Service manual
-
1. Features
1.1 Energy saving 1.1.1 All DC inverter compressors All DC inverter compressors make the capacity output better distributed, and always work at 60-140Hz which is the most efficient range. It makes the efficiency more than 30% higher than the normal. New structure-enhanced mid-frequency performance…
-
1.2 Flexible design
1.2.1 Wide capacity range The outdoor units’ capacity range from 8HP to 64HP in 2HP increment. Maximum 64 indoor units with capacity up to 130% of total outdoor units can be connected in one refrigeration system. 1.2.2 Wide operation range The V4 Plus R series system operates stably at extreme…
-
1.3 High reliability
1.3.1 Cycle duty operation In one combination, any of the outdoor unit can run as the master unit and master unit can cycle in a period, to realize the equal lifespan among the outdoor units. As a result extend the system lifespan significantly. Priority Priority Priority Priority Cycle duty between…
-
1.4 Enhanced comfort
1.4.1 Cooling and heating simultaneous for new designed MS (Mode Switch) equipment The outdoor unit individual controls the operation mode of each group indoor unit to achieve simultaneous heating and cooling in one system under the MS unit which adopts solenoid valve to precise control refrigerant…
-
1.4.3 Continuous heating during defrost operation
Each heat exchanger is defrosted by using heat transferred from one heat exchanger to the other in the outdoor unit. Outdoor Unit Outdoor Unit Outdoor Unit Heat Exchanger 1 Heat Exchanger 1 Heat Exchanger 1 Heat Heat Heat Exchanger 2 Heating Heat Exchanger 2 Defrosting heat exchanger 1 Heat…
-
1.5.4 Professional structure design
Compressor is near the outside, and there is simple pipe system for convenient maintenance. The newly designed rotating control box is so excellent that it can rotate in a wide angle. It is convenient for the inspection and maintenance of the pipeline system and greatly reduced the time of dismount…
-
2. Outdoor units lineup
-
Combination table
-
3. MS units lineup
-
4. Indoor units lineup
Cassette type One-way cassette Capacity Compact four-way cassette Two-way cassette Four-way cassette (×100W) 18 ● 22 ● ● ● 28 ● ● ● ● 36 ● ● ● ● ● 45 ● ● ● ● 56 ● ● ● ● 71 ● ● 80 ● 90 ● 100 ● 112 ● 140 ● Duct type Capacity Low static pressure duct Medium static pressure duct High static pressure…
-
Indoor units lineup
Floor-standing/Ceiling & Floor/Console Ceiling & floor Cased floor-standing console Capacity (×100W) 22 ● ● 28 ● ● 36 ● ● ● 45 ● ● ● 56 ● ● 71 ● ● 80 ● ● 90 ● 112 ● 140 ● 160 ● Wall mounted Wall mounted Wall mounted 22 ● ● 28 ● ● 36 ● ● 45 ● ● 56 ● ● 71 ● ● Capacity (×100W) Note: Due to continuous…
-
5. Nomenclature
5.1 Outdoor unit MVUH252B - VA3 Power 1 - 1 phase, 50 Hz 3 - 3 phases, 50 Hz Refrigerant A - R410A B - R22 Inverter (in)V(erter) - inverter S(tandard) – on/off Model, Modification A…Z, AA…ZZ Capacity index kW*10 The main feature of the system air cooled: C(ooling) – cooling only H(eat pump)…
-
5.2 MS unit
MS 02 E / N1 - C Series code Refrigerant type N1: R410A E: The MS can connect only one indoor unit Omit: The MS can connect multiple indoor units MS type 02: Two groups refrigerant pipe 04: Four groups refrigerant pipe 06: Six groups refrigerant pipe MS unit 14 General Information
-
5.3 Indoor unit
MVC28A – VA1 Design features (may be absent) For example: G(rey), W (hite) - color Power 1 - 1 phase, 50 Hz 3 - 3 phases, 50 Hz Refrigerant A - R410A B - R22 Inverter (in)V(erter) - inverter S(tandard) - on/off Model, Modification A…Z, AA…ZZ Capacity index kW*10 Type of the indoor unit W(all) - wall…
-
Part 2 Selection Procedure
1. Introduction 17 2. Unit selection (based on cooling load) 22 Selection Procedure 16
-
1. Introduction
1.1 Model selection procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor air-conditioning load, Calculate the maximum air-conditioning load for each room or zone. Selection of an air conditioning system…
-
The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to and smaller than the capacity index at 100% combination ratio of each outdoor unit. Up to 8~16 indoor units can be connected to one outdoor unit. It is recommended to choose a larger…
-
INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE
Indoor Unit Combination Ratio kW(Btu/h) Outdoor Unit 40(385600) 42(409500) 44(426500) 46(443600) 48(460600) 50(488600) 52(498100) 54(516900) 56(539100) 58(563000) 60(580000) 62(597100) 64(614000) 130% 120% 110% 100% 90% 80% 70% 60% 50% 146.9 135.6 124.3 113.0 101.7 90.4 79.1 67.8 56.5 (501200)…
-
1.4 Actual performance date
