Instruction for
fitter and user This description corresponds to the current state program. Changes could take place at any time without previous announcement. Assembly and operating instructions 115202080 1
-
Security indications
The following standards and directives must be respected at all works: - Protection measures after VDE0100 and VDE0105 Accident prevention rule BGV A2 in full extent DIN EN 50110-1 and DIN EN 50110-2 (Company of electrical arrangements) DIN EN 50274 (Protection against electrocution) Regarding the…
-
1 The controller for air-conditioning
Heating/cooling 1 The controller for air-conditioning The heating floor is a technique more and more used in, flats, houses, shops, schools, industrial installations, museums… This heating system is also more and more use in summer for cooling and giving a comfortable temperature when the sun…
-
Diagram of system compose of 2 circuits
Flow temperature control weathercompensated Imdividual temperature romm control with humidity control Room thermostat Control distributor Heating-circuit distributor Heating-circuit distributor The water transfer to the several distributors is managing by valves in the 2 circuits. Controller task…
-
Explanation: how the active dew point prevention work?
The active dew point prevention has great advantages compared to a simple dew point monitor. When we are to close to the dew point, this protection switches off the cooling circuit. Because of that the temperatures increase in the room. As soon as we are below a predefine point we switch on again…
-
How is the heating/cooling working?
PI Xi1 y1 PI Xi2 y2 Regler Modell: 0 y x Xi1 Vorlauftemperatur Heizen xi - dXi1 bXi1 bXi1 cXi1 TF1 (Jumper) x Xi2 Vorlauftemperatur Kühlen xi dXi2 bXi2 bXi2 cXi2 TF2 (Jumper) Xi3 xi Aussentemperatur Xi4 Raumfeuchte xi dXi4 bXi4 bXi4 cXi4 TF4 (Jumper) cXi5 TF5 x Raumtemperatur t XiM3 X / 100% y yc LY…
-
2 The controller for air-conditioning
conects to the control distributor Heating/cooling with a 2 pipes system 2.1 Components connected to the controller - Outdoor sensor EGT301F101 (Measures the outside temperature/ installed in the North side) - Clamp-on detector EGT311F101 stem temperature detector with Immersion tube EGT346F101…
-
Actuator for 3 way valves AXM117S (Temperature regulation for heating/cooling) - Actuator for 2 way valves (Heating/cooling) - Circulation Pump (optional) Area control device RDB300 (optional ) (Control the operating mode in distance, presence/absence, and the adjustment of the time. In case of…
-
2.2 Devices connected to the distributor
- Room temperature controller NRT210F011(control the temperature of each room individually, temperature sensor in each room) - Actuator (to control the temperature of each area individually, commonly use for all under floor heating system, control all type of circuit) - Dew point controller…
-
Y1- heating/cooling
Bridge made of 2 tubes Heating detector Outdoor Sensor Extern Interuptor Room humididyMeasuring transmitter Valves controller Heating/ cooling Valves change-over Heating/ cooling Temperature controler Pump Heating/cooli ng 11 Premium Armaturen + Systeme Area control device (option) 3 Writing…
-
Important informations for the fitter
- The second part of the transformer 24VAC must be connected to the earth. The point 17 must also be connected to the earth! - The creation of a bridge between the 19 and 20 is an obligation! . Assembly and operating instructions 115202080 12
-
Actuators 230 V/AC
Actuators 230 V/AC 13 Premium Armaturen + Systeme The 230V Alimentation. can come from everywhere 3.2 Connections of the distributor Assembly and operating instructions 115202080 For example a room without heating system
-
Informations Important for the fitter
- The 230V alimentation can also be supply in the concern floor E-distributor! A distributor can have 5 channels. Every channel can manage 2 actuators. In case of you would like to manage more as 2 actuators, you just need to link the different channels with a bridge from the L point of the first…
