human-Machine…
-
6 SYSAQUA
2. PURPOSE 2.1. INTRODUCTION This document describes the functioning of the SIEMENS regulator for units of the SysAqua range. It is intended for the installation technician and the end user More complete information is available in the following documents: ²²EDM : technical description of units and…
-
The dual-circuit units are identical to the single-circuit units with the exception of the (electronic) expansion and the plate heat exchanger (dual type - common to both circuits). RV1 OFA OFB RV2 OFC OFD M2-1 M2-2 M1-1 M1-2 3-1 3-2 WATER 4-1 5-1 6-1 7-1 8 7-2 6-2 5-2 4-2 The SysAqua range proposes…
-
SysAquaH in heating mode
25 20 Air temperature (°C) English 8 SYSAQUA -5 -10 -15 -20 Leaving water temperature (°C) 50 55
-
3. INTERFACES
3.1. INPUTS / OUTPUTS OF THE SYSAQUA CONTROLLER 20/25/30/35/40/45/55/65/75/90/105/125 Pump KWP1 Q1 SM1 SD/N External on/off contact Configurable external input EWT LWT B3 OAT Water inlet temperature Water outlet temperature Air temperature D1 D2 Compressor 1 K1 Q3 Compressor 2 K2 Q4…
-
10 SYSAQUA
3.3. INTEGRATED DISPLAY This user interface is a liquid crystal display with 6 buttons. It is connected to the "BSP BUS" port of the regulators POL423 and POL687 with an RJ45 cable (maximum distance 2.5m). Info Up Alarm Down Escape Enter INFO From any screen, this button returns the user to the main…
-
SYSAQUA 11
English 3.5. WEB DISPLAY This interface is available on dual-circuit units connected to an IP¨network. A Web browser enables access to a unit indicating its IP address and using the WEB account (password: SBTAdmin!). 3.6. COMMUNICATION PROTOCOLS The available communication protocols depend on the…
-
12 SYSAQUA
The units are connected either via the customer intranet or independently of the customer intranet via an optional 3G router. The connection specifications and the information made available on the cloud are detailed in the Communication Manual.
-
SYSAQUA 13
English 4. THERMAL CONTROL 4.1. INTRODUCTION 4.1.1. LOAD AND CAPACITY The function of the SysAqua units is to maintain the client water circuit at the temperature specified by the client. The temperature of the water from the client network translates the client’s "charge" to which the unit must…
-
14 SYSAQUA
English 4.1.3. OPERATING MODES The SysAqua units offer three operating modes: ²²Cooling mode = the unit cools the water circuit. The unit is regulated according to the water temperature sensor: If the measurement is less than the set-point: the unit is on stand-by If the measurement is above the…
-
SYSAQUA 15
Temperature control ensures that the water sensor selected by the client (EWT or LWT) attains the actual set-point, SP*. To manage the compressors more efficiently, the control uses the concepts of load and capacity. Load formulation The load is calculated via an algorithm PI minimizing the…
-
16 SYSAQUA
5. EQUIPMENT MANAGEMENT 5.1. TEMPERATURE SENSORS The temperatures are measured by CTN sensors 10kΩ. Resistance measurements are converted to temperature with coefficients scaled over the entire temperature range to ensure sufficient accuracy (<1 K) regardless of the operating point of the unit.…
-
SYSAQUA 17
The 4-way valve enables switching between cooling mode (valve deactivated) and heating mode (valve activated). Switchover requires either stopping the tandem for more than a minute, or a gap of less than 4 bar between the BP and the HP. 5.7. CARTER RESISTANCE 5.7.1. SYSAQUA…
-
18 SYSAQUA
6. ADDITIONAL FUNCTIONALITIES 6.1. WATER LAW The water law allows the temperature set-point to be adapted according to the exterior temperature. By default the water law is deactivated. Main Menu Status 1/4 Commissioning Commissioning 1/12 10:40:05 03.02.2016 Language selection Communications Glycol…
-
To secure the unit at low temperatures, the water law automatically limits the effective set-point to the operating envelope (Refer to the § OPERATING ENVELOPES, page 7) : SP* = min [ f(OAT), envelope heating mode ] In the example below, the water law substitutes the operating envelope for function…
-
20 SYSAQUA
English 6.3. LOAD SHEDDING MODE Main Menu Status The load shedding mode limits the electrical power consumption of the unit by limiting its capacity. The amount limited is defined by a maximum value of capacity, setting between 0 and 100%. By default the load shedding mode is deactivated. The…
-
SYSAQUA 21
The fans turn at a fixed speed, that can be regulated between 0 and 100%. Speed set-point V 0 Hz Voltage signal % REGULATOR Power frequency 50 10 V FREQUENCY INVERTER 6.5. "HIGH PRESSURE FANS” OPTION The “High Pressure Fans” option allows air rejected by the fans to be funneled. To meet the load…