Use OUTDOOR UNIT CAPACITY TABLES. Determine correct table according to the outdoor unit model and combination ratio. Enter the table at given indoor and outdoor temperature and find the outdoor unit capacity and power input. The individual indoor unit capacity (power input) can by calculated as…
-
1.5.2 Heating capacity modification
-
2. Unit selection (based on cooling load)
2.1 Given condition Condition: Cooling: indoor temperature 20oCWB, outdoor temperature 35oCDB; Cooling load Location Room A Room B Room C Room D Room E Room F Load kW(Btu/h) 2.1(7170) 2.8(9559) 3.5(11900) 4.6(15700) 5.8(19790) 7.2(24570) Power supply: outdoor 380~415V-3Ph-50Hz, indoor…
-
2.4 Conclusion
Generally, we think this result is acceptable, so we can think we have accomplished the calculation. But if you think this result is not acceptable, you can repeat the above process. Remark: In this sample, the other capacity modification indexes don’t be considered and are assumed as 1.0. For more…
-
1. Specifications
1.1 Outdoor unit specifications Independent unit specifications Model MVUR252B-VA3 MVUR280B-VA3 MVUR335B-VA3 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/60 380-415/3/60 380-415/3/60 kW 25.2 28.0 33.5 Btu/h 86,000 95,500 114,300 kW 5.73 6.67 8.07 kW/kW 4.40 4.20 4.15 kW 27.0 31.5 37.5 Btu/h…
-
Number of circuits
Outdoor air flow Sound pressure level Connectable Total capacity indoor unit Max. quantity Outdoor unit Refrigerant Additional m /h 12,000 12,000 13,000 CFM 7,060 7,060 7,650 dB(A) % 50-130 50-130 50-130 Net dimension (W×H×D) mm 1250×1615×765 Packing (W×H×D) mm 1305×1790×820 Net weight kg Gross…
-
Independent unit specifications
Model MVUR400B-VA3 MVUR450B-VA3 380-415/3/50 380-415/3/50 380-415/3/60 380-415/3/60 kW 40.0 45.0 Btu/h 136,500 153,500 kW 11.30 13.24 kW/kW 3.54 3.40 kW 45.0 50.0 Btu/h 153,500 170,600 kW 11.19 12.79 kW/kW 4.02 3.91 E655DHD-65D2YG+ E655DHD-65D2YG+ E405DHD-36D2YG E405DHD-36D2YG Type DC inverter DC…
-
Connectable
Total capacity indoor unit Max. quantity Outdoor unit Refrigerant MIV V5 Heat Recovery DC Inverter R410A CFM 8,830 8,830 dB(A) 60 60 % 50-130 50-130 23 26 Net dimension (W×H×D) mm 1250×1615×765 1250×1615×765 Packing (W×H×D) mm 1305×1790×820 1305×1790×820 Net weight kg 303 303 Gross weight kg 322 322…
-
Combination unit specifications
Combination unit MVUR532B-VA3 MVUR560B-VA3 MVUR615B-VA3 MVUR252B-VA3 MVUR280B-VA3 MVUR280B-VA3 MVUR280B-VA3 MVUR280B-VA3 MVUR335B-VA3 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/60 380-415/3/60 380-415/3/60 kW 53.2 56.0 61.5 Btu/h 181,500 191,000 209,800 kW 12.40 13.34 14.74 kW/kW 4.29 4.20…
-
Outdoor unit
Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A Net dimension (W×H×D) mm (1250×1615×765)×2 Packing (W×H×D) mm (1305×1790×820)×2 Net weight kg 255×2 255×2 255×2 Gross weight kg 273×2 273×2 273×2 R410A R410A R410A 10×2 10×2 10×2 FVC68D FVC68D FVC68D EXV EXV EXV MPa 4.4/2.6 4.4/2.6…
-
Combination unit specifications
-
indoor unit
Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A Max. quantity Net dimension (W×H×D) mm (1250×1615×765)×2 Packing (W×H×D) mm (1305×1790×820)×2 Net weight kg 255+303 255+303 303×2 Gross weight kg 273+322 273+322 322×2 R410A R410A R410A 10+13 10+13 13×2 FVC68D FVC68D FVC68D…
-
Combination unit specifications
-
Connectable
Total capacity indoor unit Max. quantity Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A dB(A) % 50-130 50-130 50-130 Net dimension (W×H×D) mm (1250×1615×765)×2 (1250×1615×765)×3 Packing (W×H×D) mm (1305×1790×820)×2 (1305×1790×820)×3 Net weight kg 303×2 303×2 255×2+303…
-
Combination unit specifications
-
Connectable
Total capacity indoor unit Max. quantity Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A CFM 22,950 23,540 24,720 dB(A) % 50-130 50-130 50-130 Net dimension (W×H×D) mm (1250×1615×765)×3 Packing (W×H×D) mm (1305×1790×820)×3 Net weight kg 255×2+303 255+303×2 Gross weight kg…
-
Combination unit specifications
-
Connectable
Total capacity indoor unit Max. quantity Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A % 50-130 50-130 50-130 Net dimension (W×H×D) mm (1250×1615×765)×3 Packing (W×H×D) mm (1305×1790×820)×3 Net weight kg 303×3 303×3 303×3 Gross weight kg 322×3 322×3 322×3 R410A R410A…
-
Combination unit specifications
-
Connectable
Total capacity indoor unit Max. quantity Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A CFM 26,490 31,780 31,780 dB(A) % 50-130 50-130 50-130 Net dimension (W×H×D) mm (1250×1615×765)×3 (1250×1615×765)×4 Packing (W×H×D) mm (1305×1790×820)×3 (1305×1790×820)×4 Net weight kg…
-
Combination unit specifications
-
Outdoor air flow
