Инструкция на Чиллеры MDV (сервис мануалы)
Модульные чиллеры MDV серии MDC-SS35/RN1L, MDC-SS65/RN1L, MDC-SS80/RN1L, MDC-SS130/RN1 с воздушным охлаждением. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1.Nomenclature
-
MCAC-ATSM-2014-05 External Appearance 25/35kW module 65/80kW module 130kW module External appearance 3
-
4.Features
4.1 New structure design The module adopts new structure design, H shape condenser, 360O air suction, increased the heat exchanging area, efficiently enhanced the heat exchange efficiency. 4.2 Modular design, flexible combination The unit adopts modular design, which can make more units to connect…
-
When unit is under protection
If master unit’s protection happens, this unit will stop but the others will keep running. If slave unit’s protection happens, this unit will stop but the others will keep running. ( Except PE, P9 protection happens) PE:Low temperature protection of evaporator. P9:Outlet and inlet water…
-
Inner grooved copper tube
MCAC-ATSM-2014-05 Hydrophilic aluminum foil 4.7 EXV more precisely flow control Patented liquid distribution components to maximize performance and minimize defrost impact. 500 steps EXV plus capillary for stable and accurate gas flow control. Fast respond resulting in higher efficiency and improved…
-
4.10 Applicable temperature range
Mode Ambient temperature range Water outlet temperature range 0˚C ~17˚C (7˚C is default, less than 5 ˚C must add the antifreeze, SS Cooling series.) -10˚C ~46˚C 5˚C ~17˚C(SP series) Heating -15˚C ~24˚C 25˚C ~50˚C (45˚C is default) Ambient temp. range -10 ˚C -15 ˚C Cooling range Heating range -15 ˚C…
-
4.13 Built-in hydraulic module
The modules are fully integrated and built-in hydraulic module, such as expansion tank, plate heat exchanger, water circulating pump, etc. It saves installation space and cost. (Available for MDC-SP25M-RN1L &MDC -SP35M-RN1L) Terminal Two-way valve Water charge valve Three-way valve 0.15MPa< Water…
-
5.Specifications
SS series Model MDC-SS35/RN1L MDC-SS65/RN1L Cooling Capacity kW 35 65 Heating Capacity kW 37 69 Cooling kW 11.5 20.4 Cooling rated current A 19.0 36.5 Heating kW 11.3 21.5 Heating rated current A 20.0 37.2 EER kW / kW 3.04 3.19 COP kW / kW 3.27 3.21 Power supply V/Ph/Hz 380-415/3/50 380-415/3/50…
-
Weight
Connection wiring MCAC-ATSM-2014-05 Packing size(D×H×W) mm 1070×1900×1030 2090×1890×1030 Net weight kg 320 530 Operation weight kg Power wire Signal wire 330 590 mm 2 10×4+16×1 35×4+16×1 mm 2 0.75×3-core with shielding 0.75×3-core with shielding Wired controller Wired controller Control type 1)…
-
Model
MDC-SS80/RN1L MDC -SS130/RN1 Cooling Capacity kW 80 130 Heating Capacity kW 85 138 Cooling kW 25.8 42.3 Cooling rated current A 43.8 73 Heating kW 26.5 43 Heating rated current A 40.0 74.4 EER kW / kW 3.1 3.07 COP kW / kW 3.21 3.21 Power supply V/Ph/Hz 380-415/3/50 380-415/3/50 Power input Power…
-
Connection
wiring Power wire Signal wire MCAC-ATSM-2014-05 mm 2 25×4+16×1 35×4+16×1 mm 2 0.75×3-core with shielding 0.75×3-core with shielding Wired controller Wired controller Control type 1) Protection for over-high discharge pressure. 2) Protection for over-low suction pressure. 3) Power supply phase…
-
6.Dimensions
-
65/80kW module
-
130kW module
-
7.Refrigeration System Sketch Drawing
SS series 7.1 35kW module refrigeration system sketch drawing Each module has one compressor with one separate unit, one refrigerant system. Fan Condenser 4-way valve Compressor Water outlet Water inlet EXV Capillary Evaporator (Double-pipe heat exchanger) Low pressure cylinder 7.2 65/80kW module…
-
Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) 130kW module refrigeration system sketch drawing Each module has two compressors with one unit, one shell-tube evaporator for two refrigerant systems. low pressure cylinder B Compressor B Fan A Fan B EXV Capillary Condenser Compressor A…
