TECHNICAL & SERVICE MANUAL
-
When Transporting
Important! Please Read Before Starting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. This air conditioning…
-
1. OPERATING RANGE
-
2. SPECIFICATIONS
2-1. Unit Specifications Indoor Unit Outdoor Unit SAP – K161GJA SAP – C161GA Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Capacity kW BTU/h 4.70 16,000 / / Air circulation (High) Moisture removal (High) m3/h Liters/h 4.70 16,000 760 2.3 V A W % W/W A 198 ~…
-
SAP – K161GJA
SAP – C161JA Power Source 220V Single phase 60Hz Voltage rating 220 V Performance Cooling Capacity kW BTU/h Air circulation (High) Moisture removal (High) m3/h Liters/h 4.70 16,000 760 2.3 V A W % W/W A 198 ~ 242 8.1 1,770 99 2.7 41 Electrical Rating Cooling Available voltage range Running amperes…
-
SAP – K181GJA
SAP – C181GA SAP – K181MBA SAP – C181MA Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Capacity kW BTU/h 5.15 17,600 / / Air circulation (High) Moisture removal (High) m3/h Liters/h 5.15 17,600 760 2.7 V A W % W/W A 198 ~ 264 9.5 2,060 94 2.5 46 Electrical…
-
SAP – K181GJA
SAP – C181JA SAP – K181MBA SAP – C181BA Power Source 220V Single phase 60Hz Voltage rating 220 V Performance Cooling Capacity kW BTU/h Air circulation (High) Moisture removal (High) m3/h Liters/h 5.15 17,600 760 2.7 V A W % W/W A 198 ~ 242 7.8 1,700 99 3.0 41 Electrical Rating Cooling Available…
-
SAP – K241GJA
SAP – C241GA SAP – K241GJA SAP – C241MA Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Capacity kW BTU/h 6.40 21,800 / / Air circulation (High) Moisture removal (High) m3/h Liters/h 6.45 22,000 830 3.3 V A W % W/W A 198 ~ 264 12.8 2,680 91 2.4 70 Electrical…
-
SAP – K241GJA
SAP – C241JA SAP – K241GJA SAP – C241BA Power Source 220V Single phase 60Hz Voltage rating 220 V Performance Cooling Capacity kW BTU/h Air circulation (High) Moisture removal (High) m3/h Liters/h 6.40 21,800 830 3.3 V A W % W/W A 198 ~ 242 14.5 2,890 91 2.2 89 Electrical Rating Cooling Available…
-
2-2. Major Component Specifications
2-2-1. Indoor Unit Indoor Unit SAP – K161GJA Controller PCB Part No. Controls Control circuit fuse POW-K181GJA Microprocessor 250 V 3.15 A Remote Control Unit RCS-2S2E Fan & Fan Motor Type Q'ty Dia. and length Fan motor model Q'ty No. of poles 50/60Hz rpm (High ) Nominal output Coil resistance…
-
SAP – K181GJA
SAP – K181MBA Controller PCB Part No. Controls Control circuit fuse POW-K181GJA Microprocessor 250 V 3.15 A Remote Control Unit RCS-2S2E Fan & Fan Motor Type Q'ty Dia. and length Fan motor model Q'ty No. of poles 50/60Hz rpm (High) Nominal output Coil resistance (Ambient temp. 20°C) Safety devices…
-
SAP – K241GJA
SAP – K241MBA Controller PCB Part No. Controls Control circuit fuse POW-K241GJA Microprocessor 250 V 3.15 A Remote Control Unit RCS-2S2E Fan & Fan Motor Type Q'ty Dia. and length Fan motor model Q'ty No. of poles 50/60Hz rpm (High) Nominal output Coil resistance (Ambient temp. 20°C) Safety devices…
-
2-2-2. Outdoor Unit
Outdoor Unit SAP – C161GA Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices W cc Ω Type Overload relay Operating temp. Open °C Close °C Operating amp.(Ambient temp. 25°C) Run capacitor µF VAC Crank case heater Rotary (Hermetic)…
-
SAP – C161JA
Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices W cc Ω Type Overload relay Operating temp. Open °C Close °C Operating amp.(Ambient temp. 25°C) Run capacitor µF VAC Crank case heater Rotary (Hermetic) C-R132H6D 80612346-S 1,400…
-
SAP – C181MA
Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices W cc Ω Type Overload relay Operating temp. Open °C Close °C Operating amp.(Ambient temp. 25°C) Run capacitor µF VAC Crank case heater Rotary (Hermetic) C-2R170H5T 80827445 1,700…