Sound pressure level Connectable Total capacity indoor unit Max. quantity Net dimension (W×H×D) Packing (W×H×D) Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A 3 m /h 55,000 57,000 60,000 CFM 32,370 33,550 35,320 dB(A) % 50-130 50-130 50-130 inch (49-7/32×63-9/16×30-1/8)×4…
-
Combination unit specifications
-
Connectable
Total capacity indoor unit Max. quantity Outdoor unit Refrigerant Additional MIV V5 Heat Recovery DC Inverter R410A dB(A) % 50-130 50-130 50-130 Net dimension (W×H×D) mm (1250×1615×765)×4 Packing (W×H×D) mm (1305×1790×820)×4 Net weight kg 303×4 303×4 303×4 Gross weight kg 322×4 322×4 322×4 R410A…
-
1.2 MS units specifications
-
2. Dimensions
-
MVUR335B-VA3
-
2.3 MS dimensions
-
3. Service space
3.1 Service space for outdoor unit Ensure enough space for maintenance. The modules in the same system must be on the same height. When installing the unit, leave enough space for maintenance. Unit: in.(mm) (Air outlet) (Air inlet) 4(100)< (Air inlet) 39-3/8(1000)< Installation and maintenance…
-
air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely H-h). Please make the air director on site. Unit: in.(mm) If miscellaneous articles…
-
4. Piping diagrams
MVUR252B-VA3, MVUR280B-VA3, MVUR335B-VA3 EXV-A Liquid valve EXV-B Heat exchanger 1 ST1 ST2 Heat exchanger 2 Low pressure gas valve ST3 High pressure gas valve Oil balance valve Pressure release valve Pressure switch Pressure sensor SV5 SV2 Oil separator Gas-liquid separator SV4 Pressure switch DC…
-
Oil separator: It is used to separate oil from high pressure and high temperature gas refrigerant, which is pumped out from compressor. The separation efficiency is up to 99%, it makes the oil return back to each compressor very soon. Gas-liquid separator: It is used to store the liquid refrigerant…
-
5. Wiring diagram and field wiring
-
54 Specifications & Performances
-
5.2 Field wiring
-
6. Electric characteristics
Units Model MVUR252B-VA3 MVUR280B-VA3 MVUR335B-VA3 MVUR400B-VA3 MVUR450B-VA3 Hz 50/ 60 50/ 60 50/ 60 50/ 60 50/ 60 Power supply Compressor OFM FLA Voltage Min. Max. MCA TOCA MFA MSC RLA (V) (V) (V) (A) (A) (A) (A) (A) 380~415 342 440 18.4 20.8 25 - 17.4 0.42 3.6 380~415 342 440 20.6 22.1 25 - 17.4…
-
7. Capacity tables
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
7.2 Heating capacity tables
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
8. Operation limits
Cooling o Heating o C o o -5 -10 -15 Indoor temperature (DB) -5 -10 23 -15 14 -20 5 o 35 C o 95 F Range for intermittent operation 35 Range for continuous operation F 86 Outdoor temperature (DB) 30 Range for intermittent operation 50 F 122 Range for continuous operation Outdoor temperature (DB) C -4…
-
9. Sound levels
Notes: • Data is valid at free field condition • Data is valid at nominal operating condition Front • Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular 51-3/16(1300) 39-3/8(1000) room in which the equipment is installed •…
-
10. Accessories
Branch joint of outdoor & indoor unit Packing Size Net/gross (mm) Weight (kg) FQZHW-02SB 272×167×232 1.6/2.2 FQZHW-03SB 472×157×312 3.9/5.0 FQZHW-04SB 745×160×335 6.2/7.5 FQZHN-01D 290×105×100 0.3/0.4 FQZHN-01SB 257×127×107 0.6/0.8 FQZHN-02SB 287×137×107 0.7/0.9 FQZHN-03SB 297×167×177 1.1/1.4…
-
1. Select installation position
101 Ensure that the outdoor unit is installed in a dry, well-ventilated place. Ensure that the noise and exhaust ventilation of the outdoor unit do not affect the neighbors of the property owner or the surrounding ventilation. Ensure that the outdoor unit is installed in a…
-
2. Foundation for installation
A solid, correct base can: Avoid the outdoor unit from sinking and avoid the abnormal noise generated due to base. Base types: Steel structure base or concrete base (See the figure below for the general making method) Φ3/8inch(10mm) Expansion bolt Rubber shocking proof mat Solid ground or…
-
3. Master and slave unit setting
When the quantity of outdoor unit is more than two in one system, the outdoor unit should be placed form large capacity unit to small capacity unit. The largest capacity unit must be placed at the first branch site, and be set as master unit, while the other are set as slave units. Take 38HP…
-
4. Installation space
Ensure enough space for maintenance. The modules in the same system must be on the same height. When installing the unit, leave enough space for maintenance. Unit: in.(mm) (Air outlet) (Air inlet) 4(100)< (Air inlet) 39-3/8(1000)< Installation and maintenance surface >39-3/8(1000) >4(100)…
-
unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely H-h). Please make the air director on site. Unit: in.(mm) If miscellaneous articles are piled around the outdoor unit, such articles must be 800mm below the top of the outdoor unit. The articles…
