Инструкция на Модульные чиллеры Midea серии MCCH...
Модульные чиллеры Midea с воздушным охлаждением конденсатора серии MCC(D)H30A-TA3SL, MCC(D)H65A-SA3L, MCCH130A-SA3L, MCCH185A-SA3, MCCH250A-SA3T. Руководство по сервису.
Смотрите также: Коды ошибок: 7 кодов →
Загружаем документ…
Текст инструкции
-
DM13-01.01.14en
-
1 General information
-
1.3 External appearance
-
2. Features
1). Low ambient temperature cooling function (Available for MCC(D)H30A-TA3SL, MCC(D)H65A-SA3L, MCCH130A-SA3L) The ambient temperature is down to -10℃ in cooling mode, and heating down to -10˚C ambient by added one board (see picture1). Wide ambient temperature range are available by adjustable…
-
MCAC-ATSM-2012-10
4).Humanized remote control (For the module with KJR-120A/MBE) S7 address on PCB should be switched to ON to realize remote control, which including remote ON/OFF, remote heating and cooling mode selection, remote alarm. The customer can simply and conveniently control the chiller and acquire the…
-
Water outlet temp
Total water outlet temp. (Just for master unit) Three-core shielding twisted pair Water outlet temp. Water outlet temp. Total water outlet temp. (Just for master unit) Total water outlet temp. (Just for master unit) Three-core shielding twisted pair Wired controller 8).Environmental care Ecological…
-
MCAC-ATSM-2012-10
12).Strong micro-computer intelligent control and monitor function Optimizing the design of system and using varieties of protection devices, to make the system more safe and reliable. 13). Superior reliability System will be more reliable with new type efficient heat exchanger. Evaporator 30kW…
-
3. Specification
Model MCCH30A-TA3SL MCDH30A-TA3SL kW 30 30 Btu/h 102,300 102,300 Heating Capacity kW 32 32 Power supply V/Ph/Hz Cooling Capacity Power supply Manual switch A Fuse A 50 36 Type Quantity Pieces Model Compressor Power input 380-415/3/50 Fixed speed Digital Scroll + Fixed speed 1+1 1+1 ZP67KCE-TFD-522…
-
1) Protection for over-high discharge pressure
2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-freezing protection in cooling mode. 5) Anti-freezing protection in Winter. 6) Protection for compressor over current. 7) Protection for compressor overload. 8) Outlet and inlet water temperature…
-
Model
MCCH65A-SA3L MCDH65A-SA3L Cooling Capacity kW 65 65 Heating Capacity kW 69 69 Cooling kW 20.4 20.4 Cooling rated current A 36.5 36.5 Heating kW 21.5 21.5 Heating rated current A 37.2 37.2 380-400/3/50 380-415/3/50 Power input Power supply V/Ph/Hz Manual switch A 150 150 Fuse A 100 100 Max. Input…
-
1) Protection for over-high discharge pressure
2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-freezing protection in cooling mode. 5) Anti-freezing protection in Winter. 6) Protection for compressor over current. 7) Protection for compressor overload. Safety protection device 8) Outlet and inlet…
-
Model kW 130 Btu/h 443,560 Heating Capacity kW 138 Power supply V/Ph/Hz Cooling Capacity Power supply Manual switch A 250 Fuse A 200 Type Quantity Compressor 380-400/3/50 Fixed speed Scroll Pieces 4 Model SH140A4ALC Brand Danfoss Capacity kW 34.7×4 Input kW 10860×4 Rate current(RLA) A 21.4×4 Locked…
-
Weight
Net weight kg Operation weight kg 1150 1270 Power wire 2 mm ×No. 35×3+16×2 Signal wire mm2×No. 0.75x3-core Control type Wired controller 1) Protection for over-high discharge pressure. 2) Protection for over-low suction pressure. 3) Power supply phase sequence protection. 4) Anti-freezing protection…
-
Model
MCCH185A-SA3 MCCH250A-SA3T kW 185 250 Btu/h 631,220 Heating Capacity kW 200 830,000 270 Power supply V/Ph/Hz 380-400/3/50 380-400/3/50 400 450 Cooling Capacity Power supply Manual switch A Fuse A Type Quantity Pieces Model Brand 300 350 Scroll (fixed speed) Scroll (fixed speed) 6 8 SH140A4ALC…
-
Safety protection device
1) Protection for over-high 1) discharge pressure. discharge pressure. 2) Protection for over-low suction 2) Protection for over-low suction pressure. pressure. 3) Power supply phase 3) sequence protection. sequence protection. 4) Anti-freezing protection in 4) Anti-freezing protection in cooling…
-
4 Dimension
317 874 1865 30kW module Front view Left view Top view 17
-
NO. NAME Air inlet Air outlet Water inlet Make-up water inlet Water outlet Drain
-
65kW module
-
Name 1 Top cover 2 Air outlet 3 Air inlet 4 Water outlet 5 Compressor 6 Electric control box 7 Water inlet
-
130kW module
-
Name 1 Top cover 2 Condenser 3 Compressor 4 Evaporator 5 Electric control box Air inlet 6 Water outlet 7 Water inlet 8 Compressor
-
185 kW module
-
Name 1 Top cover 2 Compressor 3 Evaporator 4 Water outlet 5 Electric control box 6 Water inlet 7 Condenser
-
F
-
Air outlet
Air outlet Air outlet Air outlet 1 Air in Air inlet Air in le in Air let let t 7 Air in let No. 26 Name 1 Top cover 2 Compressor 3 Evaporator 4 Water outlet 5 Electric control box 6 Water inlet 7 Condenser 8 Transportation guard plate (Be removed off after installation) 3
-
5 Refrigeration system drawing
5.1 30kW module refrigeration system sketch drawing Each module has two compressors with one separate unit, one double-pipe evaporator for two refrigerant systems. Fan 4-way valve A Compressor A Condenser 4-way valve B Compressor B Water outlet EXV Water inlet Low pressure cylinder A Low pressure…
-
Each module has three compressors with one separate unit, one shell and tube evaporator for two refrigerant systems. Pressure switch low pressure cylinder B Compressor B 4-Way valve B Pressure switch Discharge switch Fan A Fan B Pressure switch Capillary T3A Pressure switch Com. A1 digital Water…