-
SAP – C181JA
SAP – C181BA Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices W cc Ω Type Overload relay Operating temp. Open °C Close °C Operating amp.(Ambient temp. 25°C) Run capacitor µF VAC Crank case heater Rotary (Hermetic) C-R132H6D…
-
SAP – C241MA
Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices W cc Ω Type Overload relay Operating temp. Open °C Close °C Operating amp.(Ambient temp. 25°C) Run capacitor µF VAC Crank case heater Rotary (Hermetic) C-R221H5S 80687145 2,200…
-
SAP – C241JA
SAP – C241BA Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices W cc Ω Type Overload relay Operating temp. Open °C Close °C Operating amp.(Ambient temp. 25°C) Run capacitor µF VAC Crank case heater Rotary (Hermetic) C-R191H6M…
-
2-3. Other Component Specifications
-
3. DIMENSIONAL DATA
Indoor Unit SAP – K161GJA SAP – K181GJA SAP – K241GJA SAP – K181MBA SAP – K241MBA (3) Remote control unit 147.5 61 23 147.5 Center of tubing hole (2 places) Drain hose ø18 Narrow tube ø6.35 (1/4") Wide tube ø12.7 (1/2") Wide tube ø15.88 (5/8") K161, K181 K241 Unit : mm 18
-
SAP – C161GA
-
SAP – C241JA
538 SAP – C241MA SAP – C241BA Air intake Air discharge Wide tube service valve ø15.88 (5/8") Narrow tube service valve ø6.35 (1/4") Outdoor Unit Unit : mm 20
-
4. REFRIGERANT FLOW DIAGRAM
Indoor Unit SAP – K161GJA SAP – K161GJA SAP – K181GJA SAP – K181MBA Outdoor Unit SAP – C161GA SAP – C161JA SAP – C181JA SAP – C181BA , Indoor Unit Outdoor Unit Wide tube Wide tube service valve Accumulator Compressor Condenser Evaporator O.D. ø12.7 mm (1/2 ") Narrow tube Narrow tube service valve…
-
SAP – K241GJA
SAP – K241GJA SAP – K241MBA SAP – K241MBA Outdoor Unit Indoor Unit SAP – C241GA SAP – C241JA SAP – C241MA SAP – C241BA Outdoor Unit Wide tube Wide tube service valve Muffler O.D. ø15.88 mm (5/8 ") Accumulator Compressor Evaporator Condenser Capillary for liquid injection Narrow tube Strainer Narrow…
-
5. PERFORMANCE DATA
5-1. Performance charts Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit SAP – K161GJA SAP – C161GA ■ Cooling Characteristics ■ Cooling Characteristics Indoor inlet air D.B. temp. (°C) 13 Outdoor fan speed 12 Low High Outdoor fan speed 12 Low 1.18 (11) MPa (kgf/cm2G) 1.47 (14) Indoor inlet air D.B.…
-
SAP – K181GJA
SAP – C181GA SAP – K181MBA SAP – C181MA Indoor Unit Outdoor Unit Indoor inlet air D.B. temp. (°C) 13 Outdoor fan speed 14 Low 12 Low High 13 Operating current (A) Operating current (A) Outdoor fan speed 1.18 (11) MPa (kgf/cm2G) Outdoor fan speed Low High Low pressure at wide tube service valve MPa…
-
SAP – K241GJA
SAP – C241GA SAP – K241MBA SAP – C241MA Indoor Unit Outdoor Unit ■ Cooling Characteristics Outdoor fan speed 17 Low High Outdoor fan speed 19 Low 1.18 (11) MPa (kgf/cm2G) 1.47 (14) Indoor inlet air D.B. temp. (°C) Outdoor fan speed 1.28 (12) Low High 1.08 (10) 0.98 ( 9 ) 0.89 ( 8 ) 0.79 ( 7 ) 0.69 (…
-
5-2. Air Throw Distance Chart
Indoor Unit SAP – K161GJA SAP – K181GJA SAP – K181MBA Room air temp. : Fan speed : 27°C High Horizontal distance (m) Axis air velocity (m/s) Vertical distance (m) : Flap angle 0° , : Flap angle 30°, : Axis air velocity 0° : Axis air velocity 30° Heating SAP – K241GJA SAP – K241MBA Room air temp.…
-
5-3. Cooling Capacity
Indoor Unit Outdoor Unit SAP – K161GJA SAP – C161GA 240V Single Phase 50Hz RATING CAPACITY 4.70 kW AIR FLOW RATE 760 m3/h EVAPORATOR CONDENSER ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C W.B. D.B. TC 4.32 4.12 3.87 3.56 CM 1.25 1.34 1.45 1.60 21 SHC 2.92 2.81 2.68 2.53 15 23 SHC 3.27 3.16 3.04 2.89 25…
-