-
8.Wiring Diagrams
8.1 Wiring Diagrams SS series MDC -SS35/RN1L 22 Wiring Diagrams
-
Wiring Diagrams 23
-
24 Wiring Diagrams
-
MDC -SS130/RN1
Wiring Diagrams 25
-
8.2 Networking Communication Schematic
SS series Wiring Diagrams 31
-
9.Electric Characteristics
SS series Model Outdoor Unit Power Supply Compressor OFM Hz Voltage Min. Max. TOCA MFA LRA RLA kW FLA MDC-SS35/RN1L 50 380-415 21.4 0.8 3.7 MDC -SS65/RN1L 50 380-415 342 456 54.5 100 260 44.3 0.8 3.7 MDC -SS80/RN1L 50 380-415 27.6 0.8(×2) 3.7(×2) MDC -SS130/RN1 50 380-415 44.3 2.59(×2) 4.8(×2)…
-
10.Capacity Tables
10.1 Cooling SS series MDC-SS35/RN1L Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW 5.00 39.18 10.13 36.90 10.44 34.81 10.76 32.90 11.10…
-
Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW 5.00 72.77 17.97 68.52 18.52 64.64 19.10 61.10 19.69 57.25 20.67 52.67 21.70 6.00 75.23…
-
Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW 5.00 89.56 22.72 84.34 23.43 79.56 24.15 75.20 24.90 70.46 26.14 64.83 27.45 6.00 92.59…
-
Ambient temp.(℃) Chilled water outlet temp. 21.00 25.00 30.00 35.00 40.00 46.00 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW 5.00 145.54 37.25 137.04 38.41 129.29 39.59 122.20 40.82 114.50 42.86 105.34 45.00 6.00…
-
10.2 Heating
SS series MDC-SS35/RN1L Ambient temp.(℃) Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW kW kW 40.00 22.95 7.07 28.69 8.03 33.75 8.93 37.51 9.70 40.77 10.21 45.66 10.83…
-
Ambient temp.(℃) Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW kW kW 40.00 42.80 13.45 53.51 15.29 62.95 16.99 69.94 18.46 76.02 19.43 85.15 20.60 97.92 22.25 41.00…
-
Ambient temp.(℃) Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW kW kW 40.00 52.73 16.58 65.91 18.84 77.55 20.94 86.16 22.76 93.65 23.95 104.89 25.39 120.63 27.42 41.00…
-
Ambient temp.(℃) Hot water outlet temp. -10 -6 -2 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power (℃) kW kW kW kW kW kW kW kW kW kW kW kW kW kW 40.00 85.61 26.91 107.01 30.57 125.90 33.97 139.89 36.93 152.05 38.87 170.29 41.20 195.84 44.50…
-
11.Exploded View
-
Part
8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 11.2 12 13 Bottom panel II ass'y Column Gas-liquid separator Suction pipe ass'y Compressor Condenser's guard plate I ass'y Condenser's guard plate III ass'y Condenser hoisting parts Upper frame welded parts Install base welding parts of water pan Seal plate Water…
-
56 Exploded View
-
2 3 3.1 3.2 6.1 6.2 6.3 7 7.1 15.1 15.1.1 15.1.2 15.1.3 15.2 15.3 15.4 15.5 15.6 15.7 15.8 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) Part Name Column Gas-liquid separator Throttle part Electronic expansion valve Strainer Pipe support Shell-tube evaporator Four-way valve ass'y…
-
58 Exploded View
-
11.1 14.1 14.2 14.3 15 15.1 15.2 15.3 15.4 15.5 15.6 15.7 15.8 15.9 15.10 18.1 Part Name Column Suction pipe ass'y Base welded parts Gas-liquid separator Compressor Pipe support IV Front panel ass'y The middle plate Electrical maintenance board Electric control box of the door Throttle parts I…
-
MDC -SS130/RN1
60 Exploded View
-
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 5.1 6 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) Part Name Condenser hoisting parts Upper frame ass'y Motor(three-phase asynchronous) Axial-flow fan Out of wind…
-
12.Trouble Shooting
12.1 Failure &protection codes 25/35/65/80/130kW module 72 No Code Trouble 1 E0 Error of outdoor EEPROM 2 E1 Power phase sequence error 3 E2 Communication error 4 E3 Total water outlet temperature sensor error 5 E4 Outlet water temp sensor error 6 E5 Pipe temperature sensor error in condenser A 7 E6…
-
12.2 Troubles and Solutions
Troubles Possible reasons Solutions Air or other non-condensing gas still in the system. Discharge gas from refrigerant charging inlet. Re-vacuum the system if necessary. Fins in the condenser are dirty or foreign substance Clean condenser fins. blocking fins. Over high air discharge Insufficient…