-
5.4 185 kW module refrigeration system sketch drawing
Each module has six compressors with three separate units, one shell and tube evaporator for six refrigerant systems. low pressure cylinder B Unit 2 4-Way valve B Compressor B 3" Fan A Fan B EXV Capillary Compressor A Dry type evaporator EXV Capillary Condenser Water flow direction 4-Way valve A…
-
6. Piping diagram
6.1 30kW module water pipeline sketch drawing The table below describes the symbols. Symbol 30 Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint Automatic discharge valve
-
30kW module water pipeline sketch drawing
The table below describes the symbols. Symbol Symbol explanation Symbol Symbol explanation Safety valve Y-shaped filter Pressure gauge Thermometer Water flow switch Water pump Cut off valve Expansion tank Manometer Water replenishing valve 31
-
6.2 65kW module water pipeline sketch drawing
Expansion tank Water replenishing Main unit Dirt discharge valve Differential pressure by-pass valve Drain valve Auxiliary electric heater Terminal Two-way valve Three-way valve The table below describes the symbols. Symbol 32 Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter…
-
130kW module water pipeline sketch drawing The table below describes the symbols. Symbol Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint Automatic discharge valve 33
-
6.4 185 kW module water pipeline sketch drawing
The table below describes the symbols. Symbol 34 Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint Automatic discharge valve
-
250kW module water pipeline sketch drawing The table below describes the symbols. Symbol Symbol explanation Symbol Symbol explanation Stop valve Y-shaped filter Pressure gauge Thermometer Water flow switch Circulating pump Gate valve Check valve Flexible joint Automatic discharge valve 35
-
K1(A)
-
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
Air-cooled modular chiller unit 130kW module 39
-
185 kW module
-
Attached Drawing (I) Electric Drawing of Main Unit and Auxiliary Unit
Air-cooled modular chiller unit 250 kW module 42
-
than 500m
H1 H2 P1 P2 Yellow Query Fault Gray Black 100Ω A B C N Notes The wiring diagram of auxiliary heater and pump is just for reference ,please follow the instructions of corresponding auxiliary heater products. Please choose such accessory as power wire , switch of auxiliary heater according to the…
-
t han 500m H1 H2 P1 P2 Yellow 44 Query Fault Gray Black 1 00Ω A B C N Notes The wiring diagram of auxiliary heater and pump is just for reference ,please follow the instructions of corresponding auxiliary heater products. Please choose such accessory as power wire , switch of auxiliary heater…
-
than 500m
H1 H2 P1 P2 Yellow Query Fault Gray Black 1 00Ω A B C N Notes The wiring diagram of auxiliary heater and pump is just for reference ,please follow the instructions of corresponding auxiliary heater products. Please choose such accessory as power wire , switch of auxiliary heater according to the…
-
130 kW module
-
200kW module
-
than 500m
H1 H2 P1 P2 Yellow Gray Black A B C N Notes The wiring diagram of auxiliary heater and pump is just for reference ,please follow the instructions of corresponding auxiliary heater products. Please choose such accessory as power wire , switch of auxiliary heater according to the actual parameter of…
-
8 Electric Characteristics
Model Outdoor Unit Hz Voltage Min. Power Supply Max. TOCA MFA Compressor LRA RLA OFM KW FLA MCCH30A-TA3SL 50 380-415 342 456 25.3 25 74(×2) 11.8(×2) 0.55 4.0 MCDH30A-TA3SL 50 380-415 342 456 25.3 25 74(×2) 11.8(×2) 0.55 4.0 MCCH65A-SA3L 50 380-400 147(×2) 21.4(×2) 0.865(×2) 4.0(×2) MCDH65A-SA3L 50…
-
9 Capacity Tables
9.1 MCC(D)H30A-TA3SL Cooling: Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW 5.00 33.59 8.81 31.63 9.08 29.84 9.36 28.20 9.65 26.42 10.13 24.31…
-
Hot water outlet
temp. Ambient temp.(℃) -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW 40.00 19.89 6.13 24.86 6.97 29.25 7.74 32.50 8.42 35.33 8.86 39.57 9.39 45.50 10.14 41.00 19.22 6.26 24.06 7.11…
-
MCC(D)H65A-SA3L Cooling Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW 5.00 72.77 17.97 68.52 18.52 64.64 19.10 61.10 19.69 57.25 20.67 52.67…
-
Ambient temp.(℃)
Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW 40.00 42.89 13.45 53.61 15.29 63.07 16.99 70.08 18.46 76.17 19.43 85.31 20.60 98.11 22.25 41.00 41.45 13.73 51.87…
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW 5.00 145.54 35.93 137.04 37.05 129.29 38.19 122.20 39.37 114.50 41.34 105.34 43.41 6.00…
-
Ambient temp.(℃)
Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW 40.00 85.78 26.91 107.22 30.57 126.14 33.97 140.16 36.93 152.34 38.87 170.63 38.33 196.22 41.39 41.00 82.89 27.45…
-
9.4 MCCH185A-SA3
Cooling: Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW 5.00 207.12 55.49 195.03 57.20 183.99 58.97 173.90 60.80 162.94 63.83 149.91 67.03 6.00…
-
Ambient temp.(℃)
Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW 40.00 124.31 38.17 155.39 43.37 182.81 48.19 203.13 52.38 220.79 55.14 247.28 58.45 284.38 63.12 41.00 120.14 38.95…
-
Cooling: Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 35.00 40.00 46.00 52.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW 5.00 279.89 68.96 263.55 71.09 248.63 73.29 235.00 75.56…
-
Ambient temp.(℃)
