AIR-COOLED
MODULAR CHILLER UNIT INSTALLATION AND USER MANUAL SCV-xxEA AIR CONDITIONING
-
“Original instructions”
-
1. INTRODUCTION
1.1 Main characteristics Air-cooled heat pump unit consists of one or more modules. Each module has an independent electronic control unit. In addition, there is also a network in the unit enabling communications among modules. Compact and easy to transport and install, the air-cooled heat pump unit…
-
2. SAFETY CONSIDERATION
CAUTION To prevent injuries or property losses, make sure to observe the following instructions. Failure to do so may cause injuries or losses. Ensure that the residual current device (RCD) is installed. The RCD must be installed. Failure to install it may result in electric shock. There are two…
-
BEFORE INSTALLATION 3.1 Handling of the unit The angle of inclination should not be more than 15º when carrying the unit in case of overturn of the unit. a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the length of each rod must be more than the…
-
IMPORTANT INFORMATION ON REFRIGERANT This product contains fluorinated greenhouse gases covered 6. PRECAUTIONS ON INSTALLATION 6.1 Outline dimensional drawing 6.1.1 SCV-300EA by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type: R410A GWP(1) value: 2088 (1) GWP = global…
-
Table 6-1
SCV-300EA SCV-600EA SCV-900EA A 1870 2220 3220 B 1000 1055 1095 C 1175 1325 1513 D E F C Model I G Left view B Front view G 788 1105 2116 H 880 958 1008 I NOTE After installing the spring damper, the total height of the unit will increase by 135mm or so. A Top view Fig. 6-2 outline dimensional of…
-
6.3 Space requirements for parallel installation of
multiple Modular units To avoid back flow of the air in the condenser and operational faults of the unit, the parallel installation of multiple Modular units can follow the direction A and D as shown in Fig. 6-5, the spaces between the unit and the obstacle are given in Table 6-2, and the space…
-
6.5 Installation of damping devices
6.4 Installation foundation a. The unit should be located on the horizontal foundation, the ground floor or the roof which can bear operating weight of the unit and the weight of maintenance personnel. Refer to Table 12-1 (Table of applicable models and parameters) for operating weight. b. If the…
-
7. TYPICAL APPLICATION EXAMPLES
7.1 Application 1 Space heating only application without room thermostat connected to the unit. The temperature in each room is controlled by a valve on each water circuit. Heating is provided through floor heating loops. Tn T2 T1 10 12 1.2 1.3 1.1 9.1 11 Mn M2 M1 1.4 1.5 9.2 8 FHL1 FHL2 Fig.7-1…
-
7.2 Application 2
Space cooling and heating application without a room thermostat connected to the unit, but with heating/cooling thermostat controlling the fan coil units. Cooling is provided through the fan coil units only. Tn T2 T1 10 12 1.2 1.3 1.1 9.1 11 Mn M2 M1 1.4 1.5 9.2 8 FCU1 FCU2 Fig.7-2 diagram of…
-
7.3 Application 3
Space cooling and heating application without a room thermostat connected to the unit, but with heating/cooling thermostat controlling the fan coil units. Heating is provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only. Tn T2 T1 12 Mn M2 M1 18…
-
8. OVERVIEW OF THE UNIT
8.1 Main parts of the uint Fig. 8-1 main parts of SCV-300EA Fig. 8-2 main parts of SCV-600EA 11
-
Fig. 8-3 main parts of SCV-900EA
NO. NAME Air outlet Top cover Electric control box NO. NAME Air inlet Water outlet wire controller (It can be placed indoors) Compressor Evaporator Condenser Water intlet 12
-
8.2 Opening the uint
By means of a detachable service panel, the maintenance personnel can easily access the interior components of the unit. Door 2 Door 1 Door 3 Door 4 Fig. 8-4 doors of SCV-300EA Door 1 give access to the compartment of water pipes and water side heat exchanger. Door 2/3/4 give access to the hydraulic…
-
Door 2
