GPA-II Series
Energy-saving Pipeline Canned Motor Pump Installation and Operation Manual Hefei Xinhu Canned Motor Pump Co., Ltd.
-
Notes
01. Read the installation manual carefully before installation and use. 11. Some models are not suitable for drinking water. 12. The liquid may be high-temperature and high-pressure; therefore, the liquid in the system must be completely drained or the shut-off valves on both sides must be c l o s e…
-
and abnormality of motor is detected, and contact your vendor or service center
immediately. 19. If trouble cannot be addressed according to the manual, please close the valves on the inlet and outlet of the pump immediately, cut off power supply and contact your vendor or service center immediately. 20. This product shall be put in a place out of reach of children. After…
-
2. General
2.1. GPA series circulation motor pump is mainly used in domestic heating and hot water system. 2.2. Advantages Easy installation and start-up · The product is most applicable to the following systems: Provided with self-adaptive mode AUTO (Initial setting). In most cases, the motor pump needs no…
-
3. Operating Conditions
3.1. Ambient Temperature Ambient temperature: 0 ℃ ~+40 ℃ 3.2. Relative humidity(RH): Max. humidity: 95% 3.3. Medium (liquid delivery) temperature Liquid delivery temperature: +2 ℃ ~110 ℃ To avoid condensation in control box and the stator, the temperature of liquid pumped by the motor pump must be…
-
4. Installation
4.1. Installation · When i n s t a l l i n g G PA s e r i e s circulation pump, the arrow on motor pump case indicates the flow direction of liquid through the pump. · When installing the motor pump in the pipeline, two supplied gaskets must be installed at the inlet and outlet. · During the…
-
4.2. Position of Junction Box
4.3. Changing Position of Junction Box The junction box can be rotated in a step of 90° The procedures for changing the position of junction box are as follows: 1. Close the valves at the inlet and outlet and release the pressure; 2. Unscrew and remove the four socket head screws that fasten the…
-
Warning
Pumping liquid may be high-temperature and high-pressure; therefore, the liquid in the system must be completely drained or the valves on both sides of motor pump must be closed before removing the socket head screws. 4.4. Thermal Insulation of Motor Pump Body Note Caution Limiting the heat loss of…
-
Min.°5.5mm_
-
Electrical connection and protection shall comply with
local codes and norms. Warning . The motor pump must be earthed The motor pump must be connected to an external power switch, and the minimum space between all the electrodes is 3mm. · GPA series circulation motor pump needs no protection from external motor. · Check if the supply voltage and…
-
6. Control Panel
6.1. Controls on Control Panel Position Descriptions Indication lamp area in the Night Mode (AUTO). Button to start or turn off Night Mode (AUTO). Monitor that displays the actual power consumption of motor pump in Watt. Indication lamp area of eight operation modes set by motor pump. Indication…
-
Descriptions
Button Times Indication Lamp Area AUTO (Initial setting) BL1 BL2 HD1 HD2 Ⅲ Ⅱ Ⅰ PWM Self-adaptive (AUTO) Lowest Proportional Pressure Curve Highest Proportional Pressure Curve Lowest Constant Pressure Curve Highest Constant Pressure Curve Constant Velocity Curve, Velocity III Constant Velocity Curve…
-
7. Pump Setting
7.1. Pump Setting Based on System Type Initial setting= AUTO (Self-adaptive mode) Recommended and available pump setting Motor Pump Setting Position System Type A Floor heating system B Dual pipeline heating system Single pipeline heating system C Recommended Options AUTO HD1 HD2 PWM AUTO BL2 PWM…
-
· It may take several minutes or even hours to reach the optimal operation mode after motor
pump setting is changed from the optimal setting (the “Recommended abovemention”) to other optional setting. If the optimal setting of motor pump fails to enable each room to obtain desired heat distribution, then you should change the motor pump setting to other settings. · Please refer to Section…
-
8. Night Mode (AUTO)
8.1. Basic Principle Warning Night Mode is unavailable for the GPA series motor pump installed in gas boiler heating system with small water capacity. Note If VelocityⅠ, VelocityⅡ, or Velocity Ⅲ mode have been selected, theNight Mode will be disabled; if PWM mode signal input is selected, then…
-
To ensure that the best status is realized in Night Mod, the following conditions
must be satisfied: · The motor pump must be installed in the water inlet pipeline of the system and near the water outlet of boiler. · If the motor pump is installed in the water return pipeline of the system, then the Night Mode function will be disabled. · The system must be included with liquid…
-
9. PWM Signal Control Mode
3) Duty Cycle( d%) 9.1. Control and Signal Mode T = 2 ms( 500Hz) t = 0.6 ms d%=100×0.6/2=30% UiH = 4~24V UiL ≤ 1V IiH ≤ 10mA 1) Control Principle GPAXX-XX II model pump is controlled by modulated LV PWM (Pulse Width Modulation) digital signal, which means that the variance of velocity depends on the…
-
9.3. PWM Input Signal
9.3.1PWMinputsignalprofil PWM1(heating) · In area of high duty-cycle PWM1 ·When PWM1 input signal is 0% or 100%, the signal, when the input signal pump will switch to non-PWM mode (normal fluctuates in the critical point, there mode), and the default system will have no will be a delay area to…