SAP – K161GJA
SAP – C161JA 220V Single Phase 60Hz RATING CAPACITY 4.70 kW AIR FLOW RATE 760 m3/h EVAPORATOR CONDENSER ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C W.B. D.B. TC 4.32 4.12 3.87 3.56 CM 1.38 1.48 1.60 1.75 21 SHC 2.91 2.81 2.68 2.53 15 23 SHC 3.27 3.16 3.03 2.88 25 SHC 3.62 3.52 3.39 3.24 27 SHC 3.98 3.87…
-
SAP – K181GJA
SAP – C181GA SAP – K181MBA SAP – C181MA 240V Single Phase 50Hz RATING CAPACITY AIR FLOW RATE EVAPORATOR ENT. TEMP. °C W.B. D.B. TC CM 21 SHC 15 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 17 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 19 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 23 SHC 21 25…
-
SAP – K181GJA
SAP – C181JA SAP – K181MBA SAP – C181BA 220V Single Phase 60Hz RATING CAPACITY AIR FLOW RATE EVAPORATOR ENT. TEMP. °C W.B. D.B. TC CM 21 SHC 15 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 17 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 19 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 23 SHC 21 25…
-
SAP – K241GJA
SAP – C241GA SAP – K241MBA SAP – C241MA 240V Single Phase 50Hz RATING CAPACITY AIR FLOW RATE EVAPORATOR ENT. TEMP. °C W.B. D.B. TC CM 21 SHC 15 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 17 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 19 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 23 SHC 21 25…
-
SAP – K241GJA
SAP – C241JA SAP – K241MBA SAP – C241BA 220V Single Phase 60Hz RATING CAPACITY AIR FLOW RATE EVAPORATOR ENT. TEMP. °C W.B. D.B. TC CM 21 SHC 15 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 17 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 19 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 23 SHC 21 25…
-
6. ELECTRICAL DATA
6-1. Electrical Characteristics Indoor Unit Outdoor Unit SAP – K161GJA SAP – C161GA Indoor Unit Outdoor Unit Fan Motor Fan Motor Performance at Rating Conditions Running Amps. Power Input Full Load Conditions Running Amps. Power Input A 0.37 / 0.38 kW 0.070 / 0.073 A 0.37 Complete Unit Compressor…
-
SAP – K181GJA
SAP – C181GA SAP – K181MBA SAP – C181MA Indoor Unit Outdoor Unit Fan Motor Fan Motor Performance at Rating Conditions Running Amps. 9.6 / 0.105 / 0.119 1.855 / 1.918 2.03 / 2.11 / 0.38 0.48 / 0.50 13.05 / 12.52 13.9 / 13.4 kW 0.070 / 0.073 0.105 / 0.119 2.785 / 2.838 2.96 / 3.03 0.37 / 0.38 kW 0.070…
-
SAP – K241GJA
SAP – C241GA SAP – K241MBA SAP – C241MA Indoor Unit Outdoor Unit Fan Motor Fan Motor Performance at Rating Conditions Running Amps. 12.8 / 12.8 0.106 / 0.118 2.469 / 2.562 2.65 / 2.76 / 0.40 0.49 / 0.50 16.62 / 15.90 17.5 / 16.8 kW 0.075 / 0.080 0.106 / 0.118 3.509 / 3.542 3.69 / 3.74 0.39 / 0.40 kW…
-
6-2. Electric Wiring Diagrams
Indoor Unit SAP – K161GJA SAP – K181GJA SAP – K241GJA WARNING 36 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
-
SAP – K181MBA
SAP – K241MBA WARNING 37 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
-
SAP – C161GA
SAP – C161JA SAP – C181JA SAP – C181BA WARNING 38 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
-
SAP – C181MA
WARNING 39 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
-
SAP – C241JA
SAP – C241MA SAP – C241BA WARNING 40 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
-
7. INSTALLATION INSTRUCTIONS 7-1. Installation Site Selection Indoor Unit WARNING To prevent abnormal heat generation and the possibility of fire, don’t place obstacles, enclosures and grills in front of or surrounding the air conditioner in a way that may block air flow. AVOID: ● direct sunlight.…
-
AVOID