Door 1 Door 3 Door 4 Fig. 8-5 doors of SCV-600EA Door 1 give access to the compartment of water pipes ,water side heat exchanger,acculator and liquid-vapor separator. Door 2/3/4 give access to the hydraulic compartment and electrical parts. 14
-
Door 2
Door 1 Door 3 Door 4 Fig. 8-6 doors of SCV-900EA Door 1 give access to the compartment of water pipes ,water side heat exchanger,acculator and liquid-vapor separator. Door 2/3/4 give access to the hydraulic compartment and electrical parts. 15
-
8.3 main components
8.3.1 main components of SCV-300EA Fan motor Wired controller Electric control box DC inverter compressor liquid-vapor separator Oil separator Fig. 8-7 SCV-300EA rear view Water side heat exchanger Manual air purge valve Safety valve Water inlet pipe Water w switch Manual water drain valve Water…
-
Accumulator
Low pressure switch High pressure sensor Solenoid valve SV4 High pressure switch Discharge temperature switch Four-way valve Electronic expansion valve Low pressure gauge point High pressure gauge point Fig.8-9 SCV-300EA top view 17
-
8.3.2 main components of SCV-600EA
Fan motor Electric control box DC inverter compressor Oil separator Fig.8-10 SCV-600EA rear view Safety valve Accumulator Air purge valve Water side heat exchanger Water inlet pipe liquid-vapor separator Manual water drain valve Water w switch Water outlet pipe Fig.8-11 SCV-600EA front view 18
-
Low pressure
switch Solenoid valve SV4 High pressure sensor Discharge temperature switch High pressure switch Four-way valve Electronic expansion valve Low pressure gauge point High pressure gauge point Fig.8-12 SCV-600EA top view 19
-
8.3.3 main components of SCV-900EA
Fan motor Electric control box Wired controller Oil separator DC inverter compressor heat exchange DC inverter compressor Fig.8-13 SCV-900EA rear view Water side heat exchanger Safety valve Manual air purge valve Water inlet pipe Manual water drain valve Water outlet pipe Accumulator liquid-vapor…
-
singal-pass
solenoid valve Four-way valve singal-pass solenoid valve singal-pass solenoid valve singal-pass solenoid valve Low pressure switch Electronic expansion valve Electronic expansion valve Low pressure gauge point Electronic expansion valve High pressure switch singal-pass solenoid valve High pressure…
-
8.4 System diagram
8.4.1 diagram of SCV-300EA Fig.8-168-17,8-18 are the function diagrams of the 30ǃ60ǃ90 kW Full-DC Inverter Modular Air-cooled Heat Pump Unit and it shows the internal system structure to users, which is made up of main components (such as compressors, electronic expansion valves, Condenser, plate…
-
7] 7 7 (;9$ 7DI 7ZL LQOHW 7DI 69 7ZR +HDW (;9% 69 7K Fig.8-17 SCV-600EA piping diagram Table 8-2 Legend 1 Compressor1 2 Compressor2 3 CCHA (Crankcase heater A) 4 CCHB (Crankcase heater B) 5 Switch_TpA (Discharge temperature control switch A) 6 Switch_TpB ( Discharge temperature control switch B) 7…
-
7] 7 7 (;9$ 69 7DI 7$ 7ZL 69 (;9& (;9% 69 69% 69$ 7ZR 7% 7DI Fig.8-18 SCV-900EA piping diagram Table 8-3 Legend 1 Compressor1 2 Compressor2 3 CCHA (Crankcase heater A) 4 CCHB (Crankcase heater B) 5 Switch_TpA (Discharge temperature control switch A) 6 Switch_TpB ( Discharge temperature control…
-
8.5 Outdoor unit PCBs
8.5.1 MAIN PCB Label descriptions are given in Table 8-4 Figure 8-19 Main PCB of SCV-300EA and SCV-600EA Table 8-4 Content No. 1 CN1:Pump 1 connecon 2 CN30: Power sequence detecon connecon 3 S5: DIP switches 4 CN72: Power supply to user interface 5 ENC1: Unit capacity dial switch 25
-
ENC3: Address dial switch 7 DSP1: Digital display 8 FUS1:Fuse 9 CN43: Power input 10 CN12_1,CN12_2: Solenoid valve (SV4) drive ports 11 IC25: Main control chip 12 CN64: Debug port 13 CN16: Four-way valve drive port 14 CN5,CN5_1: Water side heat exchanger heater s connecon 15 CN4,CN4_1: Water ow…
-
Label descriptions are given in Table 8-5
Figure 8-20 Main PCB of SCV-900EA 27
-
Table 8-5