-
Short circuit comes out from motor or connecting
interface. Confirm resistors at motor are connected corresponding to terminals. Over high or over low voltage. Confirm voltage not higher or lower than the rated voltage +/-10%. Compressor stops Adjust refrigerant charge volume. because of integrate Over high air discharging pressure or excessive…
-
12.3 Typical malfunction solutions
1) High pressure and discharged temperature protection High pressure and discharged protection. Yes High pressure protection. No Discharge protection. Yes Inspect fan motor and capacitor (1phase) or start up the water pump. temperature Yes See the analysis of discharge temp. protection malfunction.…
-
Discharge
protection. MCAC-ATSM-2014-05 temperature Yes Discharge temperature switch is broken or joint is loose. Yes Replace discharge temperature switch, fixed joint. No Refrigerant is too less. Yes Detect leakage for all system, append refrigerant. Yes Replace the EXV or coil. No Couldn’t open the EXV. No…
-
2) Current protection
Current protection Yes The fin of heat exchanger is dirty or aged in cooling mode, or the shell-tube scaled strong. Yes Clean heat exchanger. Yes Check the fan motor, capacitor (1 phase) or start up water pump. Yes Empty, vacuuming and append refrigerant if necessary. Yes Check power supply, start…
-
4) Inlet &outlet water temperature difference protection
Inlet &outlet water temperature difference protection. Yes Yes Refer to the water flow malfunction to analysis. Yes Replace sensor. Water flow is lower. No The outlet water temperature sensor or inlet water temperature sensor brought drifting when collect temperature. temperature No PCB mistakes to…
-
7) Power supply phase sequence malfunction
Power supply phase sequence malfunction. Yes Phase sequence error. Yes Adjust connecting wire. No Lack of phase. Yes Check power supply. Yes Replace phase protector. No Phase lack protector is broken. lack No PCB mistakes to alarm. Yes Replace PCB. No Inform the customer service center. 8)…
-
9) Water flow detection malfunction
Water flow detection malfunction Yes Water pump didn’t open or error. Yes Open the pump or change; inspect the power supply or control circuit of pump. Yes Open the valve. Yes Replace the water flow switch, inspect the connecting wire. Yes Adjust the position. No Didn’t open the valve in system. No…
-
10) Total outlet water temperature sensor malfunction
Total outlet water sensor malfunction temperature Yes The circuit of total outlet water temperature sensor is broken. Yes Replace temperature sensor. No The circuit of total outlet water temperature sensor is shorten. Yes Replace sensor. temperature No The joint of total outlet water temperature…
-
12) The unit inlet water temperature sensor malfunction
The unit inlet water temperature sensor malfunction Yes The unit’s circuit of inlet water temperature sensor is broken. Yes Replace temperature sensor. No The unit’s circuit of inlet water temperature sensor is shorten. Yes Replace temperature sensor. No The unit’s joint of inlet water temperature…
-
14) Ambient temperature sensor malfunction
Ambient temperature malfunction. sensor Yes The circuit of ambient temperature sensor is broken. Yes Replace temperature sensor. No The circuit of ambient temperature sensor is shorten. Yes Replace temperature sensor. No The joint of ambient temperature sensor is loose. Yes Fixed joint. No Yes PCB…
-
13.Installation
13.1 Unit Installation 13.1.1 Transportation The angle of inclination should not be more than 15ºwhen carrying the unit, to avoid overturn of the unit. a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the length of each rod must be more than the…
-
E