-
3.3 The wiring
-
4 Important introduction indications!
4.1 Room temperature transducer EGH 130 Bridge H1 and H2 must be cut H2 H1 B08108a Controller for air-conditioning You need to check Jumper located at the back of the controller. X4 X3 X2 X1 Please check if the bridge of the controller between 19 and 20 is correct! Assembly and operating…
-
Signal for the
setting LCD screen Prescribed value Real value Compensation value Setting keyboards next / previous page Touch for the memorisation. Mode selector : Manuel, automatic, programation. Mode selector :. Manuel Automatic Programation Assembly and operating instructions 115202080 17
-
In Automatic mode
Turn on the alimentation With the touch +/- we can show prescribed value 1. Indication Xs1 20,0 °C heating 2. Indication Xs2 16,0 °C we slow down the heating Info : The setpoint 1 named XS1 (Heating base temperature) is 20°C, that mean that when we have a outside temperature of 20°C a…
-
Setting model number for checking
1. Sliding switch in ‘Programation´ (key symbol) 2. Type 3. Model 0 must be selected! 4. When that is ok, Sliding switch in “Automatic” 5. When that not ok: 6. Press “ CI “ and the model will be deleted 7. Then Press „ 0 „ button 8. Slide switch in „Automatic“ Checking the detector function: 1.…
-
Change-over-Setpoint (Temperature setpoint for Heating and cooling ) Check
1. Sliding switch in „Automatic“(Same approach as point 4.4) 2. Press „ Xi „ button, 3. Explore the different page with „ + „ and „ - „to nXi3 4. nXi3 -> Read and note outside average temperature! Now the appropriate setpoint value „ co „ (AT- Switching value Heating/cooling) change: 5. In addition…
-
Now we can check the relay
If the value CO < nXi3 (cooling) 1. Slide the switch to „Automatic“ 2. Check the output of the relay, follow the point. 4.5 Display: rel 1 (Correspond to the cooling) rel 5 (Transfer valve H/C is headed for, i.e. active) or When the value co > nXi3, the fallowing announcement take place: Display…
-
5 FAQ‚s
5.1 How can I set the time, the date and So change-over ? SET 8 2. Step Schritt 1. Schritt 1. Step Input to set time Eingabe vonthe Uhrzeit Cl Wochentag, Uhrzeit, aktiver Day, time, active1 und Sollwert von Regler setpoint for the conBetriebsart Input Eingabe : 00:00...23:59 troller 1and operating…
-
11. Step -> Sliding the switch in automatic!
If the safety battery gets empty, the time will be lost. This status is signal by the inscription “Wednesday 12” flashing on the screen. Time-dependent switching operation will only be executed after the time has been corrected 1) The automatic change over between summer and winter time occurs on…
-
5.2 How can I change the time program?
PRO Storage 32 Speicherplätze adress 1.1.Schritt step Sollwertumschaltung für: Setpoint for: --Controler Regler 1 (PI 1)1) 1 (PI --Controler Regler 2 (PI 2)2) 2 (PI Xs1 Xs3 0 06:00 0 06:00 Setpoint for: --Controler Regler 1 (PI 1)1) 1 (PI --Controler Regler 2 (PI 2)2) 2 (PI Xs2 Xs4 0 22:00 0 22:00…
-
Example: you want to program this hour program
Program every day (Monday to sunday) from 06:00 to 23:00 hour (Heating and cooling) 1. Sliding switch in „ manual „ 2. Press „ PRO „ button 3. Press „ CI „ as long as a number display in the screen. When all the number is deleted follow the list: 4. Press „ I „ button 5. Press „ 0 „ to program the…
-
5.3 How can I change the setpoint Heating
or Cooling? Xs Sollwertänderung per Tastendruck Sollwert fürfor: Setpoint Regler 1 (PI 1) 1) Controller 1 (Pl Sollwert setpoint 11 Sollwert setpoint 22 I Xs1 Xs2 I Regler 2 (PI 2) 2) Controller 2 (Pl Sollwert setpoint 11 Sollwert setpoint 22 Xs3 Xs4 16,0°C 19,0°C Regler 5 (PI 5) 2) Controller 5 (Pl…
-
Heating setpoint
The setpoint 1 named XS1 (Heating base temperature) is 20°C, that mean that when we have a outside temperature of 20°C a flow-temperature of 20°C is set. If the outside temperature changes, the setpoint 1 changes accordingly. The setpoint 2 named XS2 set to 16 °C mean that we lower the heating…
-
5.4 How can I now the sensor value?
Xi - Istwert 1 Xi1 - Istwert 2 Xi2 - Istwert 3 Xi3 - Istwert 4 Xi4 - Istwert 5 1) Xi5 - Istwert 6 1) Xi6 - gemittelte Aussentemperatur nXi3 B09354 1. Slide switch to „ Automatic „ 2. Press„ Xi“ button 3. With „ + „ change the page to read the value Xi1 = VL-Heating temperature Xi2= Same with Xi1…
-
5.5 Did the external heating / cooling change
over is necessary ? If do you use an external changer over Heating/cooling (terminal 14/17 of the controller) above a free potential contact; you need to turn off the automatic change over. Execute the following instruction: 1. Sliding switch in „Programation“ Input Model 0 must be chosen! 2. Press…
-
5.6 How can I change the slope of the
heating caracteristic ? The heating characteristic is drawn page 27. The standard heating floor slope is located between 0,5 and 0,6 To change the slope of the heating characteristic, follow this instruction: : 1. Sliding switch on „manuel“ 2. Press „PAR“ button 3. With „ + „ navigate until the SL…
-
5.7 How to activate a room controler unit ?
Follow these instructions: 1. Sliding switch on „Programation“ Input 6789 2. With „ + „ navigate until the RC inscription appears on the screen. 3. Press „ I“ button 4. Stay press on „ + „ until ON appears 5. Press „ I“ button 6. Sliding switch on „ Automatic“. The remote control RDB300 is now…