OPERATION AND INSTALLATION
-
CONTENTS
SPECIAL INFORMATION OPERATION 1. 1.1 1.2 1.3 1.4 1.5 General information�����������������������������������������3 Relevant documents�������������������������������������������� 3 Safety instructions����������������������������������������������� 3 Other symbols in this…
-
Special information
General information SPECIAL INFORMATION OPERATION The appliance may be used by children aged 8 and older and persons with reduced physical, sensory or mental capabilities or a lack of experience and know-how, provided that they are supervised or they have been instructed on how to use the appliance…
-
Safety
1.3 Other symbols in this documentation 2. Safety Note General information is identified by the adjacent symbol. ff Read these texts carefully. 2.1 Intended use Symbol ! Meaning Material losses (appliance damage, consequential losses and environmental pollution) Appliance disposal ff This symbol…
-
Appliance description
3. Appliance description 3.1 Properties The appliance is an air source heat pump that operates as a heating heat pump for outdoor installation. Heat is extracted from the outdoor air at a low temperature level, and is then transferred to the heating water at a higher temperature. The heating water…
-
Maintenance and care
5. Maintenance and care ! Material losses Maintenance work, such as checking the electrical safety, may only be carried out by a qualified contractor. A damp cloth is sufficient for cleaning all plastic and sheet metal parts. Never use abrasive or corrosive cleaning agents. Regularly check the…
-
Safety
7. 9. Safety ! Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance. 7.1 General safety instructions Preparation D0000060163 INSTALLATION We guarantee trouble-free function and operational reliability only if original accessories and spare…
-
Minimum clearances
≥500 ≥500 ≥1000 D0000078118 9.2.1 Minimum clearances with cascades ≥800 9.2 ≥300 ≥300 ≥300 D0000028299 ≥2000 D0000078119 ≥600 ≥1000 ff Maintain the minimum clearances to ensure trouble-free operation of the appliance and facilitate maintenance work. ≥250 ≥250 2 ≥300 91_00_00_0036 3 ff Never install…
-
WARNING Injury
The discharged cold air can cause condensation to be formed in the vicinity of the air outlet. ff Ensure that no risk of slipping due to wet conditions or ice formation occurs on adjacent footpaths and driveways at low temperatures. Foundations with recess (HPA-O 7 S Premium | HPA-O 7 CS Premium) 1…
-
HPA-O 7 CS Premium only) Installation on foundations Note The mounting bracket cannot be used in combination with the connection sets (AS-WP 1 and AS-WP 2). 2 1 C B A A A 100 B 300 C Depth of frost line 1 Heating flow 2 Heating return 3 Condensate drain conduit 4 Foundation 5 Gravel bed A Depth of…
-
9.5.2 T-support SK 1
Note ff Install a ribbon heater when mounting on the wall bracket or T-support (see chapter "Electrical connection / Ribbon heater"). ≥300 B D0000050006 A 9 A Depth of frost line B 300 1 Heating flow 2 Heating return 3 Conduit for supply lines 4 Foundation 5 T-support 6 Gravel bed 7 Condensate drain…
-
Preparing the electrical installation
WARNING Electrocution Carry out all electrical connection and installation work in accordance with national and regional regulations. WARNING Electrocution The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power supply by…
-
10.2 Heating water connection
! 10.4 Fitting the push-fit connectors Material losses The heating system to which the heat pump is connected must be installed by a qualified contractor in accordance with the water installation drawings that are part of the technical guide. To facilitate connection to the heating system, push-fit…
-
10.6 Filling the heating system Material losses Pipe ends must be deburred. ff Always use a pipe cutter to trim pipes. Carry out a fill water analysis before filling the system. This analysis may, for example, be requested from the relevant water supply utility. ff Push the pipe past the O-ring into…
-
10.8 Setting the flow rate on the heating side
! Material losses For operation without a buffer cylinder, it is essential that the electric emergency/booster heater (NHZ) is connected. The appliance is designed in such a way that no buffer cylinder is required in conjunction with appropriately sized area heating systems. Installations with…
-
Buffer cylinder always