25/35/65/80/130kW module B Input of airflow A D Input of airflow C unit Input of airflow unit Input of airflow The recommend space parameter Series SS A B Installation space (mm) C D E ≥1500 ≥2000 ≥2000 ≥1500 ≥8000 ● Space requirements for parallel installation of multiple scroll units To avoid back…
-
operating weight of the unit and the weight of maintenance personnel. Refer to the operating weight
parameters in specification table. If the unit is located so high that it is inconvenient for maintenance personnel to conduct maintenance, the suitable scaffold can be provided around the unit. The scaffold must be able to bear the weight of maintenance personnel and maintenance facilities. …
-
35kW
Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) 65/80kW 130kW 13.1.4 Installation of damping devices ※ Damping devices must be provided between the unit and its foundation. By means of the Φ15mm diameter installation holes on the steel frame of the unit base, the unit can be fastened…
-
a. All chilled water pipelines should be thoroughly flushed, to be free of any impurity, before the unit is operated. Any impurity should not be flushed to or into the heat exchanger. b. Water must enter the heat exchanger through the inlet; otherwise the performance of the unit will decline. c. The…
-
25/35/65/80/130kW module
Expansion tank Water replenishing Dirt discharge valve unit Differential pressure by-pass valve unit Drain valve Terminal Auxiliary electric heater Two-way valve Three-way valve 13.2.3 Water quality ※Water quality control When industrial water is used as chilled water, little furring may occur…
-
13.2.4 Performance adjustment factors
The antifreeze must be required according to anyone condition as following: 1. The outlet water temperature is below 5℃; 2. The ambient temperature is below 0 ℃; 3. Don’t start up the unit for a long time. 4. The power supply was cut off and needn’t change the water in system. Ethylene and Propylene…
-
Fouling phenomena are common and diverse, ranging from fouling of ship hulls, natural surfaces in the marine environment (marine fouling), fouling of heat-transfer components through ingredients contained in the cooling water or gases, and even the development of plaque or calculus on teeth, or…
-
b. To avoid electric shock and damages to the devices, the power supply should be cut off, when wires are connected or adjustment is done. c. When wiring connection is conducted, adjustment of other screws except connection terminals of micro switches and ground screws is prohibited. In the…
-
No.n module
No.(n-1) module No.1 module No.(n-1) address No.(n-2) address No.0 address Drill dead hole at the position, and move the total effluent temperature sensor at No.0 address to the position Water flow switch Pump 13.2.7 Installation of water system pipeline for 65/80kW module Installation of…
-
No.n module
No.(n-1) module No.1 module No.(n-1) address No.(n-2) address No.0 address Drill dead hole at the position, and move the total effluent temperature sensor at No.0 address to the position Water flow switch Pump Installation mode A: less than 16 modules 13.2.9 Diameter parameters of main inlet and…
-
Please pay attention to the following items when installing multiple modules
● Each module corresponds to an address code which cannot be repeated. ● Main water outlet temperature sensing bulb, water flow switch and auxiliary electric heater are under control of the main module. ● One wired controller and one water flow switch are required and connected on the main module. ●…
-
b. In certain occasion (especially in manufacture cooling process), for conforming the system water content requirement, it’s necessary to mount a tank equipping with a cut-off baffle at the system to avoid water Error Recommendation short-circuit, Please see the following schemes: Error…
-
h1: Main unit water resistance