Hot water outlet temp. -10.00 -6.00 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) KW KW KW KW KW KW KW KW KW KW KW KW KW KW 39.00 167.82 50.06 209.78 56.88 246.80 63.20 274.22 68.70 298.07 72.31 333.83 76.65 383.91 82.78 41.00 162.18…
-
10 Troubleshooting
Failure & Protection Codes of the Module 30kW module (For MCCH30A-TA3SL and MCDH30A-TA3SL only) No, Code 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total outlet water temperature sensor error (Be valid for main unit) 5 E4 Unit outlet water temperature…
-
No Code Trouble 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error (Be valid for main unit) 5 E4 Unit outlet water temperature sensor error 6 E5 Pipe temperature sensor error in condenser A 7 E6 Pipe temperature…
-
No Code Trouble 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error (Be valid for main unit) 5 E4 Unit outlet water temperature sensor error 6 E5 Pipe temperature sensor error in condenser A 7 E6 Pipe temperature…
-
No, Code 1 E0 Water flow detection error (The third time) 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temperature sensor error in shell and tube exchanger 6 E5 Pipe temperature sensor error in condenser A 7 E6 Pipe…
-
No, Code Trouble 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Error of total outlet water temperature sensor(Be valid for main unit) 5 E4 Outlet water temperature sensor error in shell and tube exchanger 6 E5 Pipe temperature sensor error in condenser A…
-
10.2 Troubles and Solutions
Troubles Possible reasons Solutions Air or other non-condensing gas still in the system. Discharge gas from refrigerant charging inlet. Re-vacuum the system if necessary. Fins in the condenser are dirty or foreign substance blocking fins. Clean condenser fins. Insufficient chilling air volume or…
-
Troubles
Possible reasons Over high or over low voltage. Compressor stops because of integrate Over high air expelling pressure or excessive temperature sensor or air low air suction pressure. discharge temperature protection. Component error. Filter in front (or rear) of expanding valve is blocked.…
-
10.3 Typical malfunction solutions
1) High pressure and discharged temperature protection High pressure and discharged protection. Yes High pressure protection. No Discharge protection. Yes Inspect fan motor and capacitor (1phase) or start up the water pump. temperature Yes Blower stops rotating or rotates in reversed direction in…
-
Discharge
protection. temperature Yes Discharge temperature switch is broken or joint is loose. Yes Replace discharge temperature switch, fixed joint. No Refrigerant is too less. Yes Detect leakage for all system, append refrigerant. Yes Replace the EXV or coil. No Couldn‟t open the EXV. No The EXV, capillary…
-
2) Current protection
Current protection Yes The fin of heat exchanger is dirty or aged in cooling mode, or the shell and tube scaled strong. Yes Clean heat exchanger. Yes Check the fan motor, capacitor (1 phase) or start up water pump. Yes Empty, vacuuming and append refrigerant if necessary. Yes Check power supply…
-
4) Inlet &outlet water temperature difference protection
Inlet &outlet water temperature difference protection. Yes Water flow is lower. Yes Refer to the water flow malfunction to analysis. Yes Replace sensor. No The outlet water temperature sensor or inlet water temperature sensor brought drifting when collect temperature. temperature No PCB mistakes to…
-
7) Power supply phase sequence malfunction
Power supply phase sequence malfunction. Yes Phase sequence error. Yes Adjust connecting wire. No Lack of phase. Yes Check power supply. Yes Replace phase protector. No Phase lack protector is broken. lack No PCB mistakes to alarm. Yes Replace PCB. No Inform the customer service center. 8)…
-
9) Water flow detection malfunction
Water flow detection malfunction Yes Water pump didn‟t open or error. Yes Open the pump or change; inspect the power supply or control circuit of pump. Yes Open the valve. Yes Replace the water flow switch, inspect the connecting wire. Yes Adjust the position. No Didn‟t open the valve in system. No…
-
10) Total outlet water temperature sensor malfunction
Total outlet water sensor malfunction temperature Yes The circuit of total outlet water temperature sensor is broken. Yes Replace temperature sensor. No The circuit of total outlet water temperature sensor is shorten. Yes Replace sensor. temperature No The joint of total outlet water temperature…
-
12) The unit inlet water temperature sensor malfunction
The unit inlet water temperature sensor malfunction Yes The unit‟s circuit of inlet water temperature sensor is broken. Yes Replace temperature sensor. No The unit‟s circuit of inlet water temperature sensor is shorten. Yes Replace temperature sensor. No The unit‟s joint of inlet water temperature…
-
14) Ambient temperature sensor malfunction
Ambient temperature malfunction. sensor Yes The circuit of ambient temperature sensor is broken. Yes Replace temperature sensor. No The circuit of ambient temperature sensor is shorten. Yes Replace temperature sensor. No The joint of ambient temperature sensor is loose. Yes Fixed joint. No Yes PCB…
-
11 Installation
11.1 Unit Installation 11.1.1 Transportation The angle of inclination should not be more than 15º when carrying the unit, to avoid overturn of the unit. a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the length of each rod must be more than the…
-
65kW module
130kW module 78
-
185kW module