-
5. Air ventilation assembly installation
The ventilation assembly is provided at the field installation. When installing, please take off the mesh cover firstly, and then install the unit as the following method. Example A Unit: in.(mm) Support 47-5/8(1210) C A Radius 3-9/16(90) 28-9/16(725) B 4(100) Air outlet louver dimension (optional)…
-
12 ST3.9 self-threading screws 3/8(10) 12-Φ1/8(3.2) Remove the two iron filters firstly 765 3/8(10) 393 16-3/16 8-3/8 16-3/16 (411) (213) (411) 16-3/16 8-3/8 16-3/16 (411) (213) (411) 49-7/32(1250) Unit: mm Example A Example B A A≥ 300 A A≥300 B B≥250 B B≥250 C C≤3000 C C≤3000 D 725≤D≤760 θ θ≤15° θ…
-
6. Refrigerant piping installation
-
2. The equivalent length of each branch pipe is 0.5m
-
Indoor unit main pipe
-
6.3 Example
-
6.4 Piping connection between outdoor units
All connection pipes between outdoor units should be horizontally, it is not allowed the concave at junction site. The height of each connection pipe between outdoor units is not allowed to over the height of refrigerant outlet pipe. √ Correct way Correct way × Wrong way × Wrong way . 6.5 Branch…
-
tg
Installation Procedure 116
-
7. Caution for brazing
Make sure to blow through with nitrogen when brazing. Blowing through with nitrogen prevents the creation of large quantities of oxidized film on the side of the pipe. An oxidized film adversely affects valves and compressors in the refrigerating system and prevents proper operation. The…
-
8. Remove dirt or water in the piping
Make sure there is no any dirt or water in the pipe before connecting the piping to the outdoor units. Wash the piping with high pressure nitrogen, never use refrigerant of the outdoor unit to do that. Installation Procedure 118
-
9. Gas tightness test
Charge 40kgf/cm2 nitrogen gas from the high-pressure gas valve from the meter connector. Pressure inside should be maintained no less than 24 hrs. MS Nitrogen Indoor unit Liquid pipe Nitrogen High-pressure gas pipe Nitrogen Low-pressure gas pipe Note: Pressurized nitrogen (3.9MPa; 40kgf/cm2) is…
-
10. Vacuum
Use the vacuum pump which vacuum level lower than -0.1MPa and the air discharge capacity above 40L/min. The outdoor unit is not necessary to vacuum, don’t open the outdoor unit gas and liquid pipe shut-off valves. Make sure the vacuum pump could result as -0.1MPa or below after 2 hours or…
-
Respectively connect the vacuum pump in the gas balance valve and oil balance valve
Perform the pump (last for 10 minutes or above) Close the pressure gauge and vacuum pump in turn Open the gas balance valve and oil balance valve of the outdoor unit Remove the pressure gauge and vacuum pump After the system power outages, switch the code S5 . After the system is powered on, press…
-
11. Additional refrigerant charge
Calculate the additional refrigerant charge according to the diameter and the length of the liquid side pipe of the outdoor/indoor unit connection. The refrigerant is R410A. Note: Assume equivalent pipe length of the branch joint is 0.5m, and MS is 1m (for calculation purposes). The refrigerant…
-
12. Electric wiring installation
12.1 Wiring terminals instruction A B C N Outdoor units Network centralized accounting monitoring Three-phase power supply Indoor units Outdoor units Indoor units centralized communication communication contros 12.2 Electric characteristics Units Model MVUR252B-VA3 MVUR280B-VA3 MVUR335B-VA3…
-
FLA: Full Load Amps. (A)
KW: Rated Motor Output (KW) 12.3 Electric wiring installation Note: Please select power supply for indoor unit and outdoor unit separately. The power supply should have specified branch circuit with leakage protector and manual switch. The power supply, leakage protector and manual of all the…
-
Power facilities 1
Outdoor unit GND (with leakage protector) Outdoor unit Leakage protector Manual switch GND Outdoor unit GND Outdoor unit GND Branch box Outdoor unit GND Power facilities 2 (with leakage protector) Outdoor unit GND 12.3.2 Indoor unit powering supply wiring Leakage protector Manual switch 1 2 Branch…
-
The shield net should be grounded at the wiring terminal of outdoor unit. The inlet and outlet wire net of indoor communication wire should be connected directly and could not be grounded, and form open circuit at the shield net of final indoor unit. 12.4.1 Signal wire between outdoor unit and…
-
Outdoor Unit
-
12.5 Dial switch setting