h2: Pump water resistance. h3: Water resistance of the longest water-loop distance, includes: pipe resistance, different valve’s resistance, flexible pipe resistance, pipe elbow and three-way resistance, two-way resistance or three-way resistance, as well as filter resistance. H4: the longest…
-
13.3.3 Requirements of wiring connection
● No additional control components are required in the electric cabinet (such as relay, and so on), and the power supply and control wires not connected with the electric cabinet are not allowed to go through the electric box. Otherwise, electromagnetic interference may cause failure of the unit and…
-
13.3.4 Wiring steps
Step Content 1 Check the unit and ensure that it is connected with grounding wires correctly, to avoid leakage, and the grounding devices should be mounted in strict accordance with the requirements of electrical engineering rules. The grounding wires can prevent electric shock. 2 The control box of…
-
1 .Wiring of “ON/OFF” weak electric port
○ Corresponding parallel connect the “ON/OFF”(dry contact input signal) port of the main unit’s electric control box, then, connect the “ON/OFF” signal (provide by user) to the “ON/OFF” port of main unit as follows. Power (DC 12V) Main control board is provided 0# electric control box “ON/OFF” port…
-
14.Commissioning
1. Preparation ● After the water system pipeline is flushed several times, please make sure that the purity of water meets the requirements; the system is re-filled with water and drained, and the pump is started up, then make sure that water flow and the pressure at the outlet meet the…
-
15.Maintenance
Maintenance for main components: ● Close attention should be paid to the discharge and suction pressure during the running process. Find out reasons and eliminate the failure if abnormality is found. ● Control and protect the equipment. See to it that no random adjustment be made on the set points…
-
● Connect vacuum pumping pipe at the fluoride nozzle at low-pressure side
● Remove air from the system pipe with vacuum pump. The vacuum pumping lasts for above 3 hours. Confirm that the indication pressure in dial gauge is within the specified scope. ● When the degree of vacuum is reached, inject refrigerant into the refrigeration system with refrigerant bottle.…
-
16.Control System
16.1 PCB Outline and Description SS series 16.1.1 35/65/130kW module PCB, outlook view 16.1.2 35/65/130kW module components description No. Detail information. 1 Detection of current of the compressor A1 (Protection code P4). Detection of current of the compressor B1 (Protection code P5). 2 Current…
-
not be affected
5 Shell-tube low-temperature ant-freeze sensor (Fault code Eb). Adjustment range of constant speed capability: ON and OFF. Adjustment range of constant speed capability: ON and OFF. Unit outlet water temperature sensor (Fault code E4). 6 Under refrigeration mode and heating mode, conduct adjustment…
-
1) Main unit: if abnormal water flow occurs for the first and second time, the main unit board will display fault code E9. 2) Subordinate unit: (Water flow detection will not be done). COM (I) 485 communication port (Fault code E2). COM (O) is interconnected with P, Q and E of COM (I), used for…
-
E
F 0 1 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) 2 D 3 C 4 B 5 6 A 9 E 26 When the address is 0, it serves as the main unit. 8 7 F D 3 C 4 When the address is 1,2,3……F, it serves as the subordinate unit 1,2,3……15. 5 B A ADDRRSS Each scroll part of scroll unit has the same electric…
-
16.1.3 80kW module PCB, outlook view
16.1.4 80kW module components description No. Detail information. 1 Detection of current of the compressor A1 (Protection code P4). Detection of current of the compressor B1 (Protection code P5). 2 Current is not detected within the initial 5 seconds after the compressor is started up. When the…
-