The position should be provided with an at least 50mm thick wood block, cloth or hard paper, to avoid damages to the unit. The position should be provided with an at least 50mm thick wood block, cloth or hard paper, to avoid damages to the unit. Lifting angle Fig. 2-1 Lifting of the unit 250kW…
-
11.1.2 Installation space
● Requirements of arrangement space of the unit 1) To ensure adequate airflow entering the condenser, the influence of descending airflow caused by the high-rise buildings around upon the unit should be taken into account when installing the unit. 2) If the unit is installed where the flowing speed…
-
130kW module
-
B
Input of airflow A D C 250kW module Input of airflow E Input of airflow Input of airflow The recommend space parameter Module A B Installation space (mm) C ≥1500 ≥2000 ≥2000 D E ≥1500 ≥8000 MCCH30A-TA3SL MCDH30A-TA3SL MCCH65A-SA3L MCDH65A-SA3L MCCH130A-SA3L MCCH185A-SA3 MCCH250A-SA3T ≥2000 ≥2000…
-
If the spaces mentioned above cannot be met, the air passing from the unit to the coils may be restricted, or back flow of air discharge may occur, and the performance of the unit may be affected, or the unit may fail to operate. No Model 1 MCCH30A-TA3SL Max unit combined quantity 1 2 MCDH30A-TA3SL…
-
Location drawing of installation foundation of the unit (unit: mm)
-
250kW module
-
1.4 Installation of damping devices
※ Damping devices must be provided between the unit and its foundation. By means of the Φ15mm diameter installation holes on the steel frame of the unit base, the unit can be fastened on the foundation through the spring damper. See figure above (Schematic diagram of installation dimension of the…
-
d. The pump installed in the water pipeline system should be equipped with starter. The pump will directly press water into the heat exchanger of the water system. e. The pipes and their ports must be independently supported but should not be supported on the unit. f. The pipes and their ports of…
-
Performance adjustment factors
The antifreeze must be required according to anyone condition as following: 1. The outlet water temperature is below 5℃; 2. The ambient temperature is below 0 ℃; 3. Don‟t start up the unit for a long time. 4. The power supply was cut off and needn‟t change the water in system. Ethylene and Propylene…
-
Foreign matter in the chilled water system will adversely affect the heat transfer capability of the evaporator, and could increase the pressure drop and reduce the water flow. To provide optimum unit operation, proper water treatment must be maintained. Refer to the able as following. Fouling…
-
d. Special grounding screws should be used for earth connection. Bolts should not be installed or removed at will; otherwise flow switches may suffer deformation and failure. e. Flow switches have been set at minimal flow value before leaving the factory. They should not be adjusted below the…
-
2) Installation mode II
n :the module quantity, max 16 1.2.5 Installation of water system pipeline for 65kW module Installation of single-module water system pipeline Installation of multi-module water system pipeline 1) Installation mode I (recommended installation mode) n :the module quantity, max 6
-
less than 6 modules
2) Installation mode III (recommended installation mode) n : the module quantity, max 16 Installation mode A: less than 16 modules 3) Installation mode IV n : the module quantity, max16
-
No.n module
No.(n-1) module No.1 module No.(n-1) address No.(n-2) address No.0 address Drill dead hole at the position, and move the total effluent temperature sensor at No.0 address to the position No.(n-2) module No.(n-3) module No.2 module No.(n-3) address No.(n-4) address No.1 address Water flow switch Pump…
-
Electric control box
Total water outlet temp sensor Water intlet Water outlet Installation of multi-module water system pipeline 1) Installation mode I (recommended installation mode) n : the module quantity, max8 No.1 unit No.0 address(main unit) No.1 address No.(n-1) unit No.(2n-3) address No.(2n-4) address No.n unit…
-
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows. Installation mode of multi-module combination water system pipeline n : the module quantity, max5 a. Installation mode I (recommended installation mode) No.1 unit No.0 address(main…
-
Less than 8 modules
Notice: 1) For installation of multi-module, the most modules should be not more than 8 modular units. 2) For installation of multi-module, please drill a dead hole(Φ9mm) at the total water outlet pipeline, and move the total water effluent temperature sensor at No.0 address to the hole. Table of…
-
Table of diameter parameters of main inlet and outlet pipes for 130kW module
130×1 Total inlet and outlet water pipe diameter DN65 130×5 Total inlet and outlet water pipe diameter DN125 130×2 DN100 130×6 DN150 130×3 DN100 130×7 DN150 130×4 DN125 130×8 DN200 Unit model x quantity Unit model x quantity Table of diameter parameters of main inlet and outlet pipes for kW module…
-
Minimum and Maximum water flow rates
Item Model Water flow rate(m3/h) Minimum Maximum 0&&+$7$6/ 4.68 5.72 0&'+$7$6/ 4.68 5.72 0&&+$6$/ 10.08 12.32 0&&'$6$/ 10.08 12.32 0&&+$6$/ 18.54 22.66 0&&+$6$ 27.9 34.1 0&&+$6$7 38.7 47.3 1.2.10 Design of the store tank in the system a. kW is the unit for cooling capacity, L is the unit for (G)…
-
maximum allowable pressure and cause water to discharge from the pressure relief valve, thus wasting
