Инструкция на Тиристорные регуляторы скорости вентиляторов Systemair серии PKDT / PKDM
Тиристорные регуляторы скорости вентиляторов Systemair серии PKDT / PKDM трехфазные. Инструкция по эксплуатации.
Загружаем документ…
Текст инструкции
-
Operating instructions
Date 0628 Dcontrol Type PKDT / PKDM Controllers for voltage-regulated 3-phase motors Applications: • Speed controller for fans in refrigeration, air-conditioning and clean-room engineering • Pressure / temperature controller for refrigeration engineering Manufacturer: ZIEHL-ABEGG AG…
-
1. General
Before installation and start-up, read this manual carefully to ensure a correct use. Attention! Hazardous area! Danger owing to electric current or voltage!! Important information! • The copyright for these operating instructions remains to ZIEHL-ABEGG AG, Künzelsau. • The device is constructed in…
-
3. General description
3.1 Scope of applications The controlling device as described is intended for infinitely variable speed settings in voltage-regulated 3-phase motors for driving fans and pumps. 3.2 Technical data The name plate data refer to a maximum ambient temperature of 40°C. (with internal semiconductor fuses)…
-
{ { { Date 0628 Maximum cross section for line and motor connection PKDT5 / PKDM5..20: 2.5 mm2 PKDM25/35 : 6 mm2 PKDM25/35E: 10 mm2 PKDM50/80 (E) : 35 mm2 Stepless controlled output voltage approx. 20-100 % (line voltage) Rampup time / Rampdown time for PKDM 5…35: ca. 5 sec Rampup time / Rampdown…
-
3.4 Power decrease for increased ambient temperatures
The unit´s maximum permissible ambient temperature is depending on version 40° C, or 50°C.Up to that temperature a load of the quoted rated current is possible. The removal of heat in the unit due to power dissipation is dependent on the ambient temperature, so the maximum load has to be reduced if…
-
4. Installation
4.1 Mounting • Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting devices for proper installation of the unit! • Do not mount equipment on vibrating base! • Use the appropriate fixing equipment. The plastic washers must be installed between…
-
5. Electrical connections
5.1 Mains connection Power from the mains is connected to terminals: PE, L1, L2, L3, and N. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specifications () General description: Technical data and nameplate affixed to the side). The neutral conductor…
-
5.4 Motor noise
Motor noise can occur when fans are controlled using electronic voltage controllers (Phase cutting = series “P...”). Such noise can be system-dependently perceived as a disturbance. This noise is relatively low for fast-running fans where the noise from the air is high. The noise from motors in…
-
5.8 Enable ON / OFF
Enable ON / OFF (electronic disconnection) and reset after motor fault via potential free contact, terminals „D1“-„D1“. ♦ Device ON with contact closed ♦ Device OFF with contact open (“Fault“ relay K1 not released, terminals 11-14 bridged) Display for disconnection: Green LED flashes No…
-
The signal from the sensor for detection of the actual value is connected to the terminals “E” or “E1”and “GND”, for sensor in two-wire-technology (output 4-20 mA) to terminals "E" (E1) and "24 V". Be sure to observe correct polarity. The maximum length of the connecting cable shall be 30 m…
-
6. General settings and operating elements
6.1 Programming the operating mode (speed controller / P- controller) It is possible to use the device as a speed controller or as a P-controller. Selection of the function must first be made by setting the internal dipswitch and Jumper. Caution: not under voltage! Observe the safety notices!…
-
6.2 Controls
Operation as a speed rcontroller For operation as a speed controller, the output voltage is set manually by adjusting the built-in potentiometer, by an external potentiometer or external signal (0-10 V). Setting Potentiometer Output voltage 0-100 % (switch S1-3 ON position) (Control by internal…
-
7. Settings for operation
7.1 Settings for operation as a speed controller U Motor 100 % n-min = 0 % n-max = 100 n-max n-min = 35 % n-max = 85 % The output voltage is switched off to “0” for a controller signal less than 15 % of approximately 15 % of the mains voltage that is applied. For a controller signal greater than 20…
-
7.1.5 Operation with two variable output voltages (2 steps)
Switchover between two variable output voltages for the operational mode of external control (Dipswitch S1-3 OFF position) is possible by means of external potential-free contact-making. "E" "A" (+10 V) Step 1 (low speed) When there is no input signal connected to the input terminal “E“ or “E1”…
-
7.2 Settings for operation as a controller
U Motor 100 % n-min = 0 % n-max = 100 % n-max n-min = 35 % n-max = 85 % The output voltage is switched off to “0” for a controller signal less than 15 % of approximately 15 % of the mains voltage that is applied. For a controller signal greater than 20 %, the output voltage is switched on to approx.…
-
7.2.2 Adjusting the control range via potentiometer “Pband”
The control response can be adjusted to the system conditions with this setting - small control range = greater amplification and shorter control times - big control range = longer control times and higher controller stability Pband 5 30 % ♦ At active sensors with 0-10 V or 4-20 mA (factory setting)…
-
7.2.5 Setting with pressure / temperature refrigerant medium table for Type PKDT5 with MBG-30I
-
7.2.6 Setting with pressure / temperature refrigerant medium table for type PKDM5..80 with MBG-30I
-
7.2.7 Minimum airflow rate (Minimum air shutdown active / not active)
The minimum airflow rate can be switched "ON" or "OFF" using dipswitch. Dipswitch S1-2 OFF: Dipswitch S1-2 ON: Shutdown active = Without minimum airflow rate Shutdown not active = With minimum airflow rate (factory setting) When the setpoint is reached, the modulation is reduced to “0“ %, or to the…
-
8. Faults and rectification of these
8.1 Mains fault Function only for a connected inductive load The device is provided with a built-in phase-monitoring function for the mains supply. In the event of a mains interruption (failure of a fuse or mains phase) the unit switches off after a delay. The unit then switches on again…
-
8.4 Sensor-signal faults
Function only for operation as a P-controller The unit is fitted with a built-in monitoring device for the sensor signal. A fault is signalled over the internal LEDs in the event of a interruption or a short circuit in the sensor conductors, or measured values that are outside of the measuring range…
-
9. Enclosure
9.1 Connection diagram PKDT5 TBL02_54-GB 0628 Part-No. 00153238-GB Page 24 / 28
-
L2
-
9.3 Connection suggestion for several motors with motor protection unit type STDT
• • • Total motor protection: Automatic cut-off by thermocontact actuation ^ motor overtemperature. Button for Reset after malfunction. Line protection: A thermal over current sensor and a magnetic short circuit releasing elements are the parts of the integral line protection. Adjustment to the…
-
9.4 Dimension sheet
IP 54 model range: PKDT5, PKDM5/10 (PKDM12/15) Vor Öffnen des Deckels Gerät spannungsfrei schalten! Switch off the main supply before removing the cover! IP 54 model range: PKDM20 TBL02_54-GB 0628 Part-No. 00153238-GB Page 27 / 28
-
IP 54 model range: PKDM25/35 (PKDM50/80)