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water temperature. Adjustment range of constant speed capability: ON and OFF. Total outlet water temperature sensor (Fault code E3). 6 Only the main unit is valid, and the subordinate units are…
-
COM (I) 485 communication port (Fault code E2)
COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication. 1) If faults occur between the wired controller and the main unit module, all modules will be shut down. 11 2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering…
-
PWM pressure released valve control(for digital compressor) 27 Input of transformer, 220-230V AC current. (only valid for the main unit) Input of three-phase four-wire power supply (Fault code E1) Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle…
-
16.2 Wired Controller KJRM-120D/BMK-E(Standard)
KJRM-120D/BMK-E 10.ON/OFF key 1. Operation icon 2. Mode area 3. Setting temperature 4. Timing On/Off 5. Function icon 6. On-line unit qt y. 7. Reserved 8. Clock 9. Water temp. 11.Right, Left key 12.OK key 13. Setting key 14. Add, reduce key 15. Cancel key 16. Reserved key 16.2.1. Operating…
-
7) Error: When the main unit has error or protection, this icon will be displayed. The unit need to be maintained by professionals. 6 On-line unit qty. indication: Under normal status display the quantity of the units connected to the wire ○ controller; under check status display the device serial…
-
Turn on the unit
Power up to module unit and initially deliver power to wire control. Tu r n o f f t h e u n i t Press the key again until all modes are showed (i.e. Cooling, Heating and Pump modes.) Press “mode settings” key to set the intended mode. When intend to shut the unit Press “OK” key to save the settings.…
-
This time the hour of the clock will flash, it means the current setting is the hour of Timer 1“On”, press the ▲ “▲” or “▼” to adjust, press “ ” key when finished, and then the minute of the clock will flash, it means ▲ the current setting is the minute of Timer 1“On”, press the “▲” or “▼” to…
-
Main page
Press “Setting” key twice to enter hour setting interface of “Timer 1 On” ▼ Through the “▲” or “▼” key, set the hour number of “Timing 1 On” to be 07 ▼ Press “ ” key to enter minute setting interface of “Timer 1 On”, adjust the minute number to be 10 Press “ ” key to enter hour setting interface of…
-
Note
Working mode setting is valid only when the unit is power off. 4) Set clock ▲This time the hour of the clock will flash, it means the current setting is the hour of the clock, press the “▲” or ▲ “▼” to adjust, press “ ” key when finished, and then the minute of the clock will flash, it means the…
-
T ≤Ts-δ
2 T < Ts+1-δ Ts-1+δ>T ≥Ts+1-δ Ts-1+δ≤T <Tj2 T ≥Tj2 (TAL: total outlet water temperature) Operation method: Turned off, press the "Constrain" "▲" 2 button for 3 seconds to enter the hysteresis setting selection. Can be adjusted Hysteresis parameter δ = (2,3,4,5 °C). Press “ ” or ▲ “ ” key to select…
-
3) Press the “▲” or “▼” key to adjust the main unit serial number can query 16 sets main units status ▲ information from #0~#15. Press “ ” or “ ” to adjust the spot check sequence number of one main unit then can query all the status information of this unit. Spot check content according to the main…
-
Use PQE connect with each other when several wired-controllers are parallel
The wiring procedure and principles are shown in the figure: 16.2.7. Basic conditions of operating the wired controller: 1) Applicable range of supply voltage: Input voltage is 10V AC. 2) Operating environment temperature of wired controller: -10°C~+43°C. 3) Operating RH of wired controller: RH…
-
MODBUS gateway
The Modbus gateway can be customized, the MODBUS protocol built in wired controller KJRM-120D/BMK-E, it realizes intelligent network control by X Y E ports. It can connect max. 16 wired controllers, each wired controller can control max.16 units. Max. 16 Max. 16 units Modbus gateway (P Q E) (X Y E)…