● heat sources, exhaust fans, etc. (Fig. 3) NO ● damp, humid or uneven locations. Exhaust fan Hot air Heat source DO: ● choose a place as cool as possible. Outdoor unit ● choose a place that is well ventilated. ● allow enough room around the unit for air intake/exhaust and possible maintenance.…
-
7-2. Remote Control Unit Installation
Position The remote control unit can be operated from either a non-fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places: ● In direct sunlight ● Behind a curtain or other place where it is…
-
7-3. Recommended Wire Length and Size
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation. NOTE Refer to the WIRING SYSTEM DIAGRAM for the meaning of "A" and "B" in Table 2.…
-
8. FUNCTION
8-1. Room Temperature Control ● Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit. ● The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the…
-
8-2. Dry Operation (Dehumidification)
● Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room…
-
8-4. Outdoor Fan Speed Control
● To optimize performance of the air conditioner, the outdoor fan speed is switched automatically according to the outdoor temperature. ● If the outdoor air temperature falls below 28.5°C, the fan speed switches to LOW. ● If the outdoor air temperature rises above 31.5°C, the fan speed switches to…
-
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting WARNING Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing. 9-1-1. Check power supply wiring. ● Check that power supply wires are correctly connected to terminals No.1…
-
9-2. Air conditioner does not operate
9-2-1. Circuit breaker trips (or fuse blows). A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.) ● There is a possibility of ground fault. ● Check insulation resistance. If resistance value is 2MΩ or less, insulation is defective (“NO”). Outdoor unit 1 Circuit…
-
9-2-2. Neither indoor nor outdoor unit runs
A. Power is not supplied. • Check power supply. Circuit breaker is tripped. Reset breaker. Power failure Wait for recovery or contact power company. NO Power is being supplied to the outdoor unit. B. Check remote control unit. • Try to run with another remote control unit. OK First remote control…
-
E. Check fuse on the indoor PCB Ass'y
• Check fuse on indoor PCB Ass'y for continuity. (F) If fuse has been blown, • Measure resistance of indoor fan motor winding. (FM) OK OK • Measure resistance of flap motor winding. (FLP) • Check operation lamp to see if light is ON. Light is OFF OK • Measure resistance of primary and secondary…
-
9-2-3. Only outdoor unit does not run
A. Check setting temperature. Is room temperature too low ? NO Try to lower setting temperature by temperature setting button ( button). Outdoor unit still does not run. • Try to run using another remote control unit. OK Remote control unit is defective. B. Check power relay in outdoor unit. •…
-
9-3. Some part of air conditioner does not operate
9-3-1. Only indoor fan does not run. • Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned. • Measure resistance of indoor fan motor winding. • Check fan casing foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearings.…
-
9-3-3. Only compressor does not run
• Either internal protector or overload relay is working. • Check compressor moter capacitor. YES • Measure resistance of compressor motor winding. • Temperature of compressor is abnormally high. YES YES Refrigerant gas shortage. Charge refrigerant gas (R22). NO • Measure Power supply voltage. The…
-
9-4. Air conditioner operates, but abnormalities are observed
9-4-1. Poor cooling. • Check position of remote control unit. • Cool air from air conditioner reaches position directly. YES Change position of remote control unit. • Wide and narrow tubes between indoor unit and outdoor unit are insulated. NO Insulate both wide and narrow tubes separately and then…