-
22 SYSAQUA
English 6.6. "VARIABLE PRIMARY FLOW” OPTION Main Menu Status 1/4 Commissioning Service Configuration Manual control Deice Operation hours Lock out Inputs-Outputs Parameters Archives Services Access 1/8 Configuration 1/7 Fan Pump Circuit control Contacts D1 D2 dT ret./sup. temp Control on…
-
SYSAQUA 23
The speed of the pump depends on the capacity of the unit. This speed range is determined during commissioning to adjust the power of the pump to the load drops of the installation. When the load is insufficient to activate the 1st stage of capacity, the pump runs at a reduced speed to limit the…
-
24 SYSAQUA
6.6.3. CONSTANT OUTPUT PRESSURE MODE The pump modulates its speed to maintain constant water pressure at the unit output. This pressure is measured by a pressure transducer mounted on the outlet tube. The load is calculated via an algorithm PI minimizing the difference between the transducer…
-
SYSAQUA 25
Main Menu Status English 6.7. SCHEDULING Scheduling enables operating commands to be programmed throughout the week: 1/4 Commissioning 1/12 03.02.2016 10:40:05 Language selection Communications Glycol protection Auto change over Water Law Reduced mode Limited capacity Cold OAT protection Small…
-
26 SYSAQUA
-
8. PROTECTIONS, WARNINGS AND ALARMS
The application has equipment protection procedures based on the sensors of the unit (temperature, pressure) and on the electromechanical safety devices (pressure switch, magneto-thermal circuit breaker, internal safety, etc.). Some procedures may temporarily change the operation of the unit and…
-
28 SYSAQUA
8.2.5. INSUFFICIENT VOLUME OF THE WATER CIRCUIT The unit operates in concert with the installation water circuit. The coefficients of the PI algorithms and the delays governing the behavior of the equipment in the transient phases are adapted to the expected inertia of the circuit. The inertia of…
-
SYSAQUA 29
Too low or too high a pressure at the suction of the compressor can damage it. Two levels of protection against too low pressure are implemented: 1. Protection : triggers when the pressure is too low and raises the alarm "LOPPrt". The protection limits the capacity of the circuit until the pressure…
-
30 SYSAQUA
8.7. MISCELLANEOUS PROTECTIONS 8.7.1. ORDER CONTROLLER AND PHASE BREAKER The controller, installed in the electrical panel at the head of the distribution of the phases to the equipment, ensures the correct direction of rotation of compressors, fans and hydraulic pumps. In the case of incorrect…
-
SYSAQUA 31
The Alarm Snapshot save the unit state at the instant the alarm appears. The main elements saved are: ²²Unit EWT, LWT, OAT ²²Circuit 1 : BP, HP, SH, CDT, EEV, OFAN ²²Circuit 2 : BP, HP, SH, CDT, EEV, OFAN 8.10. DEFROST CYCLE 8.10.1. PRINCIPLES When the unit is operating in heating mode and the…
-
32 SYSAQUA
9. USER INTERFACE 9.1. ORGANIZATION OF INFORMATION AND LEVEL OF ACCESS The HMI allows the state of the unit to be visualized and certain adjustments to be made. The information displayed depends upon: ²²the configuration of the unit: information not related to the unit do not appear ²²the access…
-
SYSAQUA 33
Main Menu Status 1/4 Commissioning Services Access Status HMI state HMI mode State from Mode from Cooling setp. Current setp. cool Heating setp. Current setp. heat Load Capacity Hydraulic circuit Circuit 1 Circuit 2 1/13 Delegate Automatic Schedul. HMI 8.0°C 8.0°C 44°C 44°C 0.0% 0.0% HMI state…
-
34 SYSAQUA
English 9.5. INSTALLATION MENU Limited access with the "Installer" or "Maintenance". Main Menu Status Commissioning Services Access 1/4 Commissioning 1/12 03.02.2016 10:40:05 Language selection Communications Glycol protection Auto change over Water Law Reduced mode Limited capacity Cold OAT…
-
SYSAQUA 35
Main Menu Status English 9.6. MAINTENANCE MENU Limited access with the "Maintenance" profile. 1/4 Commissioning Services Service Configuration Manual control Deice Operation hours Lock out Inputs-Outputs Parameters Archives Access 1/8 Configuration Fan Pump Circuit control Contacts D1 D2 dT…
-
36 SYSAQUA
English 9.7. ALARMS MENU If no alarm is active, pressing the "Alarm" button takes you to the alarm history Main overview 1/3 Current mode Red. H Entering water T. 42.3°C Leaving water T. 45.2°C Alarm history 1/5 - i compressor oil heating + Fault supp.pump: Alarm + Condensing P. Circuit 1:.. +…
-
SYSAQUA 37