-
16.3 Wired controller KJR-120A/MBTE(Optional)
16.3.1 NAMES OF KEYS ON THE WIRED CONTROLLER AND THE KEYPAD OPERATION DESCRIPTION R 1 ON/OFF TEMP SET 6 8 OK TIMER SET 7 9 CANCEL MODE 2 12 PAGEUP ALARM CLEAR 3 13 PAGEDOWN QUERY 4 11 ADDRESS / - CLOCK 5 10 ADDRESS/+ TIMER QUERY 17 18 TIMER SWITCH 16 ADDRESS SET 14 HYSTERESIS LOCK HYSTERESIS ADDRESS…
-
Press the button, inquire state information of No. 0 to No. 15 outdoor units (the default is state information of No.0 unit) and enter inquiry state. After entering inquiry state, inquire the information of the former unit or the following unit through “ADDRESS/+” and “ADDRESS/-”. After a certain…
-
Press this button at Check mode, when select the next scroll, the operation status of the next scroll will display; if the current scroll is 15#, and the next one is 0#. Press this button for add address at wire address setting mode. If the wired controller address is 15, press this key will display…
-
Press the button can open the weekly timer function or close the weekly timer function
16.3.2. OPERATION PROCEDURE OF WIRED CONTROLLER ● Operation procedure of mode setting 1. Press MODE at shutdown status, you could select appropriate mode as you want. The function is invalid at startup status. 2. The mode which you can select depends on outdoor unit. ● Operation procedure of water…
-
16.3.3 The adjusting logic of heating mode: (the parameter of δ1,δ2,Tj1 and Tj2 are decided by the
3: The adjusting logic of heating mode: outdoor unit) (the parameter of δ1,δ2,Tj1 and Tj2 are decided by the outdoor unit) T ≤Ts-δ 2 T < Ts+1-δ Ts-1+δ>T ≥Ts+1-δ Ts-1+δ≤T <Tj2 T ≥Tj2 (TAL: total outlet water temperature) ● Fault alarm handling ● Fault alarm handing 1.When failsfails or theor wired…
-
16.3.5 NAME AND FUNCTION DESCRIPTION OF LCD SCREEN OF WIRED CONTROLLER
Display operation mode Display operation status Display time data Display query data 16.3.6 INSTALLATION PROCEDURE Installation procedure: Outdoor unit Outdoor unit #00 #01 Outdoor unit #02 Outdoor unit #15 Wired Controller #00 Use PQE connect with the outdoor units. NOTE: Please connect the…
-
Black
Yellow Gray Outdoor electric control box Please use 3-cord with shielding wire for connection. The wire length depends on the specific situation in the installation. Communicate with upper unit(reserved). If it is under the host computer network control, displays, otherwise there is no display. X YE…
-
WEEKLY TIMER SETTING
TIMER SET Set Timer Period 2 ADDRESS/+ or ADDRESS/- Select week ADDRESS/+ or ADDRESS/- Set Period 2 start hour OK Y OK or ADDRESS/- Set Period 1 start hour ADDRESS/+ Y ADDRESS/+ or ADDRESS/- Set Period 2 start minute OK Y OK or ADDRESS/- Set Period 1 start minute ADDRESS/+ Y ADDRESS/+ or ADDRESS/…
-
NOTE
In operating, press the key "CANCEL", to turn back to the previous step or the normal display interface. 1.Before power failure of the heating water system or wired controller, the wired controller memorizes the status of the unit automatically, and sets the water temperature value except timing…
-
2.Temperature-Resistance characteristic sheet for pipe temperature sensor,ambient temperature
sensor,inlet water temperature sensor and outlet water temperature sensor. Sensor characteristic sheet Unit:Temp:℃--K, Ratio:KΩ 164 Temp. Ratio Temp. Ratio Temp. Ratio Temp. Ratio -20 115.266 20 12.6431 60 2.35774 100 0.62973 -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5 62…
-
3.Temperature-Resistance characteristic sheet for discharge temperature sensor of digital
compressor. Sensor characteristic sheet Unit:temp:℃--K, Ratio:KΩ Tem. -40 -39 -38 -37 -36 -35 -34 -33 -32 -31 -30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 Appendix Ratio 2889.60000 2704.61400 2532.87200 2373.34200 2225.07800…