S1: Starting time setting S1 Starting time is 10 minutes S1 Starting time is 12 minutes (default) S2: Night silent time setting S2 Night silent time is 6h/10h (default) S2 Night silent time is 6h/12h S2 Night silent time is 8h/10h S2 Night silent time is 8h/12h S3: Silent mode selection S3 Night…
-
Only 0, 1, 2, 3, 4 are available
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP ENC4: Network address setting Only 0, 1, 2, 3, 4, 5, 6, 7 are available. 129 Installation Procedure
-
13. Running test
13.1 Inspection and confirmation before commissioning Check and confirm that refrigeration pipe line and communication wire of indoor and outdoor units have been connected to the same refrigeration system. Otherwise, operation troubles shall happen. Power voltage is within ±10% rated voltage. …
-
Calculate the critical thickness through following steps, and take necessary actions
1. Calculate the refrigerant charge A 2. Total refrigerant charge = delivered refrigerant charge (nameplate) + supplemental refrigerant charge Leakage detector alarming device 3. Calculate the indoor volume (B) (as the minimum volume) related to mechanical ventilator 4. Calculate the refrigerant…
-
1. Select installation position
1. 2. 3. 4. A place can provide enough installation and maintenance space. Horizontal ceiling and its building construction is able to withstand the set’s weight. A place where the connecting pipes and drain pipes can be connected easily. The installation location should consider the length of the…
-
3. Body installation
3.1 Install the Φ10mm hoisting screw 1. Please useΦ10mm hoisting screw. 2. Remove the ceiling: For different architectural structure, details please contact with indoor decoration personnel. Ceiling: For make sure the ceiling level and for avoiding to the ceiling vibration, it must be strengthened…
-
3.4 Hanging the MS
1. Adjust the nut’s site, the interval between gasket (Down Side) and the ceiling should according to actual construction. Hanging Bolt Nut(Up Side) Gasket(Up Side) Installing lug Gasket(Down Side) Nut(Down Side) Down Side of the ceiling 2. 3. Hang the nut of hanging screw bolt into the slotted hole…
-
Unit: in.(mm)
6. Central install the drain pipes please follow below diagram to match pipes. As long as possible (about 4(100)) Downside gradient over 1/100 VP30 Unit: in.(mm) 7. The end of the drain pipe should leave the ground or the bottom of the drain tank more than 50mm, and should not put into the water.…
-
indoor unit
max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max…
-
Apply refrigerant oil
c) d) 2. 3. a) When connecting or disconnecting the pipe, be sure to use two spanners concurrently. Do not rest the weight of the connective pipe on the adapter of the indoor unit. Too heavy load on the adapter of the indoor unit may deform the pipe and thus affect the cooling/heating effect. The…
-
5.4 Pipe connection
1. Flare Use a pipe cutter to cut off the pipe. 90 Slant Coarse Burr Pull the pipe into the rear flare of the connective nut. A mm Outer diameter mm Max. Min. Φ6.35 8.7 8.3 Φ9.53 12.4 12.0 Φ12.7 15.8 15.4 Φ15.9 19.0 18.6 Φ19.1 23.3 22.9 90 °± 4 45 ° ±2 A R1/61~1/32inch (0.4~0.8mm) 2. Tighten the…
-
Protect with wet
towel when brazing Pipe connection from outdoor unit Low pressure gas pipe connection(Brazing) High pressure gas pipe connection(Brazing) Liquid pipe connection(Brazing) Pipe connection to intdoor unit Gas pipe(Flare) Liquid pipe(Flare) 5.6 Airtight test The refrigerant pipe after installation and…
-
6.1 Power supply specifications
The power supply cable specifications are as follows. In case power capacity is too low may result in over-heating of piping that would be burned out the unit. Item Model Power supply (V/Ph/Hz) Power switch Power supply cable Capacity Safety (A) fuse (A) Power wire Ground wire MS02/N1-C…
-
Note: 1. The signal wire must use shielding wire. User other wires might cause signal interference and lead to malfunction. 2. All the shielding wires network should be interconnected, and finally connected together to the metal plate grounding. 3. Do not tie up the signal wire together with the…
-
6.4 Spot check instruction
MS Spot check keys SW1-SW6 are separately corresponded to No.1-6 system No. Content 1 The quantity of downstream indoor units of this MS 2 The operation mode of this MS 3 Subcooling inlet temperature (T1C2) 4 Subcooling outlet temperature (T1C1) 5 Total T2(B) average value back from outdoor unit 6…
-
8. Trial running
Use the wired controller to control the operation of the unit, check the following items according to the instruction. If there is error, check the error according to the instruction and solve them. 8.1 Indoor unit 1) Check whether the switch of the wired/remote controller is normal; 2) Check…