-
9.3.2 PWM input signal profile PWM2(solar)
· In area of low duty-cycle PWM2 signal, when the input signal fluctuates in the critical point, there will be a delay area to prevent frequent stop and start of the pump. · Without PWM2 signal percentages, the circulator will stop for safety reasons. If a signal is missing, for example due to a…
-
9.4. PWM Feedback Signal
PWM feedback signal can provide operation status of the pump, such as power loss or all kinds of alarm/warning modes. PWM feedback signal will feed back exclusive alarming information. If the power voltage detects under voltage signal values, its output signal will be set to 75%. Provided sundries…
-
9.5. How to use the signals
The signal can be used to measure power consumption of the pump. The pump signal can be used to detect the actual operating point of the system rather than measuring by the current controlled by the system. The signal is also applicable to comparing velocity setting value and feedback. For example…
-
10. Bypass valve system installed between
the Inlet pipeline and return pipeline 10.1. Purposes of bypass valve Chapter 7 Bypass valve The purpose of bypass valve: when all the valves and/or temperature-sensing valves of heat radiator in the floor heating loop are closed, it can ensure that the heat from boiler can be distributed. Elements…
-
10.2. Manually-operated Bypass Valve
In accordance with the following procedures: 1. When regulating bypass valve, the pump shall be in Setting I (Velocity I Mode). The minimum flow rate(Q min) of the system shall be always guaranteed. Please refer to bypass valve manual provided by the manufacturer. 2. After the regulating of bypass…
-
11.2. Exhaust the Motor Pump
GPA series motor pump is equipped with self-venting function. Before the start up, it is not necessary to vent the air. Air in the motor pump may cause noise. After the motor pump is put into operation for several minutes, the noise will disappear. Based on the system scale and structure, set the…
-
12. Motor Pump Setting and Performance
12.1. Relations between Pump Setting and Performance PWM mode performance running area (Gear I-Gear III) Setting Pump Characteristics Curve AUTO (Initial Setting) Highest to Lowest Proportional Pressure Curve BL1 Lowest Proportional Pressure Curve The operating point of the pump will move up and…
-
Pump
Characteristics Curve Functions Lowest Constant Pressure Curve The operating point of the pump will move around the lowest constant pressure curve based on the demand of system flow rate. The supply pressure of pump remains constant and it is irrelevant with the flow rate. Highest Constant Pressure…
-
13. Performance Curve
13.1. Guide on Performance Curve Every setting of the motor pump has corresponding performance curve (Q/H curve). However AUTO (Self Adaptive Mode) mode covers just one performance scope. The area of PWM signal control performance curve (Q/H curve) is between motor pump velocity I-III. The input…
-
13.3. GPA××-4 II Series Performance Curve
GPAXX-4 II Performance Curve GPAXX-4 II PWM Signal Control Performance Curve P1W 27
-
13.4. GPA××-5 II Series Performance Curve
GPAXX-5 II Performance Curve GPAXX-5 II PWM Signal Control Performance Curve 28
-
13.5. GPA××-6 II Series Performance Curve
GPAXX-6 II Performance Curve GPAXX-6 II PWM Signal Control Performance Curve 29
-
13.6. GPA××-8 II Series Performance Curve
GPAXX-8 II Performance Curve GPAXX-8 II PWM Signal Control Performance Curve 30
-
14. Features
14.1. Nameplate Instructions No. Descriptions Manufacturer Name Product Model Digit 1 to digit 6 indicates manufacturing date Product No. Digit 7 to digit 10 indicates serial number Minimum input power P1 Power Maximum input power P1 (Watt) Minimum current Current (Amp) Maximum current Maximum…
-
14.2. Model Instructions
The model of motor pump is composed of capitalized Latin letters and Arabic numbers, which means: 01: Eight shifts+ night mode+ signal control Functional specification L: Grooving of base (for drainage of condensation) II : Side mounting of junction box Product code C: Check valve installed at the…
-
15. Technical Parameters and Installation Dimensions
15.1. Technical Parameters Power Supply Voltage Motor Protection Degree of Protection Insulation Class Relative Humidity(RH) System Load Bearing Suction Port Pressure EMC Standard Sound Pressure Class Ambient Temperature Temperature Grade Surface Temperature Liquid Temperature 1×230V…
-
15.2. Installation Dimensions
Power (W) Product Model GPA20-4PⅡ GPA20-4Ⅱ GPA25-4Ⅱ GPA32-4Ⅱ GPA20-5PⅡ GPA20-5Ⅱ GPA25-5Ⅱ GPA32-5Ⅱ GPA20-6PⅡ GPA20-6Ⅱ GPA25-6Ⅱ GPA32-6Ⅱ GPA20-8PⅡ GPA20-8Ⅱ GPA25-8Ⅱ GPA32-8Ⅱ Material of Pump Body Dimension (mm) Cast Plastic Copper SS Iron ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●…
-
16. Trouble-Shooting Schedule
Warning Before conducting any maintenance and repair of the motor pump, ensure that power supply has been cut off and will not be connected accidentally. Symptom Motor pump cannot be started Control Panel Cause Equipment fuse burned Replace the fuse Indication lamp “Off” The circuit breaker of…
-
Product Warranty
Hefei Xinhu Canned Motor Pump Co., Ltd offers 12 months of quality warranty for its products since the date of sales, and is responsible for product malfunctions or damaged due to manufacturing and material defects. This warranty is valid only when the product is installed strictly in accordance…