Detail information No. CN30:Input of three-phase four-wire power supply (fault code E1) Input of transformer, 220-240V AC current. (only valid for the main unit) Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle should be 120º among them. If the…
-
CN2:HEAT2.Water Tank Auxiliary Heater
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply,so special attention should be paid when installing the water tank auxiliary heater. CN2:HEAT1.Pipeline Auxiliary Heater Attention: the control port value of the pump actually detected is…
-
CN31:Temperature sensors input port
^ !"#$%'` Taf2:Water side antifreeze temperature sensor( !"#$%). Two:Unit water outlet temperature sensor( !"#$%). Twi:Unit water inlet temperature sensor( !"#$%). Tw:Total water outlet temperature sensor when several units are connected in parallel( !"#$%). #{|} !"#$%'` #{} ! !"#$%'` CN15:Detection…
-
CN7:Target water temperature switching port
ENC2:POWER DIP switch of outdoor unit capacity: 1, 60KW; 2, 90KW CN74:The power supply port of the wired controller .(DC9V) ENC4:NET_ADDRESS DIP switch 0-F of outdoor unit network address is enabled, which represent address 0-15 S12:Dip switch S12-1:ON of S12-1 is enable(factory default)…
-
8.6 Electric wiring
8.6.1 Electric wiring CAUTION 1. The air-conditioner should apply special power supply, whose voltage should conform to rated voltage. 2. Wiring construction must be conducted by the professional technicians according to the labeling on the circuit diagram. 3. The power wire and the grounding wire…
-
Step 5. The wires of the main power must pass the bonding clamp
Step 6. Wires should be connected firmly to the connection terminals L1, L2, L3and N. Step 7. Phase sequences must be consistent when the wires of the main power. Step 8. The main power should be located out of easy reach of non-professional maintenance personnel, to avoid mal-operation and improve…
-
k. All low positions of the water system should be provided
with drainage ports, to drain water in the evaporator and the system completely; and all high positions should be supplied with discharge valves, to facilitate expelling air from the pipeline. The discharge valves and drainage ports should not be under heat preservation, to facilitate maintenance.…
-
8.7.2 Connection drawing of pipeline
Expansion tank Water replenishing Dirt discharge valve Main unit Y-type filter, @< unit Differential pressure by-pass valve unit Terminal Drain valve Two-way valve Auxiliary electric heater Three-way valve This is the water system of standard module, which pump is not provided. Symbol explanation…
-
8.7.3 Connection mode of pipe
The water inlet and outlet pipes are installed and connected as shown in the following figures. SCV-300EA model uses screwed connection, while the SCV-600EA and SCV-900EA models use hoop connection. For the specifications of the water pipes and screw thread, see the Table 8-7 below. Table 8-7 Model…
-
Fig.8-26 connection mode of SCV-900EA pipe
8.7.4 Design of the store tank in the system In certain occasion (especially in manufacture cooling process), for conforming the system water content requirement, it’s necessary to mount a tank equipping with a cut- off baffle at the system to avoid water short following schemes: Error…
-
From equation 1
Water tank design volume = Chilled water system minimum water volume - Water pipework volume - Chiller heat exchanger volume - FCU heat exchanger volume Two factors place lower limits on the chilled water system required water volume: 1. Cooling mode limit: To ensure reliable system operation, the…
-
Ь
Q s is the heat energy (in kcal) required for room heating during the defrosting operation, which may be obtained from: Ь Ь Q s = Q h x 860 x ( t f / 60) 7 Where: Ь Ь Equation tf is the duration of defrosting operation (in mins) Tt is the permitted water system temperature drop during defrosng…
