Air-Conditioner
PUHZ-FRP71VHA INSTALLATION MANUAL FOR INSTALLER For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the outdoor unit. English is original. The other languages versions are translation of the original. INSTALLATIONSHANDBUCH FÜR INSTALLATEURE…
-
1. Safety precautions
1.2. Before installation (relocation) Caution: • Be extremely careful when transporting or installing the units. Two or more persons are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the packaging bands. Wear protective gloves to remove the unit from the packaging and to move…
-
2. Installation location
2.2. Choosing the outdoor unit installation location 0 33 + • Avoid locations exposed to direct sunlight or other sources of heat. • Select a location from which noise emitted by the unit will not inconvenience neighbors. • Select a location permitting easy wiring and pipe access to the power source…
-
3. Installing the outdoor unit
(mm) A • Be sure to install the unit in a sturdy, level surface to prevent rattling noises during operation. (Fig. 3-1) <Foundation specifications> Foundation bolt Thickness of concrete Length of bolt Weight-bearing capacity E C B Max. 30 A M10 (3/8") bolt B Base C As long as possible D Vent E Set…
-
4.2. Connecting pipes (Fig. 4-1)
B • When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 °C or more, thickness of 12 mm or more). • The indoor parts of the drain pipe should be wrapped with polyethylene foam insulation materials…
-
Stop valve
4.4. Refrigerant pipe airtight testing method (Fig. 4-4) A B C D E A Service port B Open/Close section C Local pipe D Sealed, same way for gas side E Pipe cover Fig. 4-4 4.5. Stop valve opening method (Fig. 4-5) Fig. 4-5 H Double spanner section (Do not apply a spanner other than to this section.…
-
4.7. Precautions when reusing existing R22 refrigerant pipes
• Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer. • If the diameter of the existing pipes is different from the specified diameter, refer to technological data materials to confirm if the pipes can be used. Measure the…
-
6. Electrical work
6.1. Outdoor unit (Fig. 6-1, Fig. 6-2) 1 Remove the service panel. 2 Wire the cables referring to the Fig. 6-1 and the Fig. 6-2. S1 S2 S3 F G J F G J S1 S2 S3 L N S1 S2 S3 S1 S2 S3 For Power For Power Fig. 6-1 I Fig. 6-2 F Terminal block for power (L, N, ) and Indoor-Outdoor connection (S1, S2, S3)…
-
7. Test run on air conditioner side
7.1. Before test run ► After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply. ► Use a 500-volt megohmmeter to check that…
-
8. Special functions
8.3. Refrigerant collecting (pump down) (Fig. 8-3) The refrigerant collecting function is available by performing the following procedure. 1 Close the 2 liquid stop valves and the cylinder/hydro unit side gas valve. Only the indoor unit side gas valve remains open. 2 Connect the 2 gas stop valve…
-
EG-KONFORMITÄTSERKLÄRUNG DÉCLARATION DE CONFORMITÉ CE EG-CONFORMITEITSVERKLARING DECLARACIÓN DE CONFORMIDAD CE DICHIARAZIONE DI CONFORMITÀ CE ΔΗΛΩΣΗ ΠΙΣΤΟΤΗΤΑΣ ΕΚ DECLARAÇÃO DE CONFORMIDADE CE EU-OVERENSSTEMMELSESERKLÆRING EG-DEKLARATION OM ÖVERENSSTÄMMELSE EC UYGUNLUK BEYANI CE-ERKLÆRING OM SAMSVAR…
-
<ENGLISH>
<PORTUGUÊS> English is original. The other languages versions are translation of the original. O idioma original é o inglês. As versões em outros idiomas são traduções do idioma original. CAUTION CUIDADO • Refrigerant leakage may cause suffocation. Provide ventilation in accordance with EN378-1. •…
-
x. 5 1000 Ma Fig. 2-6 Fig. 2-7 Fig. 2-8 00 5 x. Ma Fig. 2-9 1000 Fig. 2-10 Fig. 2-11 1000 00 x. 3 Ma Fig. 2-12 Fig. 2-13 Fig. 2-14 Fig. 2-15 0 50 Fig. 2-16 Fig. 2-17 Fig. 2-18
-
This product is designed and intended for use in the residential,
commercial and light-industrial environment. Importer: Mitsubishi Electric Europe B.V. Capronilaan 46, 1119 NS, Schiphol Rijk, The Netherlands French Branch 25, Boulevard des Bouvets, 92741 Nanterre Cedex, France German Branch Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany Belgian Branch…