-
1. Outdoor electric control box assembly instructions
8/10/12HP Bottom layer of electric control box Top layer of electric control box No. Content 1 Electric control box assembly 2 Three phase bridge 3 Inverter module 4 Outdoor current detection board 5 Outdoor power supply board 6 DC fan module 7 Intermediate adapter board 8 Temperature sensor 9…
-
14/16HP
Bottom layer of electric control box Top layer of electric control box No. Content 1 Electric control box assembly 2 Inverter module 3 Three phase bridge 4 Temperature sensor 5 Outdoor power supply board 6 Outdoor current detection board 7 Outdoor power supply board 8 DC fan module 9 Intermediate…
-
2. Outdoor main control board instructions
2.1 Main PCB ports instructions Troubleshooting 150
-
Outdoor main PCB ports instructions
No. Port code Content Port voltage 1 CN10 Discharge temperature detection port of inverter compressor A DC 0~5V (in dynamic change) 2 CN11 Discharge temperature detection port of inverter compressor B DC 0~5V (in dynamic change) 3 CN4 Inverter module temperature detection port DC 0~5V (in dynamic…
-
Troubleshooting
S7 chip Communication switch Dial S4 S2 ENC4 ENC2 S1 ENC1 ENC3 S12 S3 Dial switch Dial switch Main control chip drive chip Inverter LED digital tube display Spot Check button Forced cooling button MIV V5 Heat Recovery DC Inverter R410A DM14-01.01.18en 2.2 Main PCB parts instructions 152
-
2.2.1 Spot check content instructions
No. Normal display Content (present frequency) Note 1 0-- Outdoor unit address 0, 1, 2, 3 2 1-- Outdoor unit capacity setting Refer to note 1 3 2-- Outdoor unit quantity Available for main outdoor unit 4 3-- Running mode Refer to note 2 5 4-- Total capacity of outdoor units Capacity requirement 6…
-
When the outdoor unit is in standby, the first two numbers on LED digital tube will display the address of the outdoor unit, and the last two numbers display the indoor unit’s quantity which can communicate with outdoor unit. When the outdoor unit is operating, it will display the rotation frequency…
-
Dial switch setting
ENC3+S12: Indoor unit quantity setting ENC3 S12 ENC3 S12 ENC3 S12 ENC3 S12 The quantity of indoor unit is 0-15 The quantity of indoor unit is 16-31 The quantity of indoor unit is 32-47 The quantity of indoor unit is 48-63 ENC1: Outdoor unit address setting Only 0, 1, 2, 3 are available. 0 is for…
-
2.3 LED on main control board instructions
LED3 LED2 LED1 LED5 LED7 LED4 LED6 LED1: Power supply indicator lamp. The lamp will be on if the power supply is normal. LED2: Running indicator lamp. The lamp will be on if the system running is normal. LED3: Malfunction indicator lamp of network centralized control chip. The lamp will flash in…
-
3. Error code table
Error code Content E0 Communication error between outdoor units E1 Phase sequence error Display on the faulty unit, all the ODUs are in standby. Communication error between indoors and the Only display on the master unit, all the ODUs are in master unit. standby. E2 E4 Outdoor ambient temperature…
-
L1
DC generatrix low voltage error Display after P6 displaying for one minute L2 DC generatrix high voltage error Display after P6 displaying for one minute L3 Reserved - L4 MCE error/ synchronization/ closed loop Display after P6 displaying for one minute L5 Zero speed protection Display after P6…
-
4. Troubleshooting
4.1 E0: Communication error between outdoor units The error only display on faulty slave unit, all the ODU will be standby. E0: Communication error between outdoor units ODU addresses (ENC1) are set incorrectly (the master unit address should be set as 0, slave units addresses should be set from 1…
-
4.2 E1: Phase sequence error
The error only display on faulty unit, all the ODU will be standby. E1: Phase sequence error The 3-phase sequence of power supply is wrong. (The A, B, C terminal of three-phase power supply should meet compressor phase sequence requirement. If the phase sequence is adverse, the compressor will…
-
4.3 E2: Communication error between indoors and the master unit
The error only display on faulty slave unit, all the ODU will be standby. E2: Indoor units and outdoor unit communication error Communication wires P, Q, E are short circuit or disconnected (Measure the resistance among P Q and E, the normal resistance is 120Ω) Yes Reconnect the communication wires…
-
Note
1. Press the manual button on display board of indoor unit for 5 seconds, the communication address code of indoor unit will display; Codes are as follows: Indicator light Running Timer Fan/defend cold fan Warning Code Buzzer Communication address Four LED display Not warning 00---15 Normally on Not…