water. If the closed tank is too large, when the water temperature drops, the system pressure may decrease to a level below the minimum allowable value and cause trouble in the air vent. Therefore, accurate sizing of a closed expansion tank is essential. For diaphragm expansion tanks, the minimum…
-
1.3.1 Precautions
1. The air-conditioner should apply special power supply, whose voltage should conform to rated voltage. 2. Wiring construction must be conducted by the professional technicians according to the labeling on the circuit diagram. 3. Only use the electric components specified by our company, and…
-
● Only use 380-415V 3Ph 50Hz rated power supply for the unit, and the maximum allowable range of
voltage is 342V-418V. ● All electric wires must conform to local wiring connection norm. The suitable cables should be connected to power supply terminal through wiring connection holes at the bottom of the electric cabinet. According to Chinese standard, the user is responsible for providing…
-
1.3.4 Wiring steps
Content 1 Check the unit and ensure that it is connected with grounding wires correctly, to avoid leakage, and the grounding devices should be mounted in strict accordance with the requirements of electrical engineering rules. The grounding wires can prevent electric shock. 2 The control box of the…
-
Note: (For the module with KJR-120A/MBE)
1 .Wiring of “ON/OFF” weak electric port ○ 0# electric control box “ON/OFF” port Red ON/OFF signal Power (DC 12V) Main control board is provided Corresponding parallel connect the “ON/OFF” port of the main unit‟s electric control box, then, connect the “ON/OFF” signal (provide by user) to the…
-
1 Commissioning
1. Preparation ● After the water system pipeline is flushed several times, please make sure that the purity of water meets the requirements; the system is re-filled with water and drained, and the pump is started up, then make sure that water flow and the pressure at the outlet meet the…
-
1 Maintenance
Maintenance for main components: ● Close attention should be paid to the discharge and suction pressure during the running process. Find out reasons and eliminate the failure if abnormality is found. ● Control and protect the equipment. See to it that no random adjustment be made on the set points…
-
system is discharged. Before injecting refrigerant, the whole refrigeration system must be completely dry and of vacuum pumping. ● Connect vacuum pumping pipe at the fluoride nozzle at low-pressure side. ● Remove air from the system pipe with vacuum pump. The vacuum pumping lasts for above 3 hours.…
-
Regularly preventive maintenance plan
Maintenance Items General Appearance Compressor Anytime Vibration Anytime Voltage Anytime Judge whether there is abnormal sound by hearing; Watch whether the swings of distribution pipes and components are too large Rating voltage is within ±10% Clean Anytime Keep it clean anytime Calm Insulation…
-
Maintenance Safety Requirement
Each component should be maintained by qualified technicians. Please contact competent maintenance technicians in the event of leakage or breakdown. The safety devices should be checked after each maintenance. Once leakage occurs, all the refrigerant in unit should be pumped out and the leak point…
-
1 Control System
1.1 PCB Outline and Description 1.1.3 New 30kW module PCB, outlook view (Available for 0&&+$7$6/,0&'+$7$6/) 1.1.4 New30kW module components description (Available for 0&&+$7$6/, 0&'+$7$6/) No. Detail information 1 Detection of current of the compressor A1 (Protection code P4). Detection of current…
-
3) T4, T3B and T3A: when the temperature sensor is detected to suffer open circuit or short circuit, fault alarm will occur. ● When the main unit suffer fault of temperature sensor: the main unit and subordinate units will be shut down. ● When the subordinate unit suffer fault of temperature sensor…
-
2) Subordinate unit: (Water flow detection will not be done)
COM (I) 485 communication port (Fault code E2). COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication. 1) If faults occur between the wired controller and the main unit module, all modules will be shut down. 18 2) If faults occur between the main unit and subordinate…
-
Each modular part of modular unit has the same electric control function, and the main unit and subordinate units can be set through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being the main unit is given to the unit with digital…
-
MGBL-D65W/RN1 module components description: No. Detail information 1 Detection of current of the compressor A1 (Protection code P4). Detection of current of the compressor B1 (Protection code P5). 2 Current is not detected within the initial 5 seconds after the compressor is started up. When the…
-
Adjustment range of constant speed capability: ON and OFF. Adjustment range of constant speed capability: ON and OFF. Total outlet water temperature sensor (Fault code E3). 6 Only the main unit is valid, and the subordinate units are invalid. Under refrigerating mode and heating mode, conduct…
-
2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering communication fault will be shut down. Less units will be detected by the wired controller, which may display EA, and in the meanwhile, the indicator lamp of the wired controller will flash, restart…
-
Input of three-phase four-wire power supply (Fault code E1)
Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle should be 120º 28 among them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will be displayed. When the power supply returns to normal condition…
-
0&&+$6$/ module components description No. Detail information 1 Detection of current of the compressor A1 (Protection code P4). Detection of current of the compressor B1 (Protection code P5). 2 Current is not detected within the initial 5 seconds after the compressor is started up. When the current…
-
Adjustment range of constant speed capability: ON and OFF. Adjustment range of constant speed capability: ON and OFF. 7 Inlet water temperature sensor (Fault code EF). Total outlet water temperature sensor (Fault code E3). 8 Only the main unit is valid, and the subordinate units are invalid. Under…
-
COM (O) 485 communication port (Fault code E2). 20 21 Anti-freezing pressure protection of the system A(Protection code Pc). Anti-freezing pressure protection of the system B(Protection code Pd). The alarm signal output of the unit(ON/OFF signal). Auxiliary electric heater: Attention: the control…
-
through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being the main unit is given to the unit with digital compressor, and other addresses are subordinate units. Only the unit is chosen as the main unit, its electric control can…
-
0&&+$6$/ module components description No. Detail information 1 Detection of current of the compressor A1 (Protection code P4). Detection of current of the compressor B1 (Protection code P5). 2 Current is not detected within the initial 5 seconds after the compressor is started up. When the current…
-
Adjustment range of constant speed capability: ON and OFF. Adjustment range of constant speed capability: ON and OFF. 7 Inlet water temperature sensor (Fault code EF). Total outlet water temperature sensor (Fault code E3). 8 Only the main unit is valid, and the subordinate units are invalid. Under…
-
20 21 COM (O) 485 communication port (Fault code E2). Anti-freezing pressure protection of the system A(Protection code Pc). Anti-freezing pressure protection of the system B(Protection code Pd). The alarm signal output of the unit(ON/OFF signal). Auxiliary electric heater: Attention: the control…
-
through address code on the electric control board. The address code 0 # is provided as the main unit. The priority of being the main unit is given to the unit with digital compressor, and other addresses are subordinate units. Only the unit is chosen as the main unit, its electric control can…
-
1.1.9 kW Module PCB, outlook view
Electric control schematic diagram of the unit 1 Electric control diagram of the main unit and subordinate units (see Attached Drawing (I)) 2 Schematic diagram of connection and communication of the main unit and subordinate units (see Attached Drawing (II)) 3 Indicating diagram of electric control…
-
Total outlet water temperature sensor (Fault code E3). Only the main unit is valid, and the subordinate units are invalid. Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet water temperature. Adjustment range: Load, stabilize, unload, Emergency…
-
Water flow detection (Fault code of the main unit E0) is only valid for the main unit but invalid for subordinate units. 1) Main unit: if abnormal water flow occurs for the first and second time, the main unit board will display fault code E9. If abnormal water flow occurs the third time, the main…
-
1.1.11 250kW Module PCB, outlook view
4.1 1.1.12 250kW module components description No Detail information 1 Detection of current of the compressor A1 (Protection code P4). 2 Detection of current of the compressor A (Protection code P4). Current is not detected within the initial 5 seconds after the compressor is started up. When the…
-
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents are as shown in the following figure: Normal display Operating mode 7 Operating capability of the compressor B T61 frost-proof temp EXV opening A Unit outlet water temp EXV opening B…
-
Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45℃, the switch will be closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than 50℃, the switch will be opened, and the auxiliary electric…
-
1.3 KJR-120A/MBE (Standard accessory)
R 1 ON/OFF TIME ON 6 8 TEMP. SET TIME OFF 7 9 OK MODE 2 12 PAGEUP/TEMP+ ALARM CLEAR 3 QUERY 4 CLOCK 5 LOCK 14 13 PAGEDOWN/TEMP- LOC K HYSTERESIS 10 ADDRESS - 11 ADDRESS+ 16 ADDRESS SET 15 HYSTERESIS ADDRES S SE T 1. Operating instructions of buttons ①ı ON/OFF button: In the power off status, press…
-
minute can be adjusted by “ADDRESS/+” and “ADDRESS/-”, after the adjustment then press the OK
button for the setting confirmation. ⑥⑦ TIME ON/TIME OFF button Press the “TIME ON” button once Press for the first time , and enter to the hour adjustment of timing on, and press again Press for the second time , and enter to the minute adjustment of timing on. The numerical valve of hour and…
-
LCD Diagram of Wired Controller
Display operation mode Display operation status Display Query data Display time-on/off 2. OPERATION PROCEDURE OF WIRED CONTROLLER ● Operation procedure of mode setting 1). Press MODE at shutdown status, you could select appropriate mode as you want. The function is invalid at startup status. 2). The…
-
● Operation procedure of HYSTERESIS TEMP.SET(δ )
1).Through the hysteresis setting, the system can adjust the load effectively. 2). The adjusting logic of cooling mode : (the parameter of δ1,δ2,Tj1 and Tj2 are decided by the outdoor unit) 3). The adjusting logic of heating mode: (the parameter of δ1,δ2,Tj1 and Tj2 are decided by the outdoor unit)…