-
9-5-1. Indoor coil temp. thermistor (TH1) is defective. A. Open When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low indoor coil temperature. In Cooling mode: Function of freeze prevention continues to work. That is, the…
-
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance Ground wire Clip ● The insulation is in good condition if the resistance exceeds 2MΩ. Probe 10-1-1. Power Supply Wires Insulation tester Clamp the ground wire of the power supply wires with the lead clip of the insulation resistance tester and measure the…
-
10-2. Checking Continuity of Fuse
on PCB Ass'y Fuse ● Remove the PCB Ass’y from the electrical component box. Then pull out the fuse from the PCB Ass’y. (Fig. 5) ● Check for continuity using a multimeter as shown in PCB Ass’y Fig. 6. Fig. 5 10-3. Checking Motor Capacitor Remove the lead wires from the capacitor terminals, and then…
-
11. MAINTENANCE
11-1. Changing Address of Remote Control Unit in Indoor Unit If you are installing more than 1 indoor unit (up to 2) in the same room, it is necessary for you to assign each unit its own address, so each can be operated by its own separate remote control unit. You assign the addresses by matching…
-
APPENDIX INSTRUCTION MANUAL
-
Page 2
Features This air conditioner is equipped with cooling and drying functions. Details on these functions are provided below; refer to these descriptions when using the air conditioner. • Compact Size This model is smaller than its predecessors and yet offers the same capabilities. • Microprocessor…
-
Page 4
Installation Location • We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit. Before installation, check that the voltage of the electric supply in your home or office is the same as…
-
Page 5
Names of Parts Air intakes INDOOR UNIT Air outlet Remote control unit Drain hose Refrigerant tubes OUTDOOR UNIT Air outlet NOTE This illustration is based on the external appearance of a standard model. Consequently, the shape may differ from that of the air conditioner you have selected. This air…
-
Page 6
Unit Display and Operation Selector INDOOR UNIT IMPORTANT OPERATION lamp Avoid using radio equipment such as mobile phone near (within 1 m) the indoor unit. Some radio equipment may cause malfunction of the unit. If the trouble happens, disconnect power and restart the air conditioner after a few…
-
Page 7
Remote Control Unit (Display) Displayed when setting temperature Displayed when transmitting data Displayed when temperature is shown Displayed when the temperature setting is at the upper or lower allowable limit Displayed when setting timer Symbols (1) Operation mode (4) Timer COOL 12-hour ON…
-
Page 8
Remote Control Unit Transmitter Display ON/OFF operation button (Cover closed) 1 HR. TIMER button TEMP. setting buttons NIGHT SETBACK button MODE selector button FAN SPEED selector button FLAP button TIMER SET button (which advances the time displayed) TIMER ON button ADDRESS switch TIMER OFF button…
-
Page 9
Remote Control Unit (continued) TIMER ON button : The air conditioner starts at the set time. TIMER OFF button : The air conditioner stops at the set time. TIMER SET button MODE selector button (DRY) (COOL) FLAP button NOTE OI-379-09EG This button is used to set the time at which you wish the air…
-
Page 10
Using the Remote Control Unit How to Install Batteries 1. Slide the cover in the direction indicated by the arrow and remove it. 2. Install two AAA alkaline batteries. Make sure the batteries point in the direction marked in the battery compartment. 3. Use a thin object such as the tip of a pen to…