-
Pressing continued the manual button for 10 seconds
If all the LED lights turn off, that means the capacity code is 0 and the capacity of indoor units is 22×100W(7510Btu/h); If the “Timer” and “Alarm” lights are normally on, that means the capacity code is 5=(4+1) and the capacity of indoor unit is 71×100W(24230Btu/h); If the “Operation” and…
-
4.4 E4: Temperature senor (ambient temperature sensor T4, pipe temperature sensor T3/T5)
E7: Discharge temperature sensor error The error only display on faulty unit, all the ODU will be standby. E4/H7: Temperature sensor error Temperature sensor port on main PCB are loose Fasten the temperature sensor port Yes No Temperature sensor is short circuit or disabled (Using a multimeter to…
-
4.5 E5: Voltage error
The error only display on faulty unit, all the ODU will be standby. E5: Voltage error Voltage of power supply is too high or too low (the normal voltage between A and N (B and N, C and N) should be 198V~242V) Yes Provide normal power supply No Check the high voltage circuit. Whether the compressor…
-
4.6 E8: Outdoor unit address is wrong
The error only display on faulty slave unit, all the ODU will be standby. E8: Outdoor unit address is wrong The ODU's address is more than 3 or be set repeatedly Yes The addresses should be set less than 3 and differently Yes Replace or reconnect communication wires No The communication wires H1, H2…
-
4.8 H0: Communication error between main control chip and inverter driver chip
H1: Communication error between main control chip and communication chip The error only display on faulty unit, all the ODU will be standby. H0/H1 Power supply for main transformer is abnormal① PCB and Yes Provide normal power supply No The transformer is damaged② Yes Replace the transformer No…
-
4.9 H2: Quantity of outdoor unit decreased; H3: Quantity of outdoor unit increased
The error only display on master unit, all the ODU will be standby. H2/H3 Yes Communication wire between outdoor units is loosen Fasten the communication wire No Some outdoor units’ addresses (ENC1) are setting repeatedly Yes Set the addresses (ENC1) differently No Some outdoor units in combination…
-
4.10 H7: Quantity of indoor units decrease error
The error only display on master unit, all the ODU will be standby. It will display when the quantity of indoor units decrease above 3 minutes. H7: Quantity of indoor units decrease error Communication terminals P Q E are loose Yes Fasten the communication terminals Yes Set the IDU addresses…
-
4.11 H8: High pressure sensor error
When the discharge pressure is lower than 0.3MPa, the system will display H8 error, the ODU in standby. When the discharge pressure is back to normal, H8 disappears and normal operation resumes. H8: High pressure sensor error High pressure sensor connection port on main control board is loose Yes…
-
4.12 XHd: Slave units malfunction (X stands for corresponding slave unit)
XHD is only displayed on master unit. X stands for corresponding slave unit. If X is 1, it means no.1 slave unit has problem, then you should check no.1 slave unit. 4.13 P1: High pressure protection When the pressure is over 4.4MPa, the system will display P1 protection, the ODU in standby. When the…
-
4.14 P2/H5: Low pressure protection
When the pressure is lower than 0.05MPa, the system will display P2 protection, the ODU in standby. When the pressure is higher than 0.15MPa, P2 disappears and resumes normal operation. H5 error will display when system appear 3 times P2 protection in 60 minutes, it cannot resume automatically, and…
-
compressor) P3: When the current of inverter compressor is over 12A, the system will display P3 protection, the ODU in standby. When the current goes back to normal range, P3 disappears and normal operation resumes. P3: Compressor current protection Yes The indoor load is too large① Make sure the…
-
4.16 P4: Discharge temperature protection; H6: P4 protection appears three times in 100 minutes
The error only display on faulty unit, all the ODU will be standby. H6 error cannot resume automatically, and it can resume only by restarting the machine. P4/H6 Discharge temp. sensor is short circuit or disabled①. Yes Replace the sensor No System is lack of refrigerant②. (Refrigerant recharging is…
-
4.17 P5: Condenser temperature protection
When condenser temperature is over 65oC, the system will display P5 protection, the ODU in standby. When the temperature goes back to normal range, P5 disappear and normal operation resumes. P5: Condenser temperature protection Yes T3/T5 port on main control board is loose Fasten the T3/T5 port No…