-
d. If it is under the host computer network control, Net-ON displays, otherwise there is no display
e. If it is under wired controller locked or button locked state, it displays display after the lock is unlocked. the lock mark. There will be no Treatment of display data The data display area is divided into Up area and Down area, with two groups of two-digit half 7-segment digital display…
-
a. Upon entering the spot check page display for the first time, the default selected 0# modular unit displays the state data of the first page. b. Contents in other pages are displayed circularly by pressing the page-up/down button. c. Pages 1-12 of data display Down area show Error code,protection…
-
4. INSTALLATION PROCEDURE
Installation procedure: Use PQE connect with each other when several wired-controllers are parallel. NOTE Please connect the attached shorted-wires to the corresponding communication port COM(I) or COM(O) in the main control board of the last parallel unit (dial code ). Directly connect to the last…
-
OUTLINE OF FUNCTIONS
This wired controller provides the following functions: 1). Connect with the outdoor unit through the terminals P, Q and E. Connect with the upper unit through the terminals X, Y and E(reserved).Connect with other wired controllers through the terminals P, Q and E. 2). Set the action mode through…
-
1.5 Control software
a. Interface introduction 1)The LOGIN window as above picture. 2)User need to input the name and password (default name: Admin, default password: Admin); user‟s name and password could be changed after login. 3)Select the computer serial port. The system default selection is COM1 (the software will…
-
Fig.4-3
Fig.4-4 7)In case the password error time exceed 6 times (i.e. the 7th times password error), the window show as Fig.4-5, and then click OK, it will exit the program. Fig.4-5 8)In case the selected serial port is unavailable, the window as Fig.4-6 will be display. Fig.4-6 b. Detail application…
-
1)Menu includes:“System”、“Equipment management”、“Schedule management”、“Communication
parameter” “Help” 2)System configuration illustration (The ① as Fig.4-7): Not more than16 wired controllers could be connected to the computer. This kind of wired controller could be connected to the module group of : 30KW 65KW18KW etc. Total 16 sub-modules could be jointed to a wired controller.…
-
Fig.4-10
c. Menu application 1)“System” includes: “Password Modification” “Re-login” “Exit the program” Fig.4-11 1 Click “Password Modification” will display window as Fig.4-12 input old password as requirement, ○ and then reset a new password, click “OK” or “Modify”, window as Fig.4-13t will show that new…
-
Fig.4-18
1 .Click “KJR Setting”, the window as Fig. 4-20 will be display——add wired controller to the system to be ○ monitored. Fig.4-20 Detail operation procedure as follows: a Add a wired controller: Select the wired controller address (0-15) at the “KJR Address”, fill the wired controller name at “KJR…
-
Fig.4-25
a Add sub-module: Select the existing wired controller address from the “KJR Address”, and select the configured module group at the drop-down box of “Module name”, select the sub-module address in the drop-down box of the configured “Sub-module address”, and then click “Add”. The sub-module would…
-
(3)Blue color represents at less one Weekly Timing schedule has been set in this wired controller as well as at less one of this schedule in activating. Fig.4-29 a KJR Address——Wired controller address, each wired controller represents one refrigeration system. b Weekly timing function―-Display the…
-
f、Modify(See the ③ key in the Fig.4-29) ――Press this key the parameter of selected period become
changeable, and then click “ Save ” . Press the key again, all parameters in this period become unchangeable. See Fig. 4-33. Fig.4-33 Select the setting Period, click “Modify”, all parameter will become changeable status, see Fig. 4-34. Fig.4-34 g Delete key (See the ④ key in the figure) ――select a…
-
Fig.4-37
Time Off:Turn off time, when Time Off selecting ”--:--“ , then means do not turn off the unit , display as Fig 4-38. Fig.4-38 Timing Status:Drive up the weekly timing function in the current period or not. Control Mode:Automatically drive-up mode Mode set:Operation mode: Cooling, Heating, Water Pump…
-
Fig.4-43
(2)Detail procedures of modify a Weekly Timing Schedule: a Select a wired controller: By clicking the “System diagram for weekly timing AC” wired controller icon at the left side in the wired controller, or by selecting the wired controller at the drop-down box of “KJR Address”. b Select a wired…
-
Fig.4-47
Fig.4-48 Fig.4-49 4)“Communication parameter” includes:“Serial port set” and “History set” See Fig.4-50 Fig.4-50 ①ı Click “Serial port set”, window as Fig. 4-51 will pop up—— modify or select the serial port in computer. The available serial port source is captured by software, and saved at the…
-
Fig.4-53
②Click “History set”, an interface as Fig. 4-54 displays ―――to modify or select the history error saving duration. Fig.4-54 5) “Help” includes:“User guidance” and “About”. See Fig. 4-55 Fig.4-55 1 Owner‟s manual——Software application manual, i.e. this manual. ○ ②About——some relevant software…
-
Fig.4-58