-
8.7.5 Minimum chilled water flow
The minimum chilled water flow is shown in the table 8-8 If the system flow is less than the minimum unit flow rate, the evaporator flow can be recirculated, as shown in the diagram. h3: Water resistance of the longest water-loop distance, includes: pipe resistance, different valve’s resistance…
-
8.7.10 Installation of single-module water system pipeline
Electric control box Water inlet Total water outlet temperature sensor Water outlet Fig.8-30 SCV-300EA Electric control box Water inlet Total water outlet temperature sensor Water outlet Fig.8-31 SCV-600EA Electric control box Water inlet Water outlet Total water outlet temperature sensor Fig.8-32…
-
8.7.11 Installation of multi-module water system pipeline
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows. 8.7.11.1 Installation mode of multi-module combination water system pipeline No.n module No.(n-1) module No.1 module No.(n-1) address No.(n-2) address No.0 address Drill dead hole…
-
9. STRAT-UP AND CONFIGRUATION
9.1 Initial start-up at low outdoor ambient temperatures 09/20/2015 During initial start-up and when water temperature is low, it is important that the water is heated gradually. Failure to do so may result in concrete floors cracking due to rapid temperature change. Please contact the responsible…
-
10. TEST RUN AND FINAL CHECK
10.1 Check item table after installation Table 10-1 Checking item Description Yes Units are fixed mounting on level base. Ventilating space for heat exchanger at the air side is meeting for requirement Maintenance space is meeting for requirement. Whether installing site is meet for requirements…
-
10.2 Trial run
10.2.1 Start up the controller and check whether the unit displays a fault code. If a fault occurs, remove the fault first, and start the unit according to the operating method in the “unit control instruction”, after determining that there is no fault existing in the unit. 10.2.2 Conduct trial run…
-
11. MAINTENANCE AND UPKEEP
11.1 Failure information and code In case the unit runs under abnormal condition, failure protection code will display on both control panel and wired controller, and the indicator on the wired controller will flash with 1Hz. The display codes are shown in the following table: Table11-1 No. 1…
-
PA Cooling return water temperature too high 27 Pb Winter antifreeze protection 28 Recovered upon failure recovery Recovered upon failure recovery Occurs 10 times in 150 minutes. The failure needs to be recovered manually or power disconnection. Protection occurs 3 times in 60 minutes and the…
-
Table 11-2
SCV-900EA No. Code 1 E0 Main control parameter memory EPROM failure Recovered upon failure recovery 2 E1 Phase sequence failure of main control board check Recovered upon failure recovery 3 E2 Main control and wired control communication failure Recovered upon failure recovery 4 E3 Total water…
-
A valve not inserted fault 1HE
36 HE B valve not inserted fault 2HE C valve not inserted fault 3HE Recovered upon failure recovery Recovered upon failure recovery Recovered upon failure recovery 1F0: IPM module communication failure Recovered upon failure recovery 2F0: IPM module communication failure Recovered upon failure…
-
11.2 Data display of wired controller
a. Ordinary displayed data are displayed in all display pages. * serial number can query 16 sets main units’ status information from #0̚#15. Press “ ” or “ ” to adjust the spot check sequence number of one main unit then can query all the status information of this unit. Ȑ b. If the unit…
-
Table 11-4
SCV-900EA No. Sport Check Item 0 34 33.xx Static pressure selection (0 static pressure by default) Standby: main unit address (88 on the left) + number of online sets (88 on the right) On: display frequency Defrosting: dFdF 35 34.xx DC voltage A (reserved) 36 35.xx DC voltage B (reserved) 37 36.xx…
-