-
4.18 XP6: Inverter module protection (When X is 1, it means A inverter module; 2 means B inverter
module) H4: P6 protection appears three times in 60 minutes When the system displays H4 error code, the system can resume only by restarting the machine. At this time, malfunction should be disposed promptly to avoid further damage. H4 will display if P6 occur 3 times in 60 minutes Check whether…
-
1) L0 troubleshooting
Step 1: Compressor check Measure the resistance between each two of U, V, W terminals of the compressor, all the resistance should be the same and equal to 0.9~5 Ohms. (Fig. A and Fig. B) Measure the resistance between each of U, V, W terminals of the compressor to ground (Fig. C), all the…
-
2) L1/L4 troubleshooting
Step 1: Check the DC voltage between 1 and 2 terminal, the normal value should be 510V~580V, if the voltage is lower than 510V, go to step 2. 1 2 Step 2: Check whether the wires of rectifier circuit are loose or not. If wires are loosen, fasten the wires. If wires are OK, replace the main PCB.…
-
3) L2 troubleshooting
Step 1: Check the DC voltage between 1 and 2 terminal, the normal value should be 510V~580V, if the voltage is higher than 580V, go to step 2. 1 2 Step 2: Check the voltage between the two electrolytic capacitors, the normal value should be 510V~580V. Turn the measure range of the meter to 1kV…
-
system B, make sure that the U, V, W terminals are connected in right order, then start system B
If compressor A can start normally, that means compressor is OK, the control box of system A is malfunction, then raplace the main PCB of system A with correct wire connection. If compressor A can not start normally, that means compressor A is demaged, needs to be replaced. System A System B Connect…
-
bad, the oil need to be replaced
The oil is black, it has been carbonized The oil is a little yellowing, but it is clear and transparent, the quality is OK Theoil oilisisstill stilltransparent, transparent,but The but there is impunity thethe there is impunity in theinoil, oil, the impunity impunity may clogmay the clog filter the…
-
The
The crankshaft crankshaft is worn. is A normal bearing of the compressor A clean filter (on the suction pipe of the system) Troubleshooting The scroll plate of is worn. the The bearing is worn seriously, it is damaged completely The filter is blocked by impunity, the suction and of the exhaust…
-
Step 3: Replace the compressor
Pour out some oil from each compressor (Inv & Fix); check the quality of the oil The oil is clean The oil is dirty Pour out all of the oil from the compressor, oil separator and gas-liquid separator Check the filter between the ball valve and the 4-way valve The filter is clean The filter is blocked…
-
3. Add oil to the compressor from the discharge pipe
The discharge pipe is connected to the oil pool of the compressor by the inner oil balance pipe, add oil from the discharge pipe with a funnel 4. The type of the oil is FVC-68D, make sure the type of the oil is right because different compressor need different type of oil, if the type is wrong there…
-
If the system display three times P9 protection in 60 minutes, the system will stop and display H9 error code. When the system displays H9 error code, the system can resume only by restarting the machine. At this time, malfunction should be disposed promptly to avoid further damage. P9/H9: Fan…
-
P9 protection analysis
Conditions Fault indicator Power supply Digital lamp of fan indicator lamp tube module of fan module display Malfunction analysis Check the power supply circuit for fan module. Power on Off Off Quantity Check whether there has power supply for lightning of IDU or protection plate, whether the…
-
4.20 PL/C7: Temperature protection of main inverter module
When the temperature of inverter module is over 80oC, it will display PL protection. If the system display three times PL protection in 100 minutes, the system will stop and display C7 error code. When the system displays C7 error code, the system can resume only by restarting the machine. PL/CL…
-
Attached table 1: Resistance value of ambient temperature and pipe temperature sensor
-
Attached table 2: Resistance value of compressor discharge temperature sensor
-
Attached table 3: Commissioning and operating parameters of refrigerant system
Conditions 1: Make sure outdoor unit can detect all the indoor units, the quantity of indoor units display steadily and be equal to actual quantity of installed indoor units. Conditions 2: Make sure all the valves in outdoor unit are open, indoor units EXV have connected to indoor PCB. Conditions 3…