Fig.4-59 Fig.4-60 Provided that the selected wired controller in lock status, the key would display “Unlock KJR”(see Fig. 4-61), once successful unlock the wired controller, the message box (see Fig. 4-62) would display, then the key displays “Lock KJR”(see Fig. 4-63); If the set failed, message box…
-
Fig.4-65
If successful query the system, a message box (see Fig. 4-66) will pop up and note you query success, and system parameter interface will update according to the query result. (Fig. 4-67) Fig.4-66 Fig.4-67 Whereas, “Query overtime” would display (see Fig. 4-68). Provided that the wired controller…
-
Fig.4-70
Fig.4-71
-
Sub-module Query
Click the “Query”, system will query the operative status and display the information in the operation interface according to the current selected sub-module. In the querying, a message box (see Fig. 4-72) would pop up: “Query success” (see Fig. 4-73) to note you the query is successful and update…
-
More parameters
Click More Parameters, you could query more data (See Fig.4-79). If the sub-module hasn‟t been selected, a message box as Fig. 4-80 would show. You must click a certain sub-module firstly, and then to click the “More parameters” key, more parameter could be queried; a message box (See Fig.4-81) will…
-
Fig.4-84
Fig.4-83 Click the “System operate set” in the conditioner of without Control Mode has been selected, a message box as Fig. 4-85 would show. Fig.4-86 Fig.4-85 Click the “System operate set” in the conditioner of without Mode set has been selected, a message box as Fig. 4-86 would show. Click the…
-
Fig.4-90
Fig.4-91 3)Uniformly set all wired controllers: Tick Uniformly Set as Fig. 4-92, and then select the corresponding parameters, click the System Operate Set, system starts to set up. A message box as Fig. 4-93 will display during the setting. Once successful setting, a message box as Fig. 4-94 will…
-
Fig.4-98
Fig.4-97 2 The window “System Properties” will be popped-up after selecting the “Properties”, and then select the “Device Manager” in the “Hardware” as Fig. 4-98 3 The window “Device Manager” will be showed up after clicking the “Device Manager, as Fig. 4-99. Fig.4-99 Fig.4-100 4 Click the icon “ ”…
-
1.6 Lonworks (Optional)
1.6.1 Introduction It is applied the central A/C system and the Building Management System (BMS) (namely Automated Building System) to realize the integration of A/C system and Building Management system. To LonWorks To Air-cooled Modular system SWITC H O F PO WER PO WER AC 220V 15.6.2 Features…
-
Software configuration ● LonMark standard allocative attribute ● Support Direct-Memory reading and writing by the LNS network management tool. 7 Communication port Communication port 8 Size 31.9cm X 25.1cm X 6.1cm 1.6.4 External dimension There are three installation methods as the following figure.…
-
Connection Method 2
LSQ-LONWORKS RS485(P Q E) Air-cooled Modular units:Max 16 units(The network address is unique) LONWORKS NET WORK BMS SYSTEM Caution This system adopts the manner of shared network variable to manage A/C system, which cannot access the appointed A/C within central A/C system, until the co-responding…
-
nciCtrl_Addr
Corresponding address of wired controller Caution First power on, it needs to set the gateway property as the actual conditioner, then connect the gateway which has been set to the Air-cooled Modular system. * In a Air-cooled Modular system, there are wire controller and gateway, the address which…
-
nvoOutTemp
nvoOnNum nviSetMode nvoRunNum nviSetTemp Air-cooled Modular system nviTempDiff nvoSystemMode nvoCoolTempHi nvoCoolTempLo nviClrErrorState nvoHeatTempHi nvoHeatTempLo Input network variable of air-cooled modular system Output network variable of air-cooled modular chiller unit system
-
Name
Network variable name 1 Running state nvoSystem Mode Network variable type Date definition Descriptions Display the running mode HVAC_COOL: Cool Mode of Air-cooled Modular HVAC_HEAT: Heat Mode SNVT_hvac_mode HVAC_FAN_ONLY: Water pump Mode system. The initial value of first HVAC_OFF:Off Mode power on…
-
The network variable which is assigned to each unit module: 6 output network variable, used for
displaying detail parameters of unit modules. NO Name Running mode Error code Protection code Network variable name nvoRunMode s[n] nvoErrorCod e[n] nvoProtectCo de[n] Network variable type Date definition Operating mode of unit HVAC_COOL: Cool Mode * n means the address of the unit, HVAC_HEAT: Heat…
-
6 Name Current of Compressor A Current of Compressor B Network variable name nvoCompA Current[n] nvoCompB Current[n] Network variable type Date definition SNVT_count 0~250A SNVT_count 0~250A Descriptions Compressor A current of unit. *n means the address of the unit, nvoCompACurrent[1] means the…
-
2.Temperature-Resistance characteristic sheet for pipe temperature sensor,ambient temperature
sensor,inlet water temperature sensor and outlet water temperature sensor. Sensor characteristic sheet Unit:Temp:℃--K, Ratio:KΩ Temp. Ratio Temp. Ratio Temp. -20 115.266 20 12.6431 60 2.35774 Ratio Temp. 100 0.62973 Ratio -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5 62 2.19073…
-
3.Temperature-Resistance characteristic sheet for discharge temperature sensor of digital
compressor. Sensor characteristic sheet Temp Ratio Temp Ratio Temp Ratio Unit:temp:℃--K, Ratio:KΩ Temp. Ratio Temp. Ratio -40 2889.60000 13 148.39300 66 17.29460 119 3.45032 172 0.97524 -39 2704.61400 14 141.59040 67 16.70980 120 3.35400 173 0.95632 -38 2532.87200 15 135.14040 68 16.13360 121…
-