11.5 Care and maintenance
11.9 First startup after shutdown Maintenance period It's recommended that before cooling in summer and heating in winter every year, consult local air conditioner customer service center to check and maintain the unit, to prevent air conditioner errors which bring inconvenience to your life and…
-
11.16 Wiring of “ALARM” port
11.13 System antifreezing Connect the device provided by user to the “ALARM” ports of the module units as follows. In case of freezing at the water-side heat exchanger interval channel, severe damage may be caused, i.e. heat exchange may be broken and appears leakage. This damage of frost crack is…
-
11.18 Replacement of safety valve
Replace the safety valve as follows: 1) Reclaim the refrigerant completely in the system. Doing so requires professional staff and equipment; 2) Note to protect the tank coating. Avoid damage to coating from external force or high temperature when removing and installing the safety valve; 3) Heat…
-
RECORD TABLE OF TEST RUN AND MAINTENANCE
Table 11-5 Model: Code labeled on the unit: Customer name and address: Date: 1. Whether there is sufficient water flow passing waterside heat exchanger? ( 2. Whether leakage detection has been made on all the water pipe? 3. Whether pump, fan and motor are lubricated? ( ( ) 4. Whether unit has been…
-
RECORD TABLE OF ROUTINE RUNNING
Table 11-6 Model: Date: Weather: Operation time: Startup ( Outdoor temperature ) Shutdown ( ) Dry bulb đ Wet bulb đ đ High pressure 03D Low pressure 03D Voltage 9 Current $ Inlet (dry bulb) đ Outlet (dry bulb) đ Inlet đ Outlet đ Indoor temperature Compressor Air temperature of air-side heat…
-
12. APPLICABLE MODELS AND MAIN PARAMETERS
Table 12-1 Model SCV-300EA SCV-600EA SCV-900EA Cooling capacity kW Heating capacity kW Standard cooling input kW 10.8 22 36.8 Cooling rated current A 16.7 33.9 60 Standard heating input kW 10.5 20.3 32.8 Heating rated current A 16.2 31.3 42 Power supply 380-415V 3N~ 50Hz Operation control Control of…
-
13. INFORMATION REQUIREMENTS
Table 13-1 Information requirements for comfort chillers Model(s): SCV-300EA Outdoor side heat exchanger of chiller: Air to water Indoor side heat exchanger chiller: Water Type: Compressor driven vapour compression Driver of compressor: Item Rated cooling capacity Electric motor Symbol Value Unit…
-
Table 13-2
Information requirements for comfort chillers Model(s): SCV-600EA Outdoor side heat exchanger of chiller: Air to water Indoor side heat exchanger chiller: Water Type: Compressor driven vapour compression Driver of compressor: Item Rated cooling capacity Electric motor Symbol Value Unit Prated,c 55.5…
-
Table 13-3
Information requirements for comfort chillers Model(s): SCV-900EA Outdoor side heat exchanger of chiller: Air to water Indoor side heat exchanger chiller: Water Type: Compressor driven vapour compression Driver of compressor: Item Rated cooling capacity Electric motor Symbol Value Unit Prated,c 82…
-
Table 13-4
Information requirements for heat pump space heaters and heat pump combination heaters Model(s): Air-to-water heat pump: Water-to-water heat pump: Brine-to-water heat pump: Low-temperature heat pump: SCV-300EA [yes] [yes/no] [yes/no] [yes/no] For low-temperature heat pumps, parameters shall be…
-
Table 13-5
Information requirements for heat pump space heaters and heat pump combination heaters SCV-600EA Model(s): Air-to-water heat pump: [yes] Water-to-water heat pump: [yes/no] Brine-to-water heat pump: [yes/no] Low-temperature heat pump: [yes/no] Equipped with a supplementary heater: [yes/no] Heat pump…
-
Table 13-6
Information requirements for heat pump space heaters and heat pump combination heaters SCV-900EA Model(s): Air-to-water heat pump: [yes] Water-to-water heat pump: [yes/no] Brine-to-water heat pump: [yes/no] Low-temperature heat pump: [yes/no] Equipped with a supplementary heater: [yes/no] Heat pump…
-