-
Page 11
Using the Remote Control Unit (continued) Mounting the Remote Control Unit Truss-head tapping screws 4 × 16mm (supplied) Remote control unit holder When attaching to wall 1) Comfirm the indoor unit beeps when the ON/OFF button is pressed at the wall location where the remote control unit is to be…
-
Page 12
Operation with the Remote Control Unit 1. Operation STEP 2 STEP 3 STEP 1 STEP 5 NOTE STEP 4 Check that the circuit breaker on the power panel is turned on and that the operation selector of the indoor unit is in the ON position. Press the setting buttons as described below and change the settings as…
-
Page 13
Operation with the Remote Control Unit (continued) NOTE • This appliance has a built-in 3-minute time delay circuit to ensure reliable operation. When the operation button is pressed, the compressor will start running within three minutes. In the event of power failure, the unit will stop. When the…
-
Page 14
Operation with the Remote Control Unit (continued) 3. Night Setback Mode Night Setback Mode is used for saving energy. Press the NIGHT SETBACK button while operation. The mark appears on the display. To release the night setback function, press the NIGHT SETBACK button again. In Cooling and DRY…
-
Page 15
Special Remarks “DRY” ( ) Operation How it works? • • • Once the room temperature reaches the level that was set, the unit repeats the cycle of turning on and off automatically. During DRY operation, the fan speed is automatically set to LOW or VERY LOW; the fan speed then switches back and forth…
-
Page 16
Using the 12-Hour ON and OFF Timer 2. TIMER ON mode (Example) After the length of time set for TIMER ON elapses, the unit begins operating. The display depicted at left indicates that the air conditioner will begin operating in three hours. Setting procedure: • • STEP 1 Press the MODE button and set…
-
Page 17
Using the 12-Hour ON and OFF Timer (continued) 3. ON/OFF Parogram Timer A combination of the TIMER ON and TIMER OFF modes, this function allows you to specify the time that the unit turns on and the time when it turns off. (Example) The unit will turn on three hours from now, and turn off five hours…
-
Page 18
Using the 1-Hour OFF Timer 1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed. The indicator in the display indicates that this function is operating. Setting procedure: Regardless of…
-
Page 19
Adjusting the Airflow Direction 1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right. When the humidity is high, the vertical vanes should be in the front position during the cooling or dehumidifying operation. If the vertical vanes…
-
Page 20
Operation without the Remote Control Unit INDOOR UNIT If you have lost the remote control unit or it has trouble, follow the steps below. Operation selector 1. When the air conditioner is not running If you want to turn on the air conditioner, switch the operation selector to the OFF position, and…
-
Page 21
Care and Cleaning (continued) Anti-Mold Filter How to remove the anti-mold filter The anti-mold filter behind the air intake grille should be checked and cleaned at least once every two weeks. 1. Grasp both ends of the air intake grille and pull it out and up. 2. Push the anti-mold filter up…
-
Page 22
Care and Cleaning (continued) Air Cleaning Filter (hot provided) NOTE The air cleaning filter removes dust and dirt from the air, and reduces odors and smoke from tobacco. The air clean filter is not provided with the air conditioner and must be purchased separately. Ask for the STK-F4B model when…
-