required HPA-O 13 S Premium No HPA-O 13 C Premium No HPA-O 13 CS Premium No Recommended buffer cylinder volume, underfloor heating system ff Install the open heating circuit(s) in the lead room (room where the external programming unit of the heat pump control unit is installed, such as in the…
-
11. Electrical connection
WARNING Electrocution ff Before working on the appliance, isolate it from the power supply at the control panel. Note The leakage current of this appliance can be > 3.5 mA. The connection must only be made by a qualified contractor and in accordance with these instructions. Note Please observe the…
-
ff Pivot the terminal area to the side. ff Connect the cables according to the following diagram. L N X5 / DHC 1/N/PE~230/50 C 32A D0000075146 3,0 kW 3,2 kW 6,2 kW ff Fix the terminal area in place with the locking mechanism. ff Connect the electric emergency/booster heater if you want to utilise…
-
11.5 Closing the terminal area
1 2 A. 1 Serrated washer 2 Screw ff Secure the cover with the screw and serrated washer. ff Connect the following components to the heat pump manager in accordance with the technical guides: Circulation pump for the heat consumer side Outside temperature sensor Return sensor (only for operation with…
-
Commissioning
12.1.3 High limit safety cut-out Closing the terminal area At ambient temperatures below -15 °C it is possible that the high limit safety cut-out of the electric emergency/booster heater may trip. ff Check whether the high limit safety cut-out has tripped. 26_03_01_1880 26_03_01_1867 1 1 Electric…
-
Settings
12.3 Initial start-up 12.3.1 Heating curve adjustment The efficiency of a heat pump decreases as the flow temperature rises. The heating curve should therefore be adjusted with care. Heating curves that are set too high cause the zone valves or thermostatic valves to close, which may lead to the…
-
Appliance shutdown
Setting in the Sound power Heating WPM level output Output reMaximum value Maximum at stricted to due to output A-7/W35 [%] restriction [kW] [dB(A)] 70 52 4.80 HPA-O 7 (C)S Premium 63 50 4.30 HPA-O 10 (C) Premium 70 54 7.10 70 54 7.10 HPA-O 13 (C)(S) Premium 70 57 9.00 61 54 7.85 ff In the “PROGRAMS…
-
16.1 Checking the IWS DIP switch settings
IWS Carry out the following steps to make the IWS accessible. 1 2 26_03_01_1866 BA ff Remove the cover. 4 3 26_03_01_0921 BA 1 LEDs 2 DIP switch (WP-Typ) 3 Reset button 4 DIP switch (BA) DIP switch (WP-Typ) The DIP switch (WP-Typ) on the IWS serves to set the relevant heat pump type. 26_03_01_1869…
-
16.2 Light emitting diodes (LEDs)
DIP switch (BA) ff Check whether the DIP switch (BA) is set correctly. Heating mode BA Heating and cooling mode BA BA BA D0000051579 ON 16.1.1 Closing the terminal area 26_03_01_0921 1 D0000057052 ON 1 LEDs 2 Reset button The following table shows the meaning of the LEDs on the IWS. LED indicator…
-
16.4 Resetting the high limit safety cut-out
The electric emergency/booster heater stops if the heating water temperature exceeds 85 °C, for example if the flow rate is too low. 26_03_01_1880 1 ff Carry out a manual defrost, as many times as necessary, until the fan runs freely again. Observe the information in the WPM instructions and…
-
17. Specification
17.1 Dimensions and connections HPA-O 7 S Premium | HPA-O 7 CS Premium d45 1160 900 1270 593 g02 82 157 g01 d47 100 e02 e01 e01 Heating flow e02 Heating return d45 d47 g01 g02 Condensate drain Drain Air intake Air discharge www.stiebel-eltron.com Type of connection Diameter Type of connection…
-
HPA-O 10 Premium | HPA-O 10 C Premium | HPA-O 13 Premium | HPA-O 13 S Premium | HPA-O 13 C Premium | HPAO 13 CS Premium d45 1380 1490 593 g02 82 157 1045 g01 d47 100 e02 e01 e01 e02 d45 d47 g01 g02 Heating flow Type of connection Diameter Heating return Type of connection Diameter Condensate drain…
-
www.stiebel-eltron.com
-
17.2 Wiring diagram
-
ung
-
HPA-O 10 Premium | HPA-O 10 C Premium | HPA-O 13 Premium | HPA-O 13 C Premium (three-phase)
-
g
-
Z3 Interference suppression filter 17.3 Application limit 17.3.1 Heating -25 -5 D0000075400 Integral heat pump control unit (IWS) Inverter, compressor Filter assembly DC assembly Heating flow temperature sensor - KTY Heating return temperature sensor - KTY Hot gas temperature sensor - PT1000 Outdoor…
-
17.4 Output diagrams
-
Cooling capacity
-
таблицы и схемы — в просмотре
-
Cooling capacity
-
17.5 Data table
-