English 9.7.2. THE LIST OF ACTIVE ALARMS The list of active alarms allows visualization of current alarms The first line shows the number of active alarms (3 in the example below) Alarm list 1/4 Acknowledge 3 + Fault supp.pump: Alarm + Condensing P. circuit 1: Com. fault + Suction T. circuit 1: Com.…
-
38 SYSAQUA
10. AUTOMATIC ARCHIVING 10.1. SAVING ARCHIVES The regulator registers the main variables of the unit. The values are recorded according to the principle of the circular buffer. The software "Scope Light" allows recovery of the records, to display them in graphical form and to export them in csv…
-
Variable
actual operating status: 0 = auto 1 = OFF 2 = ON 3 = Reduced mode 4 = Load shedding actual operating mode: 0 = OFF 1 = cooling 2 = cooling reduced mode 3 = cooling load shedding 4 = heating 5 = heating reduced mode 6 = heating load shedding Preheat phase: 0 = over 1 = on-going Load Unit COV Archive…
-
40 SYSAQUA
Variable Reverse valve state: 0 = OFF 1 = ON Superheat Fan state: 1 = OFF 2 = Stage 1 3 = Stage 2 Condensing temperature Discharge temperature Evaporating temperature Coil temperature Suction temperature Unit COV Archive filename ObjectID SysAqua 20 to 125 SysAqua 140 to 210 enum 1…
-
SYSAQUA 41
Csv archive files are of ASCII type and use the ";" as separator. The first line of the file contains the characteristics of the saved file: Field Description Internal variable of the record Internal name of the record Engineering unit system enumeration: 2 = Metric, 3 = Imperial Engineering unit…
-
42 SYSAQUA
English 10.3. RECOVERY OF ARCHIVES WITH SD CARD The saved archives can be recovered with a standard SD card. The procedure is: 1. Put the SD card in read / write mode 2. Insert the SD card into the regulator 3. Access "Maintenance" then go to the menu "Maintenance Archives Save -> SD". 4. Press…
-
11. MANAGEMENT OF SITE AND APPLICATION PARAMETERS
11.1. SAVING OF PARAMETERS ON AN SD CARD The unit parameters can be recovered with a standard SD card. This conserves a copy of he settings made during commissioning or after an intervention. The procedure is specific according to the regulator type. 11.1.1. SYSAQUA…
-
44 SYSAQUA
English 11.2. RELOADING PARAMETERS FROM AN SD CARD The unit parameters contained on an SD card can be re-injected into the regulator. Caution The SD card must contain only one parameters file 1. Insert the locked SD card into the regulator 2. Access "Maintenance" then go to the menu "Maintenance” …
-
11.3. REPROGRAMMING THE REGULATOR WITH AN SD CARD
It is possible to re-program all or part of the regulator using an SD card. It should contain the following files depending on the intended reprogramming: Reprogramming Heat control (principal program) Languages dictionary and network variables Loaded and remote display Display web version Projet…
-
46 SYSAQUA
English 11.3.2. SYSAQUA 140/150/170/190/210 The reprogramming procedure: 1. Put the SD card SD N°1 in read / write mode 2. Switch on the regulator and insert the SD card N°1 3. Press the reset button with a rod 4. Press and hold and turn on the regulator. The red / green flashing indicates that the…
-
12. OVERVIEW OF THE HMI
12.1. SYSAQUA 20/25/30/35/40/45/55/65/75/90/105/125 Main overview 1/3 Current mode Red. H Entering water T. 42.3°C Leaving water T. 45.2°C Main Menu Status 1/4 1/3 Hydraulic circuit Pump0 Pump1 Access 1/12 Delegate Automatic Schedul. HMI 8.0°C 8.0°C 44°C 44°C 0.0% 0.0% Commissioning 1/12 03.02.2016…
-
48 SYSAQUA
English 12.2. SYSAQUA 140/150/170/190/210 Main overview 1/3 Current mode Red. H Entering water T. 42.3°C Leaving water T. 45.2°C Main Menu Status 1/4 1/3 Hydraulic circuit Pump0 Pump1 Access 1/13 Delegate Automatic Schedul. HMI 8.0°C 8.0°C 44°C 44°C 0.0% 0.0% Commissioning 1/12 03.02.2016 10:40:05…
-
13. LIST OF WARNING AND ALARMS
Message Type Definition Desc. 3phdet alarm Phase controller §8.7 Cpr1.inAlarm alarm fault in the digital output of compressor 1 §8.7 Cpr2.inAlarm alarm fault in the digital output of compressor 2 §8.7 DefrDTReq warning Defrosting by delta T §8.10 DefrDTShdnReq warning Defrosting prior to circuit…
-
50 SYSAQUA
Message Type Definition Desc. SrcFan.inAlarm alarm fault of the digital output of the fans §8.7 TDcrgGas.inAlarm alarm Fault in the sensor analog input §8.6 TDcrgGas.openloop alarm Sensor in open loop §8.6 TDcrgGas.shortedloop alarm sensor shorted §8.6 TDcrHiAlmCnt lock-out backflow temperature §8.3…
-
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. UM AQA 01-N-4GB Route de Verneuil 27570 Tillières-sur-Avre FRANCE & : +33 (0)2 : +33 (0)2 Part number : J581604GB Supersedes : UM AQA 01-N-3GB Systemair AC SAS